PLANNING AND ZONING 
Development Services Department 
10000 N. El Mirage Road, El Mirage, Arizona 85335 
623-876-2996; Fax 623-876-4605; TDD 623-933-3258 
www.elmirageaz.gov 
 
MEMORANDUM 
TO: 
 
Albert Madrid, Ware Malcomb  
FROM: 
Jose A. Macias, Senior Planner 
 
 
Development Services Department, Planning & Zoning  
RE: 
 
PZ22-02-06 Nexen DC Site Plan   
DATE: 
October 4, 2022 
Mr. Madrid, 
Please see the comments from the El Mirage Technical Advisory Committee (TAC) for a site 
plan zoning application for warehouse/distribution center use. 
BUILDING & SAFETY 
1. No comment. 
ECONOMIC DEVELOPMENT  
2. No comment.  
ENGINEERING 
3. See attached memorandum.  
FIRE DEPARTMENT 
4. No comment. 
PLANNING & ZONING 
Comments shall be address with the submittal of construction documents.  
5. Official addresses for all three buildings will be assigned when construction documents 
are submitted for staff review.  
6. If buildings are occupied by multiple tenants, the property owner/management shall 
notify the city and request for an address update for each suite. 
7. A separate building permit shall be submitted for staff review for +the construction of the 
perimeter fence/wall.  
8. Note: A Final Plat may be required for city approval and to record any easements and/or 
dedication of land prior to issuing the Certificate of Occupancy. (Separate fees will 
apply) 
9. Note: See Zoning Code §154.125 SIGN REGULATIONS of the El Mirage Zoning Code 
Chapter 154 for sign requirements.

2 
 
10. Note: Signs other than building numbers and address will require a permit, this includes 
monument signs, pole signs, and wall signs.   
11. Landscape Plan Note: A landscape plan consisting of a preliminary plan and a final plan 
shall be prepared, submitted, and approved for all applicable development projects in 
accordance with the procedures and requirements set forth in this subchapter.  
12. Landscape Plan Note: All changes in landscape plans before, during, or after preliminary 
or final landscape plan approval shall be approved by the Zoning Administrator or his or 
her designee prior to the installation of any such landscape change.  
13. Landscape Plan Note: All changes in the landscaping of a site before, during, or after 
final landscape plan approval and landscape installation shall be approved by the Zoning 
Administrator or his or her designee as set forth in this subchapter.  
14. ARS 28-8481 (MILITARY LAND USE COMPATIBILITY): The site is located in the 
Luke Air Force Base 75 to 80 LDN Zone and is subject to ARS 28-8481 regulations and 
new buildings are subject to ARS 28-8482 Sound Attenuation Standards in Building 
Code. 
15. Elevations: no comment. 
POLICE DEPARTMENT 
16. No comment.  
PUBLIC WORKS 
17. No comment.  
 
EPCOR WATER  
18. The site is located within the EPCOR Utilities’ sewer and water service area and shall 
coordinate site development and services with the private company. See attached 
comment.

Engineering 
Development Services Department 
10000 N El Mirage Road, El Mirage 85335 
623-972-8116; Fax 623-876-4605; TDD 623-933-3258 
www.elmirageaz.gov 
 
 
MEMORANDUM  
 
TO: 
 
Jose Macias, Planner/GIS 
FROM: 
Bryce Christo, P.E., Assistant City Engineer 
SUBJECT: 
Nexen DC Development Application Review  
DATE: 
09-26-22 
 
Below are the Engineering Department’s comments for the above referenced submittal provided 
in September 2022. These items will have to be addressed prior to the Planning and Zoning 
Meeting. 
 
Narrative (These items were not addressed with the Development Application submittal) 
1. Project Proposal – It is noted that the project will be built in two phases. All offsite 
improvements will be required in Phase 1. A Phasing Plan per Section F of the City’s 
Design and Development Standards Manual (DDSM) shall be provided with the 
Development Application. 
2. Site Design – The Narrative states that the project is requesting a parking variance due to 
the proposed building being a warehouse and that the number of spaces required per City 
Code is much greater than is required. A Parking Waiver must be submitted and shall 
include the number of spaces required per City Code, the number of spaces actually 
required by the site and how that number was determined and explain how additional 
spaces can be accommodated, if required, in the future. The Waiver shall include a 
breakdown per lot/building. 
3. How many employees are anticipated to be on site during a typical shift per building? 
How many shifts will there be?  
 
The below items will have to be addressed during the Construction Plan Submittal. 
 
Site Plan/Civil Plans 
4. Add the following to the plans: 
a. The right of way width of both Ramirez Road and Dysart Road. 
b. Exterior signs 
5. Property Data Section 
a. The APN for the site is 509-18-978. 
b. Show a breakdown for each building showing the areas of the warehouse and the 
office. 
c. Show the number of parking spaces provided per lot/building. 
6. It appears Building A has 188 parking spaces, Building B has 188 parking spaces and 
Building C has a 199 parking spaces.  If this is accurate, each lot/building will require 5 
standard ADA spaces and one van accessible ADA space. The Site Plan appears to meet 
these requirements but please verify.

