1 
 
RESOLUTION R23-05-10 EHXIBIT 
CITY OF EL MIRAGE AMENDMENTS 
AMENDMENTS TO THE  
2018 INTERNATIONAL BUILDING CODE 
The following sections, paragraphs, and sentences of the 2018 International Building Code are 
hereby amended as follows:  Standard type (including italics) is text from the IBC. 
CAPITALIZED type is text inserted. Lined through type is deleted text from the IBC. 
APPENDICES C AND H ARE EXPRESSLY ADOPTED AND INCORPORATED HEREIN BY 
THIS REFERENCE 
SECTION 101 GENERAL 
101.1 Title. These regulations shall be known as the Building Code [NAME OF 
JURISDICTION] of CITY OF EL MIRAGE, hereinafter referred to as “this code.” 
SECTION 105 PERMITS 
105.2 Work exempt from permit. Exemptions from permit requirements of this code shall 
not be deemed to grant authorization for any work to be done in any manner in violation of the 
provisions of this code or any other laws or ordinances of this jurisdiction. Permits shall not be 
required for the following: 
Building: 
1. One-story detached accessory structures used as tool and storage sheds, playhouses and 
similar uses, provided the floor area is not greater than 120 square feet (11 m²). 
2. Fences not over 7 feet (2134 mm) high. 
3. Oil derricks. 
4. Retaining walls that are not over 4 feet (1219 mm) in height measured from the bottom of the 
footing to the top of the wall, unless supporting a surcharge or impounding Class I, II or IIIA 
liquids.   
5. Water tanks supported directly on grade if the capacity is not greater than 5,000 gallons (18 
925 L) and the ratio of height to diameter or width is not greater than 2:1. 
6. PLATFORMS, Sidewalks and driveways not more than 30 inches (762 mm) above adjacent 
grade, and not over any basement or story below and are not part of an accessible route. 
7. Painting, papering, tiling, carpeting, cabinets, counter tops and similar finish work. 
8. Temporary motion picture, television, and theater stage sets and scenery. 
9. Prefabricated swimming pools accessory to a Group R-3 occupancy that are less than 18 
inches (610 mm) deep, are not greater than 5,000 gallons (18 925 L) and are installed entirely 
above ground.

2 
 
10. Shade cloth structures constructed for nursery or agricultural purposes, not including service 
systems. 
11. Swings and other playground equipment accessory to detached one- and two-family 
dwellings. 
12. Window awnings in Group R-3 and U occupancies, supported by an exterior wall that do not 
project more than 54 inches (1372 mm) from the exterior wall and do not require additional 
support. 
13. Non-fixed and movable fixtures, cases, racks, counters and partitions not over 5 feet 9 
inches (1753 mm) in height. 
SECTION 105  PERMITS 
 
