UNIQUE CAD & DESIGN
911PERMIT@GMAIL.COM
2482
1

UNIQUE CAD & DESIGN
FLOOR PLAN
KEYNOTES
911PERMIT@GMAIL.COM
2482
2

8725 W C P Hayes DR -
Tolleson AZ.
Guess House
AC Load Calculations
for
Haro Arredondo Irvin E
Prepared By:
AC. Design
351 N Meridian Dr
Apache Juntion Arizona
85120
Tuesday, May 5 , 2026

Rhvac - Residential HVAC Loads - A.J.az. Page 2
Project Report
General Project Information
Project Title: 8725 W C P Hayes DR
Designed By: AC Desgns .
Project Date: 05.05.2026
Client Name: Haro Arredondo Irvin
Client Address: 8725 W C P Hayes DR
Client City:
Company Name: AC. Design
Company Address: 351 N Meridian Dr
Company City: Apache Juntion
Company E-Mail Address: Arizona 85120
Design Data
Reference City: Tolleson , Arizona
Building Orientation: Front Door , faces North
Daily Temperature Range: Hight
Latitude: 33 Degrees
Elevation: 1106 ft.
Altitude Factor: 0.961
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter: 41 38.4 n/a n/a 70 n/a
Summer: 108 70 14% 45% 75 -7
Check Figures
Total Building Supply CFM: 579 CFM Per Square ft.: 2.019
Square ft. of Room Area: 287 Square ft. Per Ton: 283
Volume (ft³): 2,292
Building Loads
Total Heating Required Including Ventilation Air: 5,850 Btuh 5.850 MBH
Total Sensible Gain: 12,227 Btuh 100 %
Total Latent Gain: -58 Btuh 0 %
Total Cooling Required Including Ventilation Air: 12,227 Btuh 1.02 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2.50, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\ ..2482- irvin's guess house - Tuesday, May 5 , 2026

Rhvac - Residential HVAC Loads - A.J.az. Page 3
Miscellaneous Report
System 1 System 1 Outdoor Outdoor Outdoor Indoor Indoor Grains
Input Data Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter: 41 38.4 80% n/a 70 n/a
Summer: 108 70 14% 45% 75 -6.89
Duct Sizing Inputs
Main Trunk Runouts
Calculate: Yes Yes
Use Schedule: Yes Yes
Roughness Factor: 0.00300 0.01000
Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft.
Minimum Velocity: 0 ft./min 0 ft./min
Maximum Velocity: 900 ft./min 750 ft./min
Minimum Height: 0 in. 0 in.
Maximum Height: 0 in. 0 in.
Outside Air Data
Winter Summer
Infiltration Specified: 0.610 AC/hr 0.320 AC/hr
23 CFM 12 CFM
Infiltration Actual: 0.610 AC/hr 0.320 AC/hr
Above Grade Volume: X 2,292 Cu.ft. X 2,292 Cu.ft.
1,398 Cu.ft./hr 733 Cu.ft./hr
X 0.0167 X 0.0167
Total Building Infiltration: 23 CFM 12 CFM
Total Building Ventilation: 0 CFM 0 CFM
---System 1---
Infiltration & Ventilation Sensible Gain Multiplier: 34.87 = (1.10 X 0.961 X 33.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier: -4.50 = (0.68 X 0.961 X -6.89 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier: 30.65 = (1.10 X 0.961 X 29.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.610 AC/hr (23 CFM), Construction: Average
Summer Infiltration Specified: 0.320 AC/hr (12 CFM), Construction: Average
Duct Load Factor Scenarios for System 1
Attic Duct Duct Surface From
No. Type Description Location Ceiling Leakage Insulation Area [T]MDD
1 Supply Attic 16B 0.12 8 21.7 MDD
C:\ ..2482- irvin's guess house -
Tuesday, May 5 , 2026