2 
 
7. The City will construct the five lane (2-M-2) roadway section for the ultimate Dysart 
Road and both the right of way and 8-foot PUE along the Nexen property have already 
been dedicated. The project is responsible for an eight-foot-wide detached meandering 
sidewalk, streetlights, ITS conduit and landscaping/irrigation along the Dysart Road 
frontage. The project will also be responsible for any deceleration/turn lanes and 
associated right of way/easement revisions.  
8. The project is responsible for a six-foot-wide sidewalk (meandering if possible) and 
landscaping/irrigation along Ramirez Road. The project will also be responsible for any 
deceleration/turn lanes and associated right of way/easement revisions. 
9. The project is responsible for the cost of 25% of the future traffic signal at Ramirez Road 
and Dysart Road which is $179,690.50 as calculated by the City’s Engineering consultant 
(see attached cost estimate). 
a. The property owner shall pay the above fee to the City at the time of, and as a 
condition to, the issuance of the certificate of occupancy for the first building. 
b. This payment will constitute the property owner’s sole obligation with respect to 
the traffic signal. 
c. The payment will be refunded if the City abandons the traffic signal or the 
construction of the signal has not commenced within 10 years of the payment to 
the City. 
10. A 1 foot Vehicular Non-Access Easement (VNAE) is required along Dysart Road except 
at the proposed driveways. 
11. It appears the three lots will share utilities, access, retention, etc. An Agreement will need 
to be in place that establishes this. 
12. The northernmost proposed driveway on Dysart Road shall be right in/right out only. Of 
the other two driveways on Dysart Road, one must be right in/right out and one may be 
full access.  It is recommended to coordinate the final location with the developer on the 
east side of Dysart (Dermody Properties) and/or come to an Agreement with the property 
owner to the south to have the southernmost drive aisle straddle the property line. 
13. A Design Exception will be required for the following: 
a. Providing a full access driveway on Ramirez Road within 660 feet of the 
Dysart/Ramirez intersection, measured from nearest face of curb to nearest face of 
curb. This will have to be addressed in the TIA. 
b. Having a driveway spacing of less than 150 feet on a collector road, measured 
from nearest face of curb to nearest face of curb. The west driveway on Ramirez 
Road is approximately 120 feet away from the approved Cavco driveway to the 
west. This will have to be addressed in the TIA. 
14. The driveways shall be per MAG or City details. The Site Plan calls out City type 
driveways but the design shown on the Site Plan does not match the City Details of 251-1 
or 251-2. 
15. If any portion of the driveway ramp/walkway is proposed within the Nexen property, a 
Pedestrian Access Easement shall be dedicated to the City.  
16. Stop signs are recommended at each driveway. Verify all driveways have a minimum 
throat of 50 feet unless they could potentially be signalized in the future in which the 
length shall be a minimum of 150 feet. 
17. If a driveway is either designated for truck entry or prohibits use by trucks, please 
provide the necessary signage. Verify that any driveway to be used by a truck can 
accommodate a WB-67 vehicle without encroaching into the adjacent lane. 
18. Verify that the sight distance requirements at each proposed driveway are per City Detail 
EM-158. The linework shown on the Site Plan appears inaccurate.

3 
 
19. Show the separation between the proposed site driveways and the proposed adjacent 
driveways. 
20. Keep the sidewalk along Ramirez Road within the right of way. This sidewalk can be 
attached if necessary. The sidewalk along Dysart Road shall be detached and meandering 
if possible. 
21. 6-inch MAG type curbing is required around all driveways and parking lots. Curb that 
carries drainage shall include a gutter. The curbing shall be no closer than 3 feet to any 
property line.  
22. The trash enclosures shall be per City Detail EM-113. 
23. Pre-Application Note 5 may no longer apply as it is believed that the farmer has ceased 
farming the subject property. Please contact Dermody Properties for confirmation.   
24. Plans shall include applicable City Notes. Call out MAG, City, etc. details to be used. 
Use the City’s Design & Development Standards Manual (DDSM) as a guide for the final 
design. 
 
Preliminary Grading & Drainage Plans 
25. Verify the slope does not exceed 2% in any direction within ADA parking spaces. 
26. Side slopes adjacent to the public right of way, areas where pedestrian access is permitted 
and within Public Utility Easements (PUE) shall be 6:1 or flatter. There shall be at least 
two feet of level ground between any wall or vertical obstruction and the top of any side 
slope grading.  
27. Heights and/or elevations for any proposed retaining walls will be required. Structural 
drawings for the proposed retaining walls shall be reviewed by the Building Safety 
Division.  Safety rail is required when the vertical drop is 30 inches or more and 
recommended when 12 inches or more. 
28. Show the basin overflow elevations and the ultimate outfall of the site. 
29. The finished floor elevations of the proposed buildings shall be a minimum of 12 inches 
above the 100-year base flood elevations and high-water level of any adjacent retention 
basin and 14 inches above the ultimate outfall of the site.  
30. The proposed retention basins or underground pipes shall be located a minimum of 4 feet 
away from any structures and shall not be located within any building setbacks, 
easements, or fire lanes.  
31. Trash racks and safety rails are recommended for any on-site headwalls. 
32. The retention pipe for Basin B1 is missing drywells. 
33. The Dysart Road plans show a proposed scupper 585 feet south of the Ramirez Road 
southern curb line. A second scupper will be required near the southern boundary of the 
site. Dysart Road AutoCAD files can be provided upon request. There is also an existing 
catch basin on Ramirez Road that outlets to the project site. 
 
Preliminary Utility Plans 
34. The Utility Plans shall show all utilities and utility easements including electric, gas, 
phone and cable. 
35. All proposed water and sanitary sewer lines will be private so the easement can be 
removed.  The onsite improvements shall be designed per City standards and the offsite 
improvements shall be designed per EPCOR standards.   
36. The fire line requires a backflow preventer at both entrances into the site. 
37. The domestic water and landscape service lines shall tie in to the mains in Dysart Road 
and/or Ramirez Road and shall have their own meter and backflow preventer. 
38. Water meters/vaults shall be located within the right of way and backflow preventers 
shall be located on private property but not within the PUE.

4 
 
39. Show the sizes of the proposed utility services.  The minimum fire service line shall be 6 
inches, the minimum domestic and landscaping service line shall be 1 inch and the 
minimum sanitary sewer service size shall be 6 inches. 
40. The sanitary sewer services shall have backwater valves per City Detail EM-442. 
41. Do not install utilities under any driveway or adjacent concrete apron. 
42. Show utility horizontal and vertical clearance information per MAG Detail 404 and City 
Detail EM-402. 
43. Water valves are recommended along the fire line, approximately every 500 feet, and at 
locations so that the maximum number of hydrants to be out of service per closure is two. 
44. A fire hydrant is required on the west side of Building C.  Final hydrant locations/spacing 
will be reviewed and approved by the Fire Department.  
45. Any hydrants within the project site will be private and painted “Safety Red” per City 
Detail EM-360. All hydrants require markers per MAG Detail 122. 
46. It is recommended to have a streetlight at each driveway. 
47. Show the location of any on-site lighting. A Photometric Plan will be required that shows 
any light or combination of lights which cause light on a public street, other than lights 
specifically intended for that purpose, shall not exceed one foot candle as measured from 
the center line of the street. Show the foot candles along the centerline of Ramirez Road 
and the ultimate Dysart Road to verify that the proposed lighting will not exceed the 
maximum limit. 
 
Preliminary Landscape Plans 
48. Add City Landscaping and Irrigation Notes (City Detail EM-101-4) to the plan set. 
49. Verify that the placement of the Site Distance Easements matches City Detail EM-158. 
Add the easements to the intersection of Dysart & Ramirez. 
50. A separate landscaping service, meter and backflow preventer is required. 
51. All plantings at maturity shall maintain a minimum of 6 feet of clearance from all fire 
hydrants and fire suppression devices per City Detail EM-361. 
52. No walls/footer or trees shall be placed within the proposed Public Utility Easement 
(PUE). It appears several trees along Dysart Road on the Building C lot are within the 
PUE. Please verify. 
53. Trees shall not be placed within 5 feet of any City curb or sidewalk or within 6 feet of 
any public utility. 
54. Add a note to the plans that the maintenance for all landscaping and irrigation shown on 
the plans will be the responsibility of the property owner. 
55. Irrigation plans will be required. 
 