105.5 Expiration. A PERMIT SHALL BE CONSIDERED EXPIRED IF MORE THAN 180 
DAYS SHALL PASS BETWEEN APPROVALS OF INSPECTIONS LISTED IN SECTION 109.  
WHEN A PERMIT EXPIRES BY LIMITATIONS AND HAS BECOME NULL AND VOID, AND 
THE BUILDING OFFICIAL HAS NOT BEEN NOTIFIED IN WRITING BY THE PERMIT 
APPLICANT THAT NO WORK WAS DONE UNDER THE PERMIT, THE BUILDING OFFICIAL 
MAY FILE A “NOTICE OF NON-COMPLIANCE” WITH THE MARICOPA COUNTY 
RECORDER’S OFFICE FOR FAILURE TO OBTAIN THE REQUIRED INSPECTIONS. Every 
permit issued shall become invalid unless the work on the site authorized by such permit is 
commenced with 180 days after its issuance, or if the work authorized on the site by such permit 
is suspended or abandoned for a period of 180 days after the time the work is commenced. The 
building official is authorized to grant, in writing, one or more extension of time, for periods not 
more 180 days each. The extension shall be requested in writing and justifiable cause 
demonstrated. 
105.5.1 COMPLETING WORK AND FINAL INSPECTION. EVERY PERMIT ISSUED BY 
THE BUILDING OFFICIAL SHALL EXPIRE 24 MONTHS AFTER THE DATE OF PERMIT 
ISSUANCE. IF THE BUILDING OR WORK AUTHORIZED BY SUCH PERMIT HAS NOT 
RECEIVED FINAL INSPECTION APPROVAL PRIOR TO THE PERMIT EXPIRATION 
DATE, ALL WORK SHALL STOP UNIT A NEW PERMIT IS OBTAINED FOR THE VALUE 
OF THE WORK REMAINING UNFINISHED.  
EXCEPTION: THE BUILDING OFFICIAL MAY APPROVE A PERIOD EXCEEDING 24 
MONTHS FOR COMPLETION OF WORK WHEN THE PERMIT HOLDER CAN 
DEMONSTRATE THAT THE COMPLEXITY OR SIZE OF THE PROJECT MAKES 
COMPLETING THE PROJECT WITHIN 24 MONTHS UNREASONABLE. ANY 
REQUEST SHALL BE PRIOR TO THE EXPIRATION OF THE PERMIT. 
SECTION 113 BOARD OF APPEALS 
[A] 113.1 General. APPEALS SHALL BE IN ACCORDANCE WITH SECTION 96.01 OF 
THE EL MIRAGE MUNICIPAL CODE. In order to hear and decide appeals or orders, decisions 
or determinations made by the building official relative to the application and interpretation of 
this code, there shall be and is hereby created a board of appeals. The board of appeal shall be 
appointed by the applicable governing authority and shall hold office at its pleasure. The board 
shall adopt rules of procedure for conducting its business.

3 
 
SUBSECTIONS 113.2 THROUGH 113.3 ARE DELETED IN THEIR ENTIRETY. 
SECTION 1111 SIGNAGE 
1111.1 Signs. Required accessible elements shall be identified by the International Symbol 
of Accessibility at the following locations. 
1. Accessible parking spaces required by Section 1106.1. 
A. ACCESSIBLE PARKING SPACES MAY ALSO BE IDENTIFIED BY THE USE OF 
THE ACCESSIBILITY ICON. 
Exception: Where the total number of parking spaces provided is four or less, 
identification of accessible parking is not required. 
2. Accessible parking spaces required by Section 1106.2. 
Exception: In Group I-1, R-2, R-3 and R-4 facilities, where parking spaces are assigned 
to specific dwelling units or sleeping units, identification of accessible parking spaces is 
not required. 
3. Accessible passenger loading zones. 
4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered at a 
single location. 
5. Accessible entrances where not all entrances accessible. 
6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, 
shall be above the check-out aisle in the same location as the check-out aisle number or 
type of check-out identification. 
7. Family or assisted-use toilet and bathing rooms. 
8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible. 
9. Accessible areas of refuge in accordance with Section 1009.9. 
10. Exterior areas for assisted rescue in accordance with Section 1009.9. 
11. In recreational facilities, lockers that are required to be accessible in accordance with 
Section 1109.9. 
1111.2 Directional signage.  Directional signage indicating the route to the nearest like 
accessible element shall be provided at the following locations. These directional signs shall 
include the International Symbol of Accessibility OR THE ACCESSIBILITY ICON and sign 
characters shall meet the visual character requirements in accordance with ICC A117.1. 
1. Inaccessible building entrances. 
2. Inaccessible public toilets and bathing facilities. 
3. Elevators not serving an accessible route. 
4. At each separate-sex toilet and bathing room indicating the location of the nearest family 
or assisted-use toilet or bathing room were provided in accordance with Section 1109.2.1