Rhvac - Residential HVAC Loads - A.J.az. Page 4
Load Preview Report
Sys Sys Sys
Net ft.² Sen Lat Net Sen Duct
Htg Clg Act
Scope Ton /Ton Area Gain Gain Gain Loss Size
CFM CFM CFM
Building 1.02 283 287 12,227 -58 12,227 5,850 79 579 579
System 1 1.02 283 287 12,227 -58 12,227 5,850 79 579 579 12
Supply Duct Latent -3 0
Not MDD:
Zone 1 287 12,227 -55 12,227 5,850 79 579 579
9x13
1-Room ( kitchen , bath and bedroom) 287 12,227 -55 12,227 5,850 79 579 579 13
C:\ ..2482- irvin's guess house - Tuesday, May 5 , 2026

Rhvac - Residential HVAC Loads - A.J.az. Page 5
System 1 Room Load Summary
Htg Min Run Run Clg Clg Min Act
Room Area Sens Htg Duct Duct Sens Lat Clg Sys
No Name SF Btuh CFM Size Vel Btuh Btuh CFM CFM
---Zone 1---
1 Room 1 287 5,850 79 13 - 12,227 -55 579 579
Duct Latent -3
System 1 total 287 5,850 79 12,227 -58 579 579
System 1 Main Trunk Size: 12 in.
Velocity: 737 ft./min
Loss per 100 ft.: 0.068 in.wg
Duct size results above are from Manual D Ductsize.
Runout duct velocities are not printed with duct size results from Manual D Ductsize since they can vary within the room.
See the Manual D Ductsize report for duct velocities and other data.
Cooling System Summary
Cooling Sensible/Latent Sensible Latent Total
Tons Split Btuh Btuh Btuh
Net Required: 1.02 100% / 0% 12,227 -58 12,227
Actual: 1.50 75% / 25% 13,500 4,500 18,000
Equipment Data
Heating System Cooling System
Type: Air Source Heat Pump Air Source Heat Pump
Model: KUSAE181A KUSAE181A
Indoor Model: KNSAE181A
Brand: LG LG
Description: AHRI 214931167 AHRI 214931167
Efficiency: 8.9 HSPF2 18 SEER2
Sound: 0 0
Capacity: 19,000 Btuh 18,000 Btuh
Sensible Capacity: n/a 13,500 Btuh
Latent Capacity: n/a 4,500 Btuh
AHRI Reference No.: n/a 9152487
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 108F, SOWB: 70F, WODB: 41F, SIDB: 75F, SIRH: 45%, WIDB: 70F, Sen. gain:
12,227 Btuh, Lat. gain: -58 Btuh, Sen. loss: 5,850 Btuh, Entering clg. coil DB: 75F, Entering clg. coil WB: 60.9F, Entering
htg. coil DB: 70F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 579 CFM, Req. htg. airflow: 79 CFM
C:\ ..2482- irvin's guess house - Tuesday, May 5 , 2026