Exterior Elevations 
56. No comments 
 
ALTA Survey 
57. Note 3 on Sheet 1 states that the western portion of the site is located in Special Flood 
Hazard Area ‘A’ but this is not accurate.  
 
Preliminary Drainage Report 
58. The finished floor elevation of the proposed buildings shall be a minimum of 12 inches 
above the 100-year base flood elevations and high-water level of any adjacent retention 
basin and 14 inches above the ultimate outfall of the site. 
59. Using a coefficient of 0.95 for the whole site is acceptable. If the designer wishes to 
break down the site further, the City Runoff Coefficients per City Code Section

5 
 
155.054(B)(6)(a) shall be used. Concrete = 0.95, roofs/asphalt = 0.85, grass = 0.15 and 
desert/rock lawn = 0.70.  
60. Provide basin overflow elevations and the low outfall of the lot. 
61. Calculations for the storm drain, catch basin, scuppers, etc. will be required. 
62. Reference the 2022 Design and Development Standards Manual. 
63. A Final Drainage Report will be required.  
 
Preliminary Water Report 
64. All proposed on-site water lines will be private.  The onsite improvements shall be 
designed per City standards and the offsite improvements shall be designed per EPCOR 
standards. The City of El Mirage will be responsible for fire protection and the design of 
that system will be reviewed and approved by the City. 
 
Preliminary Sewer Report 
65. All proposed on-site sanitary sewer lines will be private.  The onsite improvements shall 
be designed per City standards and the offsite improvements shall be designed per 
EPCOR standards.   
66. Section I and V – The sanitary sewer main in Dysart Road is 12 inches. The developer 
shall contact EPCOR to determine the schedule for the availability of this line. 
 
Traffic Impact Statement (TIS) (No TIA was provided with the Development Application so the 
original TIS comments have been provided again) 
67. Introduction – The property is at the southwest corner of Ramirez & Dysart, not the 
northwest. 
68. An exhibit shall be provided to show (a) the spacing between each of the proposed 
driveways, (b) the spacing between the driveways and the Ramirez/Dysart intersection 
and (c) the Ramirez driveway and the proposed TI Cold driveways, measured from near 
curb to nearest curb. 
69. A full Traffic Impact Analysis will be required. The TIA shall follow the City’s Traffic 
Impact Study Criteria (attached). The report shall review the requirements for 
deceleration lanes for the site driveways, determine if any signals warrants are met for the 
driveways and the Ramirez/Dysart intersection, describe the effect on the surrounding 
area from a traffic standpoint and recommend any improvements to the area to 
accommodate the proposed site. 
 
Title Report 
70. No comments 
 
Phase I Environmental Assessment 
71. Section 3.5 – The City is in the process of transferring the Water and Sewer Service 
Areas to EPCOR. 
 
Miscellaneous 
72. A Final Plat will be required to show all right of way and easement dedications. The Plat 
shall be reviewed and approved by the City and recorded prior to Certificate of 
Occupancy.  
73. A Geotechnical Report will be required to provide on-site pavement sections. Verify the 
proposed pavement sections can handle 75,000 lbs. for the fire access lane or more if the 
trucks entering and existing the site will be heavier.

6 
 
74. A Haul Permit will be required if 500 cubic yards or more of material will be brought 
into or out of the site. This will require a separate application, an exhibit showing the haul 
route and insurance from the company performing the haul. The fee is $300. 
75. An Approval to Construct (ATC) will be required from MCESD for the water and sewer 
line extensions. A copy shall be provided to the City prior to the release of any 
Engineering permit. 
76. A Dust Control Permit from the County will be required prior to the release of any 
Engineering permit. 
77. A Stormwater Pollution Prevention Plan (SWPPP) will be required per the City’s SWPPP 
Guidelines document. A Notice of Intent (NOI) from ADEQ will be required prior to 
release of any Engineering permit. 
78. Any cutting of the pavement in Ramirez Road will require Pavement Cut Fees per the 
most current Fee Schedule. 
79. The City will not release any permits until EPCOR approves the water and sewer design. 
The applicant is responsible for submitting plans to EPCOR for review and approval. 
 
The above comments are meant to be general in nature and are not considered to be all inclusive. 
Additional comments will arise during the formal permit submittal.

TRAFFIC IMPACT STUDY CRITERIA 
City of El Mirage, Arizona 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Revised January 1, 2021

2
 
TABLE OF CONTENTS 
 
Page 
 
INTRODUCTION 
 
 
 
----------------------------------------- 
        3 
 
STUDY REQUIREMENTS  
 
----------------------------------------- 
        3 
 
STUDY CLASSIFICATIONS 
 
----------------------------------------- 
        3 
 
TRAFFIC STUDY ANALYSIS 
AND APPROACH  
 
 
----------------------------------------- 
        4 
 
 
Study Area  
 
 
----------------------------------------- 
        4 
 
Study Time Frame  
 
----------------------------------------- 
        4 
 
Analysis Time Periods 
 
----------------------------------------- 
        5 
 
Data Collection 
 
 
----------------------------------------- 
        5 
 
Trip Generation 
 
 
----------------------------------------- 
        6 
 
Trip Distribution and Assignment ----------------------------------------- 
        6 
 
Traffic Analysis 
 
 
----------------------------------------- 
        7 
 
REPORT FORMAT  
 
 
----------------------------------------- 
        8 
 
COORDINATION WITH OTHER 
PUBLIC AGENCIES 
 
 
----------------------------------------- 
        9 
 
REPORT SUBMITTALS 
 
 
----------------------------------------- 
        9 
 
AUXILIARY LANE CRITERIA 
           ----------------------------------------- 
        9 
 
DRIVEWAY CRITERIA 
 
 
----------------------------------------- 
        9

3
 
 
INTRODUCTION 
 
The purpose of this document is to provide criteria for the preparation of Traffic 
Impact Studies for new land developments or additions to existing developments 
and to establish the report format for these studies. 
 
STUDY REQUIREMENTS 
  
A Traffic Impact Study prepared by a Registered Professional Engineer in the 
State of Arizona is required for all developments unless waived in writing by the 
City Engineer. If the Traffic Impact Study is waived, a Traffic Impact Statement is 
required that includes the total vehicle trips that will be generated by the 
development, using the Institute of Transportation Engineers (ITE) Trip 
Generation publication (most recent edition). 
 