4 
 
5. At exits and exit stairways serving a required accessible space, but not providing an 
approved accessible means of egress, signage shall be provided in accordance with Section 
1009.10. 
6. Where drinking fountains for persons using wheelchairs and drinking fountains for 
standing persons are not located adjacent to each other, directional signage shall be 
provided indicating the location of the other drinking fountains. 
SECTION 1203 TEMPERATURE CONTROL  
1203.1 Equipment and systems. HABITABLE SPACES Interior spaces intended for 
human occupancy shall be provided with active or passive space heating AND 
SPACECOOLING systems capable of maintaining a minimum indoor temperature BETWEEN 
70°F of 68°F (2120°C) AND 90°F (32°C) at a point 3 feet (914 mm) above the floor on the 
design heating day. 
Exception: Space heating AND COOLING systems are not required for: 
1. Interior spaces where the primary purpose of the space is not associated with human 
comfort. 
2. Group F, H, S or U occupancy  
SECTION 1607 LIVE LOADS 
TABLE 1607.1 
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS, Lo, AND MINIMUM 
CONCENTRATED LIVE LOADS 
OCCUPANCY OR USE 
UNIFORM 
CONCENTRATED  
  
  
(psf) 
(lbs) 
25 Residential  
  
  
  
  
One- and two- family dwellings 
  
  
  
  
  
  
  
  
  
Uninhabitable attics with storage 
20 40 
  
  
Habitable attics and sleeping areas 
20 40 
  
 (NO OTHER CHANGES IN ITEM #25) 
  
  
  
 
SECTION 1612 FLOOD LOADS 
1612.3 Establishment of flood hazard areas. To establish flood hazard areas, the 
applicable governing authority shall adopt a flood hazard map and supporting data. The flood 
hazard map shall include, at a minimum, areas of special flood hazard as identified by the 
Federal Emergency Management Agency in an engineering report entitled “The Flood 
Insurance Study for [INSERT NAME OF JURISDICTION] MARICOPA COUNTY, ARIZONA 
AND INCORPORATED AREAS REVISED ON JULY 19, 2001,” dated [INSERT DATE OF

5 
 
ISSUANCE] as amended or revised with the accompanying Flood Insurance Rate Map (FIRM) 
and Flood Boundary and Floodway Map (FBFM) and related supporting data along with any 
revisions thereto. The adopted flood hazard map and supporting data are hereby adopted by 
reference and declared to be part of this section. 
SECTION 1704 SPECIAL INSPECTIONS AND TESTS, CONTRACTOR RESPONSIBILITY 
AND STRUCTURAL OBSERVATION 
1704.1 General. Special inspections and tests, statements of special inspections, 
responsibilities of contractors, submittals to the building official and structural observations shall 
meet the applicable requirements of this section. THE BUILDING OFFICIAL MAY ALSO 
REQUIRE OTHER SPECIAL INSPECTIONS NOT PRESCRIBED IN THIS SECTION AS 
NEEDED. 
SECTION 2106 SEISMIC DESIGN 
2106.1 Seismic design requirements for masonry. Masonry structures and components 
shall comply with the requirements in section 1.18 of TMS 402/ACI 530/ASCE 5 depending on 
the structure’s seismic design category. ALL NEW MASONRY ELEMENTS, REGARDLESS 
OF SEISMIC DESIGN CATEGORY, SHALL MEET THE FOLLOWING MINIMUM 
REINFORCEMENT REQUIREMENTS: 
1. CONNECTIONS TO COLUMNS SHALL COMPLY WITH SECTION 1.18.4.3.2.1 OF TMS 
402/ACI 530/ASCE 5.2 
2. VERTICAL WALL REINFORCEMENT OF AT LEAST 0.20 SQUARE INCH (130 MM ) IN 
CROSS-SECTIONAL AREA SHALL BE PROVIDED CONTINUOUSLY FROM SUPPORT 
TO SUPPORT AT EACH CORNER, AT EACH SIDE OF EACH OPENING, AT THE ENDS 
OF WALLS AND AT MAXIMUM SPACING OF 4 FEET (1219 MM) APART 
HORIZONTALLY THROUGHOUT THE WALL. 
3. HORIZONTAL WALL REINFORCEMENT NOT LESS THAN 0.20 SQUARE INCH (130 
MM ) IN CROSS-SECTIONAL AREA SHALL BE PROVIDED (1) AT THE BOTTOM AND 
TOP OF WALL OPENINGS AND EXTEND NOT LESS THAN 24 INCHES (610 MM) OR 
LESS THAN 40 BAR DIAMETERS PAST THE OPENING, (2) CONTINUOUSLY AT 
STRUCTURALLY CONNECTED ROOF AND FLOOR LEVELS AND AT THE TOP OF 
WALLS, (3) AT THE BOTTOM OF WALLS OR IN THE TOP OF FOUNDATIONS WHEN 
DOWELED IN WALLS, AND (4) AT MAXIMUM SPACING OF 10 FEET (3048 MM) 
UNLESS UNIFORMLY DISTRIBUTED JOINT REINFORCEMENT IS PROVIDED. 
4. WHERE ANCHOR BOLTS ARE USED TO CONNECT HORIZONTAL ELEMENTS TO 
THE TOPS OF COLUMNS, ANCHOR BOLTS SHALL BE PLACED WITHIN LATERAL 
TIES. LATERAL TIES SHALL ENCLOSE BOTH THE VERTICAL BARS IN THE COLUMN 
AND THE ANCHOR BOLTS. THERE SHALL BE A MINIMUM OF TWO NO. 4 (M #13) OR 
THREE NO. 3(M #10) IN THE TOP 5 INCHES (127 MM) OF THE COLUMN. 
SECTION 3109 SWIMMING POOLS, SPAS AND HOT TUBS 
3109.1 General. The design and construction of swimming pools, spas and hot tubs shall 
comply with the International Swimming Pool and Spa Code MARICOPA COUNTY 
ENVIRONMENTAL SERVICES DEPARTMENT REQUIREMENTS.