Form
Residential Plans Examiner Review Form
RPER 1.01
for HVAC System Design (Loads, Equipment, Ducts) 8 Mar 10
County, Town, Municipality, Jurisdiction
Header Information
REQUIRED ATTACHMENTS¹ ATTACHED
Contractor
Manual J1 Form (and supporting worksheets): Yes No
Mechanical License # or MJ1AE Form² (and supporting worksheets): Yes No
OEM performance data (heating, cooling, blower): Yes No
Building Plan # Manual D Friction Rate Worksheet: Yes No
Duct distribution system sketch: Yes No
Home Address (Street or Lot#, Block, Subdivision)
HVAC LOAD CALCULATION (IRC M1401.3)
Design Conditions Building Construction Information
Winter Design Conditions Building
Outdoor temperature 41 °F Orientation (Front door faces) North
North, East, West, South, Northeast, Northwest, Southeast, Southwest
Indoor temperature 70 °F
Number of bedrooms 0
Total heat loss 5850 Btu/h
400
Conditioned floor area Sq Ft
Summer Design Conditions
Outdoor temperature 108 °F Number of occupants 0
Indoor temperature 75 °F Windows
Grains difference -7 Gr @ 45 % Rh Eave overhang depth 1.3 Ft
Sensible heat gain 12227 Btu/h Internal shade
Latent heat gain -58 Btu/h Blinds, drapes, etc
Total heat gain 12169 Btu/h Number of skylights 0
HVAC EQUIPMENT SELECTION (IRC M1401.3)
Heating Equipment Data Cooling Equipment Data Blower Data
Equipment type Air Source Heat Pump Equipment type Air Source Heat Pump
Furnace, Heat pump, Boiler, etc. Air Conditioner, Heat pump, etc Heating CFM 579 CFM
Model KUSAE181A Model KUSAE181A
Cooling CFM 579 CFM
Heating output capacity 19000 Btu/h Sensible cooling capacity 13500 Btu/h
Heat pumps - capacity at winter design outdoor conditions
Latent cooling capacity 4500 Btu/h
Auxiliary heat output capacity Btu/h Total cooling capacity 18000 Btu/h
HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1)
Design airflow 579 CFM Longest supply duct: Ft Duct Materials Used (circle)
99
Trunk Duct: Duct board, Flex, Sheet metal,
External Static Pressure (ESP) 0.43 IWC Longest return duct: Ft Lined sheet metal, Other (specify)
Component Pressure Losses (CPL) 0.35 IWC Total Effective Length (TEL) 99 Ft
Branch Duct: Duct board, Flex, Sheet metal,
Available Static Pressure (ASP) 0.078 IWC Friction Rate: 0.08 IWC Lined sheet metal, Other (specify)
ASP = ESP - CPL Friction Rate = (ASP × 100) ÷ TEL
I declare the load calculation, equipment selection, and duct system design were rigorously performed based on the building plan listed
above, I understand the claims made on these forms will be subject to review and verification.
Contractor's Printed Name Date
Contractor's Signature
Reserved for use by County, Town, Municipality, or Authority having jurisdiction.
¹ The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions.
² If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions.
Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program.

9055 W. Van Buren St., Tolleson, AZ 85353 • (623) 936-7111 • TTY users, dial 711 for Relay • www.tolleson.az.gov
AFFIDAVIT OF POSTING
On October 5, 2026, Ken Hernandez certify that the following public notice was posted on the
property per A.R.S. § 9-462.04:
NOTICE OF PUBLIC HEARINGS
CITY OF TOLLESON
NOTICE IS HEREBY GIVEN that the City of Tolleson Planning and Zoning Commission will conduct
a PUBLIC HEARING on TUESDAY, OCTOBER 27, 2026 at 5:00 PM, and the Mayor and Council will
conduct a PUBLIC HEARING on TUESDAY, OCTOBER 27, 2026 at 6:00 PM, both during Regular
Meetings held in the Council Chambers at the Tolleson Civic Center, 9055 West Van Buren Street,
Tolleson, Arizona 85353, and via Zoom Webinar. Planning and Zoning Commission Webinar:
https://us02web.zoom.us/j/83763983293 (Meeting ID: 837 6398 3293); Mayor and Council
Webinar: https://us02web.zoom.us/w/84069679194 (Meeting ID: 840 6967 9194); and
telephone access for both meetings: 1-253-215-8782.
The purpose of the public hearings is to solicit comments from interested parties regarding Use
Permit Application No. PNZ-26-0027, submitted by the property owner Haro Arredondo Irvin E.,
to construct a separate 400-square-foot guest house at 8725 W. C.P. Hayes Drive, Tolleson,
Arizona 85353. The subject property, identified as APN 102-48-249, is approximately 7,179
square feet and is currently zoned Residential Single-Family (R1-7).
Published in the Arizona Business Gazette–Republic Edition on October 9, 2026.
KHERNANDEZ
Ken Hernandez, Code Compliance Officer