STUDY CLASSIFICATIONS 
  
Traffic Impact Studies will be classified into three categories: 
 
Category I- 
Those developments that are estimated to generate 500 
vehicle trips or less during either of the a.m. or p.m. peak 
hours. 
 
Category II- 
Those developments that are estimated to generate more 
than 500 vehicle trips during either of the a.m. or p.m. peak 
hours but not more than 1,000 peak hour trips. 
 
Category III- 
Those developments that are estimated to generate more 
than 1,000 vehicle trips during either of the a.m. or p.m. peak 
hours. 
 
The developer should first estimate the number of vehicle trips that will be  
generated by the proposed development and provide this information along with 
the other suggested study elements of the Traffic Impact Study to the City for 
Review and approval prior to the start of construction.

4
 
 
TRAFFIC STUDY ANALYSIS AND APPROACH 
 
 The following presents the specific items to be included in a Traffic Impact 
Study. 
 
Study Area 
 
a) All site driveways  
 
 
 
 
 
All categories 
 
b) All major intersections within 1 mile of the study site, 
    either signalized or un-signalized. 
 
 
 
All categories 
 
c) All driveways where traffic movements could be  
    affected by new driveway traffic movements.  
 
All categories 
 
d) Additional locations as requested by the reviewing 
    agency. 
 
 
 
 
 
 
 
All categories 
 
Study Time Frame 
 
The study should include, as a minimum, an analysis of the expected traffic 
conditions for the time period when the development is expected to open. The 
opening day conditions should include all of the proposed development traffic as 
if the development was fully completed and occupied. 
 
Additional study years should be included as follows: 
 
Category I: 
Opening year and 5 years in the future. 
 
Category II: Opening year, 5 years and 10 years in the future. 
 
Category III: Opening year, 5 years, 10 years and 20 years in the future. 
 
The study for phased construction developments should include an analysis for 
each year that planned new phased construction is to be started. In addition, the 
required 5, 10 or 20 year analysis after the start of the last phase of the 
development as stated above for the specific categories. 
 
Analysis Time Periods 
 
The study should include an analysis of the impact of the development traffic for 
the typical adjacent street peak hour conditions which normally occur within the 
time periods from 6:00 to 9:00a.m. and 3:30 to 6:30p.m. on a typical weekday 
and an analysis of the impact of the development daily weekday traffic generated 
on the adjacent street system and site driveways. In addition, if requested by the

5
 
City, additional time periods and or weekend analysis may be required in the 
study if the developer has unusual peaking characteristics or if the adjacent non-
site traffic conditions warrant an analysis of other peak traffic time periods. 
 
Data Collection 
  
 
The traffic impact study should include information on the following existing and 
proposed conditions within the study area: 
 
a) Traffic Volumes 
 
1. Existing and proposed traffic volumes for the adjacent existing and 
proposed intersections and driveways to include daily weekday 
a.m. peak hour and p.m. peak hour (and other time periods as 
noted in the previous section). Daily traffic volumes should be 
provided as a 24-hour directional roadway section count and peak 
hour volumes should be provided by specific intersection or 
driveway turning movement directions. 
 
2. Existing traffic volume data should be adjusted to average 
conditions based on City adjustment factors or appropriate 
adjustment factors available from other public agencies. 
 
3. Projected traffic volumes should be based on available traffic 
projections from the Maricopa Association of Governments (MAG), 
other appropriate documented traffic projected sources or historical 
traffic volume trends. Projected traffic volumes shall include 
adjustments, as necessary, to reflect other adjacent future 
development. 
 
b) Land Use 
 
1. Existing and proposed land use in the study area should be 
discussed and included in the study as it impacts the proposed 
development street system or driveways. 
 
c) Roadway Conditions  
 
1. Existing and proposed roadway conditions shall be identified 
including pavement type, width, traffic lanes, medians, curb and 
gutter, speed limits, horizontal and vertical curvature and traffic 
control devices.

6
 
d) Crash Experience 
 
1. Crash experience should be documented for the past 36-month 
time period for the adjacent roadway system included within the 
study area. 
 
Trip Generation 
 
The trip generation for the proposed development shall be estimated using the 
latest edition of Trip Generation published by ITE. Exceptions to the use of this 
document must be approved by the City and may include actual traffic generation 
counts from a similar existing facility having the same size and surrounding area 
characteristics or from other recognized sources that provide trip generation data 
not included in the ITE manual. 
 
If proposed within the Traffic Impact Study, adjustments to the site traffic 
generation should be documented to reflect site traffic interaction, pass-by traffic, 
use of other modes of transportation, carpooling or other means of trip reduction. 
Trip reduction methods should be discussed with the City prior to use within the 
report. 
 
Trip Distribution and Assignment 
 
Site traffic shall be assigned to the proposed site driveways and street 
intersections included within the study area based on an analysis of the market 
area for the proposed development. The market area will vary based on the type 
and location of the development. However, as a minimum, the following 
guidelines should be used: 
 
● Residential trip distribution should be based on the locations of employment   
   and commercial attractions and the available street system. 
 
● Commercial, industrial and office trip distribution should be based on the   
    surrounding population densities and the available street system. 
 
The area to be constructed in the development of the site trip distribution should 
normally be within a 10-mile radius of the study site. However, other conditions of 
the proposed development, the adjacent street system and the location of site 
traffic attractors and generators may indicate the need to expand or reduce the 
area of influence. 
 
Traffic Analysis 
 
The study should include the following minimum items for analysis.

7
 
a) Traffic flow conditions, including the level of service using the latest edition 
of the Highway Capacity Manual (Special Report 209, Transportation 
Research Board) 
 
1. An analysis of the existing traffic conditions. 
 
2. An analysis of the future non-site traffic conditions. 
 
3. An analysis of the traffic conditions with the addition of site traffic. 
 
 
b) Roadway capacity conditions using generally accepted daily volume traffic 
demand compared to roadway cross sections. 
 
1. Existing traffic conditions  
 
2. Future non-site traffic conditions. 
 
3. Future traffic conditions with the addition of site traffic. 
 
c) Intersection and driveway traffic control device requirements using results 
of the items below and the Federal Highway Administrations (FHWA) 
Manual on Uniform Traffic Control Devices for Streets and Highways 
(edition adopted by the Arizona Department of Transportation) 
 
1. Existing conditions. 
 
2. Future non-site conditions. 
 
3. Future total traffic conditions. 
 
d) Intersection and driveway geometrics using recognized accepted formulas 
with documentation provided within the report. 
 