6 
 
AMENDMENTS TO THE  
2018 INTERNATIONAL RESIDENTIAL CODE 
 
APPENDICES A, B, C, E, G, H, K, N, P, Q, R, S AND T ARE EXPRESSLY ADOPTED AND 
INCORPORATED HEREIN BY THIS REFERENCE 
SECTION R101 GENERAL 
R101.1 Title.  These provisions shall be known as the Residential Code for One and Two-
Family Dwellings of [NAME OF JURISDICTION] CITY OF EL MIRAGE, and shall be cited as 
such and will be referred to herein as “this code.”  
SECTION R102 APPLICABILITY 
R102.4 Referenced codes. THE OTHER CODES LISTED IN SECTIONS 102.4.1 
THROUGH 102.4.2 AND REFERENCED ELSEWHERE IN THIS CODE SHALL BE 
CONSIDERED PART OF THE REQUIREMENTS OF THIS CODE TO THE PRESCRIBED 
EXTENT OF EACH SUCH REFERENCE AND AS ADOPTED AND AMENDED BY THE CITY 
OF EL MIRAGE. The codes and standards referenced in this code shall be considered part of 
the requirements of this code to the prescribed extent of each such reference and as further 
regulated in Sections R102.4.1 and R102.4.2. 
SECTION R105 PERMITS 
R105.2.4 FLAMMABLE LIQUIDS AND GASSES. A PERMIT SHALL BE REQUIRED FOR 
THE INSTALLATION OF ANY CONTAINER OR PUMP FOR STORING AND HANDLING 
FLAMMABLE LIQUIDS AND GASES.  ALL CONTAINERS AND EQUIPMENT FOR THE 
STORAGE AND HANDLING OF FLAMMABLE LIQUIDS OR GASES, OR BOTH, SHALL BE 
INSTALLED IN ACCORDANCE WITH THE 2018 INTERNATIONAL FIRE CODE.  ALL 
TANKS MUST BE FILLED FROM VEHICLES PARKED ON PRIVATELY OWNED 
PROPERTY.  NO PUMP SHALL BE LOCATED WITHIN A BUILDING.   
R105.2 Work exempt from permit. Exemption from permit requirements of this code shall 
not be deemed to grant authorization for any work to be done in any manner in violation of the 
provisions of this code or any other laws or ordinances of this jurisdiction. Permits shall not be 
required for the following. 
Building: 
1. One-story detached accessory structures, provided the floor area is not greater than 200 
square feet (18.58 m2)120 SQUARE FEET (11 M2). 
2. Fences not over 7 6 feet (2134 mm 1829 mm) high. 
3. Retaining walls that are not over 4 feet (1219 mm) in height measured from the bottom of the 
footing to the top of the wall, unless supporting a surcharge. 
4. Water tanks supported directly on grade if the capacity is not greater than 5,000 gallons (18 
925 L) and the ratio of height to diameter or width is not greater than 2:1. 
5. Sidewalks and driveways.