1. Analyze adequacy or need for additional through traffic lanes or 
auxiliary right or left turn lanes for existing, future non-site and 
future total traffic conditions and include storage requirements. 
 
2. Analyze potential conflicts of proposed driveway locations with 
existing and/or proposed adjacent driveways or intersection traffic 
lane configurations for the future total traffic conditions. 
 
e) Crash summary and identification of trends and/or potential safety 
hazards.

8
 
f) Other analysis as requested by the City or as may be required due to the 
type and location of the proposed development. 
 
1. Weaving analysis. 
 
2. Parking analysis. 
 
3. On-site circulation including queuing analysis at major on-site 
turning movement locations. 
 
4. Site access quantity, location and traffic lane configuration.  
 
g) Mitigation measurements 
 
All recommended on-site and off-site improvements required to mitigate 
projected traffic congestion or safety issues shall be identified with the 
resultant traffic flow conditions indicated for comparison to the “before 
conditions”. 
 
REPORT FORMAT 
 
The Traffic Impact Study should include the following items and report sections: 
 
a) Title page. 
 
b) Table of contents and list of figures and tables. 
 
c) Introduction including description of project, purpose of report and 
executive summary. 
 
d) Proposed development description including location, land use and 
proposed use. Include vicinity map on site plan. 
 
e) Study area description. 
 
f) Existing conditions including site land use, adjacent roadway description 
and traffic volumes. Include summary of existing traffic counts, graph of 
existing (adjacent) daily and peak hour traffic and roadway condition 
diagrams. 
 
g) Projected traffic including site traffic generations, distributions and 
assignment and non-site traffic for each time period to be analyzed. 
Include tabular data as needed to show trip rate formulas used in the 
study and a summary of the site traffic assignment. Graphics should be 
included showing the daily and peak hour volumes for each analysis time 
period included in the study for both the site and non-site traffic.

9
 
 
h) Total traffic should be shown for each analysis time period. 
 
i) Traffic analysis showing tabular and graphic results of the analyses. 
 
j) Summary and conclusions. 
 
k) Appendix providing any material related to the traffic study data collection 
and study results. 
 
COORDINATION WITH OTHER PUBLIC AGENCIES 
 
If applicable, the requirements for the Traffic Impact Study as noted in this 
document may need to be coordinated with the requirements of other local 
agencies such as adjacent cities or towns, the Maricopa County Department of 
Transportation or the Arizona Department of Transportation. Any deviation from 
the requirements of this document due to the requirements of other agencies 
should be presented in written form to the City for review and approval or denial. 
 
REPORT SUBMITTALS 
 
A minimum of two (2) copies of the report shall be submitted to the City for 
review. Additional copies of the report may be required for review by other 
adjacent public agencies. 
 
AUXILIARY LANE CRITERIA 
 
Use the City of El Mirage Auxiliary Lane Criteria Memorandum 
 
DRIVEWAY CRITERIA 
 
See City of El Mirage Detail EM-259

Date: 6-29-21
Job No.: 18-081.4
Labor Class Rate
$220.00
$185.00
$150.00
$110.00
$105.00
$60.00
$150.00
$140.00
$125.00
$90.00
DESCRIPTION
Principal
Project 
Manager
Project 
Engineer
Engineer
CAD 
Tecnician
Clerical
Survey 
Manager
Survey 2-
man
Project 
Surveyor
Survey Tech
Task Cost
Task 1: Supplemental Topo / Utility
6
2
5
$1,540.00
Task 2: Signal Design
2
16
32
80
$14,690.00
   ~Cost Estimate
1
3
3
$965.00
Task 3: Utility Coordination
12
$1,800.00
Task 4: Project Meetings
   ~Over the Shoulder (Draft Plans 30%) 
6
$900.00
   ~Progress Comment Resolution (95%) 
4
2
$820.00
Task 5: Project Management
16
$2,960.00
TOTAL HOURS
0
19
41
37
80
0
0
6
2
5
190
SUBTOTAL FEES
$0.00
$3,515.00
$6,150.00
$4,070.00
$8,400.00
$0.00
$0.00
$840.00
$250.00
$450.00
$23,675.00
ALLOWANCE
Task 6: Post Design
20
$3,000.00
Item 7: Pothole Budget
$4,000.00
$30,675.00
TOTAL FIXED FEE
Fee Estimation Worksheet
PROJECT: Dysart and Ramirez Signal

From:
Veloz, Jose Ruben
To:
Jose Macias
Cc:
Beuche, Anthony
Subject:
RE: [EXTERNAL] FW: Development Application Review: PZ22-02-06 Nexen Dc
Date:
Monday, October 3, 2022 4:10:27 PM
Attachments:
image001.jpg
image002.png
image003.png
image004.png
image005.png
image008.jpg
image009.jpg
image011.png
image010.png
Application for Fire Line - EPCOR 2016.pdf
Hi Jose,
 
I received the preliminary utility plans, water and sewer report for the project. When you are ready
for the official submittal, please provide the following:  
 
 
Plan Review Application. See attached form
Utility Plans
Water and Sewer Report
Plan Review Fee. The plan review fee is $2,500.00. An invoice will be sent to you after the official
submittal is received.
 
Please let me know if you have any questions.
 
Thanks.  
 
 
 
 
 
Logo
 
Ruben Veloz
Senior Engineering Technician
Developer Services
2355 W. Pinnacle Peak Road, Suite 300
Phoenix, AZ  85027
Tel 623.445.2495. | epcor.com

From: Jose Macias <jmacias@elmirageaz.gov> 
Sent: Tuesday, September 20, 2022 7:55 AM
To: Beuche, Anthony <ABeuche@epcor.com>
Cc: Gunter, Christian <CGunter@epcor.com>; Veloz, Jose Ruben <JVeloz@epcor.com>
Subject: RE: [EXTERNAL] FW: Development Application Review: PZ22-02-06 Nexen Dc
 
Anthony,
 
Thank you for the information, I will update my EPCOR contact list.
 
Regards,
 
 
Jose A. Macias
Senior Planner | GIS
Development Services - Planning & Zoning | GIS Division
P: 623.876.2996 | F: 623.876.4605 | E: jmacias@elmirageaz.gov
 
 
 
 
 
El Mirage City Hall Hours: Mon – Thurs 7:00 am to 5:30 pm & Closed Fridays.
 
From: Beuche, Anthony <ABeuche@epcor.com> 
Sent: Tuesday, September 20, 2022 6:59 AM
To: Jose Macias <jmacias@elmirageaz.gov>
Cc: Gunter, Christian <CGunter@epcor.com>; Veloz, Jose Ruben <JVeloz@epcor.com>
Subject: [EXTERNAL] FW: Development Application Review: PZ22-02-06 Nexen Dc
 
Good Morning Jose,
Thank you for forwarding the Nexen submittal documents.  As further documents are received,
please forward them to Ruben Veloz (copied on this email) and myself.  Ruben is the EPCOR
manager for projects in the City of El Mirage expansion area.
Thanks,
Tony
 
 
Logo
 
Tony Beuché. P.E.
Developer Services Manager - Western
2355 W. Pinnacle Peak Road, Suite 300

Phoenix, AZ  85027
Tel 623.445.2452 (Direct) | epcor.com
 
From: Gunter, Christian <CGunter@epcor.com> 
Sent: Monday, September 19, 2022 2:36 PM
To: Beuche, Anthony <ABeuche@epcor.com>
Cc: jmacias@elmirageaz.gov
Subject: FW: Development Application Review: PZ22-02-06 Nexen Dc
 
Tony,
 
Jose at City of El Mirage sent me the email below and the attachments. I believe it should have gone
to you.
 
Please let Jose and I know if you are the correct contact at EPCOR?
Thanks,
 
Chris Gunter, PE
623-445-2474 - Desk
727-656-5166 - Cell
epcor. com
 
From: Jose Macias <jmacias@elmirageaz.gov> 
Sent: Monday, September 19, 2022 10:26 AM
To: Gunter, Christian <CGunter@epcor.com>
Subject: FW: Development Application Review: PZ22-02-06 Nexen Dc
 
Notice: External Email
Use caution when opening links, attachments, and when prompted to enter User IDs,
Passwords or Confidential Information.
Please report any suspicious email with the "Report Phish" button.
Chris,
 
Attached please find a Development Application for a Site Plan in the EPCOR Service area for your
review. Comments are due by Monday September 26, 2022.
 
If you have any questions, please feel free to contact my office.
 
Regards,
 
Jose A. Macias
Senior Planner | GIS
Development Services - Planning & Zoning | GIS Division

10000 N. El Mirage Road, El Mirage, AZ 85335
P: 623.876.2996 | F: 623.876.4605 | E: jmacias@elmirageaz.gov
 
 
 
 
 
El Mirage City Hall Hours: Mon – Thurs 7:00 am to 5:30 pm & Closed Fridays.
 
This email message, including any attachments, is for the intended recipient(s) only, and
contains confidential and proprietary information. Unauthorized distribution, copying or
disclosure is strictly prohibited. If you have received this message in error, or are obviously
not one of the intended recipients, please immediately notify the sender by reply email and
delete this email message, including any attachments. Thank you.
This email message, including any attachments, is for the intended recipient(s) only, and contains
confidential and proprietary information. Unauthorized distribution, copying or disclosure is strictly
prohibited. If you have received this message in error, or are obviously not one of the intended
recipients, please immediately notify the sender by reply email and delete this email message,
including any attachments. Thank you.
This email message, including any attachments, is for the intended recipient(s) only, and
contains confidential and proprietary information. Unauthorized distribution, copying or
disclosure is strictly prohibited. If you have received this message in error, or are obviously
not one of the intended recipients, please immediately notify the sender by reply email and
delete this email message, including any attachments. Thank you.

WO # ___________ 
DISTRICT # ___________ 
  
 
APPLICATION FOR FIRE LINES 
 
NOTE:  “Fire Lines” are water lines that are connected to EPCOR’s distribution system that are used 
exclusively for on-site private fire hydrants and/or for interior fire sprinkler systems for buildings.  
Fire Lines shall be utilized for fire protection services only and shall serve only a single property.  
Though EPCOR reviews the engineering plans of the Fire Lines, EPCOR’s approval of the Fire Lines 
is limited only to that portion to be constructed within rights-of-way or water easements. 
 
 
Date of Application:  
 
 
 
 
 
Name of Business that will be served by the Fire Lines:    
 
 
 
 
 
 
 
Contact Name of Applicant (Applicant must be an employee of the Business listed above):   
 
 
 
 
 
 
 
 
 
 
 
  Phone No.:   
 
 
 
 
 
Applicant’s Mailing Address:   
 
 
 
 
 
 
 
 
 
 
 
Applicant’s E-Mail Address:   
 
 
 
 
 
 
 
 
 
 
 
Contact Name of Engineer:   
 
 
 
 
  Phone No.:   
 
 
 
 
 
Engineer’s E-Mail Address:   
 
 
 
 
 
 
 
 
 
 
 
Name of Engineering Company:   
 
 
 
 
 
 
 
 
 
 
 
 
The Applicant, upon the terms and conditions set forth herein, applies to EPCOR Water Arizona Inc. 
 
(“Utility”) for a fire line connection to be located at  
 
 
 
 
 
 
   
 
 
 
 
 
 
 
 
 
 
 more fully described in Exhibit A. 
 
 
Applicant agrees to be bound by all the terms and conditions of this Application and of the Utility’s rules and 
regulations for water service as on file with and approved by the Arizona Corporation Commission as they 
presently exist or as they may hereafter be modified, altered, or changed from time to time.  In case of any 
conflict with the provisions of this Application, the rules and regulations for water service shall control. 
 
Subject to the previous paragraph, terms and conditions that are binding upon acceptance of this 
Application by the Utility are as follows: 
 
1. The Applicant is responsible for all Work, which is defined as the connections to the distribution 
main, the installation of the fire lines, the installation of the control valves and backflow prevention 
assemblies, and all required excavations, saw-cutting, backfilling, pavement and sidewalk 
replacements, permits, approvals, and associated work, all to the satisfaction of Utility, the local fire 
department, and the entity that owns the rights-of-way.  This Work shall be in compliance with the 
details in Exhibit B and with the design requirements listed in Exhibit C, and with all requirements 
of the local fire department and the entity that owns the rights-of-way.    
 
2. All Work described in Paragraph 1 above that occurs within the right-of-way or water easement, 
including the installation of the backflow prevention assembly, shall be subject to inspection, testing 
and acceptance by the Utility before commencement of service.  Applicant will comply with Utility’s 
1

inspection and testing requirements for the Work.  Applicant will provide Utility two business 
days’ prior notice before the Work begins, and when any portion of the Work is ready for 
inspection and testing.  Utility will then promptly inspect and test the Work to determine if such has 
been constructed in accordance with Utility’s specifications and details.  As a result of Utility’s 
inspection and testing, Utility may provide written notification to Applicant of punch list items that 
require correction and Applicant agrees to promptly correct all defects and deficiencies in 
construction, materials and workmanship. 
 