7 
 
6. Painting, papering, tiling, carpeting, cabinets, counter tops and similar finish work. 
7. Prefabricated swimming pools accessory to a Group R-3 occupancy that are less than 24 18 
inches (610 mm) deep. 
8. Swings and other playground equipment. 
9. Window awnings supported by an exterior wall that do not project more than 54 inches (1372 
mm) from the exterior wall and do not require additional support. 
10. Decks not exceeding 200 square feet (18.58 m2) in area, that are not more than 30 inches 
(762 mm) above grade at any point, are not attached to a dwelling and do not serve the exit 
door required by Section R311.4. 
105.5 Expiration. Every permit issued shall become invalid unless the work authorized by 
such permit is commenced within 180 days after its issuance or after commencement of work if 
more than 180 days pass between inspections. The building official is authorized to grant, in 
writing, one or more extension of time, for periods not more 180 days each. The extension shall 
be requested in writing and justifiable cause demonstrated. A PERMIT SHALL BE 
CONSIDERED EXPIRED IF MORE THAN 180 DAYS SHALL PASS BETWEEN APPROVALS 
OF INSPECTIONS LISTED IN SECTION 109. WHEN A PERMIT EXPIRES BY LIMITATIONS 
AND HAS BECOME NULL AND VOID, AND THE BUILDING OFFICIAL HAS NOT BEEN 
NOTIFIED IN WRITING BY THE PERMIT APPLICANT THAT NO WORK WAS DONE UNDER 
THE PERMIT, THE BUILDING OFFICIAL MAY FILE A “NOTICE OF NON-COMPLIANCE” 
WITH THE MARICOPA COUNTY RECORDER’S OFFICE FOR FAILURE TO OBTAIN THE 
REQUIRED INSPECTIONS. 
105.5.1 COMPLETING WORK AND FINAL INSPECTION. EVERY PERMIT ISSUED BY 
THE BUILDING OFFICIAL SHALL EXPIRE 24 MONTHS AFTER THE DATE OF PERMIT 
ISSUANCE. IF THE BUILDING OR WORK AUTHORIZED BY SUCH PERMIT HAS NOT 
RECEIVED FINAL INSPECTION APPROVAL PRIOR TO THE PERMIT EXPIRATION DATE, 
ALL WORK SHALL STOP UNIT A NEW PERMIT IS OBTAINED FOR THE VALUE OF THE 
WORK REMAINING UNFINISHED. 
EXCEPTION: THE BUILDING OFFICIAL MAY APPROVE A PERIOD EXCEEDING 24 
MONTHS FOR COMPLETION OF WORK WHEN THE PERMIT HOLDER CAN 
DEMONSTRATE THAT THE COMPLEXITY OR SIZE OF THE PROJECT MAKES 
COMPLETING THE PROJECT WITHIN 24 MONTHS UNREASONABLE. ANY REQUEST 
SHALL BE PRIOR TO THE EXPIRATION OF THE PERMIT. 
SECTION R108 FEES 
R108.2 Schedule of permit fees. On buildings, structures, electrical, gas, mechanical and 
plumbing systems or alterations requiring a permit, a fee for each permit shall be paid as 
required, in accordance with the schedule as established by the CURRENTLY ADOPTED FEE 
SCHEDULE FOR THE CITY OF EL MIRAGE applicable governing authority. 
SECTION R112 BOARD OF APPEALS 
R112.1 General. APPEALS SHALL BE IN ACCORDANCE WITH SECTION 96.01 OF THE 
EL MIRAGE MUNICIPAL CODE. In order to hear and decide appeals of orders, decisions or 
determinations made by the Building Official relative to the application and interpretation of this