3. Upon Applicant’s receipt of invoice from Utility, Applicant will pay to Utility a non-refundable 
inspection and administration fee equal to $2,500.00.  The inspection and administration fee is 
to compensate Utility for the cost of its administration, coordination, engineering reviews, 
inspections, testing and approval incurred by Utility in connection with the design, construction, 
installation and connection of the Fire Line(s).  This fee is a non-refundable contribution in aid of 
construction.  Applicant will not begin any work until Utility receives payment of the inspection and 
administration fee.   
 
4. The Applicant shall utilize the services of an Arizona licensed and insured contractor to perform the 
Work.  At a minimum of seven (7) calendar days prior to the start of Work, the Applicant will 
submit the following documents to Utility for its review and approval: 
 
a. a copy of the contractor’s license;  
b. a copy of the contractor’s certificate of insurance (EPCOR Water Arizona Inc. must be listed 
as an Additional Insured); 
c. a copy of the contractor’s bid. 
 
Utility will verify and confirm whether the contractor has the appropriate license classification to 
perform this type of Work, and will verify that the contractor’s insurance is current and effective.  
Applicant will not begin any Work until written approval of these items is obtained from the 
Utility.  Written approval may be in the form of an e-mail. 
 
5. Applicant will pay all of the costs of permitting, constructing, installing, and connecting the Fire 
Line(s) including, but not limited to, the costs of engineering, materials, labor, transportation, 
equipment, necessary permits and approvals, easements, testing, corrections, insurance and 
bonds, wherever applicable.  Applicant’s costs for the Fire Line(s) shall be considered a non-
refundable contribution in aid of construction. 
 
6. Applicant estimates a construction start date of __________________________________, 20___.  
Applicant will not commence construction until (a) Applicant has given proper notification to Utility’s 
inspector per Paragraph 2, (b) Utility receives payment of the inspection and administration fee per 
Paragraph 3, and (c) Applicant receives written notice of approval per Paragraph 4. 
 
7. The construction and installation of the Fire Line(s) shall be in accordance with good utility and 
engineering practices, the rules, regulations and requirements of the local fire department, Utility’s 
specifications and details, and the requirements of all other agencies having jurisdiction over the 
Fire Line(s) and rights-of-way. 
 
8. If Applicant begins construction of any Work before all of the conditions set forth in Paragraph 6 are 
satisfied, such construction will be at Applicant’s sole risk and subject to repair, alteration or 
reconstruction at Applicant’s expense as directed by Utility or any regulatory agency. 
 
9. After construction of the Work is completed, Applicant will promptly provide to Utility all of the 
following: 
 
a. Copies of all paid bills, invoices and other statements of expenses incurred by Applicant as 
a result of the Work; and, 
2

b.
Lien waivers and releases from contractors, subcontractors and vendors for materials,
equipment, supplies and construction included in the Work.
10. The Fire Line(s) will not be used to provide public utility service until inspected, tested and approved 
by Utility and Final Acceptance of the Work has occurred.  Utility specifically reserves the right to 
withhold Final Acceptance of the Work unless the Work has been constructed in accordance with the 
terms of this Application and are reasonably satisfactory to Utility upon inspection and testing.
11. Utility will notify Applicant of Utility’s Final Acceptance of the Work within ten (10) days after the 
satisfaction of all of the following conditions:
a.
Applicant has corrected all punch list items identified by Utility;
b.
Applicant has paid all fees required by this Application and by the terms of Utility’s then-
current and applicable tariffs;
c.
Applicant has delivered to Utility all documents required in Paragraph 9: and,
d.
If Utility has determined that an easement is required, Applicant has, at no cost to Utility, 
granted or caused to be granted to Utility, perpetual rights-of-way and easements and 
obtained all necessary zoning and other governmental approvals as required, each in a form 
and with substance reasonably satisfactory to Utility’s legal counsel, for Utility’s ownership, 
operation, maintenance and replacement of that portion of the Fire Lines(s) within the 
easement, including adequate access from public roadways.  As a condition to Applicant’s 
conveyance of easement rights to Utility, Utility may require Applicant to deliver to Utility, 
among other documents and information reasonably requested by Utility, an ALTA survey 
and a title report pertaining to the real property subject to such easement, both of which must 
be in form and substance satisfactory to Utility’s legal counsel. Unless otherwise mutually 
agreed upon in writing, such easements:
i.
will be free of physical encroachments, encumbrances or obstacles that will 
materially impair Utility's maintenance and operation of that portion of the Fire Line(s) 
between Utility’s distribution line and the newly installed backflow preventer;
ii.
will have a minimum width of 20 feet; and,
iii.
will specify that the service lines will be separated by a reasonable distance from 
other utility lines and facilities so as to prevent damage or conflicts in the event of 
repairs or maintenance.
12. Concurrently with Utility’s Final Acceptance of the Work, if an easement was granted for any portion 
of the Fire Line(s), all lines within the easement shall become, and shall thereafter remain, as 
between Utility and Applicant, the sole property of Utility without the requirement of any written 
document of transfer to Utility.  Applicant represents and warrants to Utility that, at the time of such 
transfer, Utility will receive good and marketable title to the conveyed Fire Line(s), free and clear of 
any and all liens, claims, mortgages or other encumbrances.  Applicant shall furnish any document 
pertaining to ownership and title as may be requested by Utility, including documents which evidence 
or confirm transfer of ownership and possession to Utility, and the good, merchantable and lien-free 
title to such portions of the Fire Line(s).  All risk of loss of the Fire Line(s) shall be with Applicant until 
title to that portion of the Fire Line(s) is transferred to Utility in accordance with the terms of this 
Application.
13. WARRANTY – For one year after Utility’s written Final Acceptance of the Work, Applicant will, upon 
Utility’s reasonable request, promptly correct any and all defects and deficiencies in construction, 
materials and workmanship in the Work discovered by Utility.
14. Neither Utility’s inspection nor acceptance of the Work relieves or limits Applicant’s responsibilities 
and liabilities under this Application.
15. Utility does not provide fire protection services and does not warrant, guarantee or represent that any 
water utility services it provides will comply with any fire-protection requirements of any 
3

governmental agency, or of any county, municipal, or private fire protection providers.  Utility will 
allow public and private fire protection providers to use water from its system for fire-fighting 
purposes, provided that Utility’s normal system demands are first met and water system pressure is 
not decreased to less than 20 pounds per square inch. 
 
16. Utility does not guarantee a continuous supply of service or a constant water pressure of service.  
Utility is not liable for damages occasioned by such events, interruptions or failure to commence 
service or unsatisfactory service or any act or failure to act arising out of this Application caused by 
an act of God or the public enemy, accident, fire, explosions, strikes, riots, war, delay in receiving 
shipments of required material, order of any court or judge granted in any bona fide adverse legal 
proceedings or action, or any order of any commission or tribunal having jurisdiction in the 
premises; or without limitation by the preceding enumeration, any other act or thing reasonably 
beyond its control or incident to interruptions necessary for repairs or changes in Utility’s production, 
storage, transmission, distribution, collection, and other related facilities. 
 
17. Applicant will defend, indemnify and hold harmless Utility, its officers, directors, agents, and 
employees from and against any and all claims, damages, judgments, fines, penalties, 
assessments, costs and expenses, including attorneys’ fees and court costs, to which they or any of 
them may be subjected by reason of injury, death, loss, claim, penalty, assessment or damage 
caused or contributed to by the active or passive negligence or willful misconduct of Applicant, its 
agents, servants, employees, contractors or subcontractors in the execution of, or failure to execute, 
Applicant’s obligations under this Application; provided, however, that Applicant shall not be 
required to indemnify Utility to the extent of any negligent or wrongful acts of Utility, its officers, 
directors, agents or employees. 
 
18. UTILITY WILL NOT BE LIABLE TO APPLICANT FOR ANY INCIDENTAL, CONSEQUENTIAL, 
SPECIAL, PUNITIVE, OR OTHER INDIRECT DAMAGES, REGARDLESS OF WHETHER SUCH 
DAMAGES ARISE UNDER BREACH OF CONTRACT, TORT, STRICT LIABILITY, OR OTHER 
THEORY OF LAW. 
 
19. This Application represents the entire understanding between the parties with respect to its subject 
matter, superseding all prior communications, understandings and agreements of or between the 
parties with respect to such subject matter.  There are no oral or collateral agreements between the 
parties with respect to such subject matter. 
 
20. Utility reserves the right to deem this Application null and void if Applicant does not begin 
construction of the Fire Line within six months after the date of this Application.  If Applicant has not 
started such construction within six months after the date of this Application, Applicant may issue a 
written request to Utility for an extension of this Application.  Utility’s response to any such request 
for extension will not be unreasonably delayed, but will be within Utility’s sole discretion.  If Utility 
deems the Application null and void, Utility will provide written notice of cancellation of this 
Application to Applicant. 
 
 
Signatures Follow (Next Page) 
 
 
4

Signed and agreed to by the Applicant with an effective date as shown first above written. 
 
 
ACCEPTANCE BY APPLICANT: 
 
Signature of Applicant:   
 
 
 
 
 
 
 
 
 
 
 
Title of Applicant:  
 
 
 
 
 
 
 
 
 
 
 
 
Date of Signature:  
 
 
 
 
 
 
 
 
 
 
 
 
 
Acknowledgment: 
 
 
STATE OF ______________________ ) 
                   
 
     
    
) 
COUNTY OF ____________________ ) 
 
      On _______________________, 20___, before me, __________________________, a Notary Public in  
 
and for said State, personally appeared _________________________, personally known to me (or proved 
to me on the basis of satisfactory evidence) to be the person whose name is subscribed to the within 
instrument and acknowledged to me that he/she executed the same in his/her authorized capacity, and that 
by his/her signature on the instrument the person, or the entity upon behalf of which the person acted, 
executed the instrument. 
 
WITNESS my hand and official seal. 
 
Signature 
______________________________ (Seal) 
 
 
 
 
 
 
 
 
************************************************************************************************************************** 
 
 
ACCEPTANCE BY EPCOR WATER ARIZONA INC.: 
 
Printed Name of Utility Representative:   
 
 
 
 
 
 
 
 
 
Signature of Utility Representative:  
 
 
 
 
 
 
 
 
 
 
Title of Utility Representative:  
 
 
 
 
 
 
 
 
 
 
 
Date of Signature:  
 
 
 
 
 
 
 
 
 
 
 
5

EXHIBIT A 
 
MAP SHOWING LOCATION OF PROPOSED FIRE LINE(S)

EXHIBIT B 
 
DESCRIPTION / DETAILS OF THE WORK

EXHIBIT C 
 
DESIGN REQUIREMENTS FOR FIRE LINES 
 
 
1. Fire line connections to Utility’s mains shall be used for fire protection systems only.  Metered 
services cannot be connected to fire lines. 
 
2. The minimum size fire line connection shall be 4 inches. 
 
3. For fire lines, backflow prevention devices are required within 75 feet of the main.  If the 
building riser is within 75 feet from the main, then a vertically mounted backflow prevention 
device may be located on the building riser.  If the building riser is further than 75 feet from the 
main, then a backflow prevention device shall be installed as close at practicable to the service 
connection (property line). 
 
4. Backflow prevention devices are not required for private hydrant connections that are not 
looped and that do not have fire sprinkler connections. 
 
5. Backflow prevention devices shall have been issued a certificate of approval by the University 
of Southern California Foundation for Cross-Connection Control and Hydraulic Research.  The 
certificate of approval shall be forwarded to Utility’s Backflow Prevention Specialist prior to 
Utility’s Final Acceptance of the fire lines. 
 
6. Backflow prevention devices shall not be located in rights-of-way, sidewalks, driveways, 
visibility triangles, or other locations where accidental damage or visibility obstruction would 
likely occur. 
 
7. Backflow prevention devices shall be fully accessible for testing, repairs, and replacement.  
There shall be an unobstructed radius of not less than three feet from the outer perimeter of 
each backflow prevention device. 
 
8. Per the Uniform Plumbing Code (610.2), in the absence of specific pressure drop information, 
the diameter of the inlet or outlet of any backflow prevention device or its connecting piping 
shall not be less than the diameter of such water distribution piping to the fixtures served by 
the device.  If available, pressure drop information shall be provided with the submitted plans. 
 
9. Per the Uniform Plumbing Code (603.3.11), looped on-site fire line systems shall be provided a 
backflow preventer at each point of connection to the public water system. 
 
10. A control valve is required at ALL fire line connections to public water mains.  The control valve 
shall not be located in sidewalks, driveways, curbs or gutters. 
 
11. Thrust blocks are not allowed in rights-of-way.