8 
 
code, there shall be and is hereby created a board of appeals. The Building Official shall be an 
ex officio member of said board but shall have no vote on any matter before the board. The 
board of appeals shall be appointed by the governing body and shall hold office at its pleasure. 
The board shall adopt rules of procedure for conducting its business, and shall render all 
decisions and findings in writing to the appellant with a duplicate copy to the Building Official.  
SUBSECTIONS R112.2 THROUGH 112.4 ARE DELETED IN THEIR ENTIRETY. 
SECTION R301 DESIGN CRITERIA 
R301.2 Climatic and geographic design criteria. Buildings shall be constructed in 
accordance with the provisions of this code as limited by the provisions of this section. 
Additional criteria shall be established by the local jurisdiction and set forth in Table R301.2(1). 
TABLE R301.2(1) 
(DUE TO SPACE LIMITATIONS THE TABLE COULD NOT BE REPRODUCED; ONLY THE 
VALUES ARE LISTED) 
GROUND SNOW LOAD: 0 
WIND SPEED (MPH): 115 EXPOSURE B (UNLESS OTHERWISE DESIGNATED BY THE 
BUILDING OFFICIAL) 
TOPOGRAPHIC EFFECTS: NO 
SPECIAL WIND REGION: NO 
WINDBORNE DEBRIS ZONE: NO 
SEISMIC DESIGN CATEGORY: B 
WEATHERING: NEGLIGIBLE 
FROST LINE DEPTH: 0” 
TERMITE: MODERATE TO HEAVY 
DECAY: NONE TO SLIGHT 
WINTER DESIGN TEMPERATURE: NONE TO SLIGHT 
ICE SHIELD UNDERLAYMENT REQUIRED: NO 
FLOOD HAZARDS: MCFCD REQUIREMENTS 
AIR FREEZING INDEX: N/A 
MEAN ANNUAL TEMPERATURE: 72.3°F 
R301.2.4 Floodplain Construction. Buildings and structures constructed in whole or in part 
in flood hazard areas (including A or V Zones) as established in Table R301.2(1) shall be 
designed and constructed in accordance with Section R322. Buildings and structures located in 
whole or in part in identified floodways shall be designed and constructed in accordance with 
ASCE 24 THE REGULATIONS OF THE MARICOPA COUNTY FLOOD CONTROL DISTRICT.

9 
 
R301.5 Live Load.  The minimum uniformly distributed live load shall be as provided in 
Table R301.5. 
TABLE R 301.5 
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS 
(in pounds per square foot) 
USE 
LIVE 
LOAD 
  Uninhabitable attics with storage 
20 40 
  Habitable attics and sleeping areas 
20 40 
  Sleeping Rooms 
20 40 
(NO OTHER CHANGES TO TABLE) 
SECTION R303 LIGHT, VENTILATION AND HEATING 
R303.10 Required heating AND COOLING. Where the winter design temperature in Table 
R301.2(1) is below 60°F (16°C) every dwelling unit shall be provided with heating AND 
COOLING FACILITIES capable of maintaining a minimum room temperature of not less than 
BETWEEN 68 70°F(20 21°C) AND 90°F (32.2°C) at a point 3 feet (914 mm) above the floor and 
2 feet (610 mm) from exterior walls in all habitable rooms at the design temperature. The 
installation of one or more portable space heaters OR PORTABLE SPACE COOLERS shall not 
be used to achieve compliance with this section. 
SECTION R309 GARAGES AND CARPORTS 
R309.5 Fire Sprinklers. DELETE THIS SUBSECTION IN ITS ENTIRETY. 
SECTION R310 EMERGENCY ESCAPE AND RESCUE OPENINGS 
R310.4 Bars, grilles, covers and screens.  Where bars, grilles, covers, screens or similar 
devices are placed over emergency escape and rescue openings, area wells, or window wells, 
the minimum net clear opening size shall comply with Sections R310.2.1 through R310.2.3 and 
such devices shall be releasable or removable from the inside without the use of a key, tool, 
special knowledge or force greater than that required for the normal operation of the escape and 
rescue opening. THE DWELLING SHALL BE EQUIPPED WITH SMOKE ALARMS 
INSTALLED IN ACCORDANCE WITH SECTION R314. 
SECTION R313 AUTOMATIC FIRE SPRINKLER SYSTEMS 
DELETE THIS SECTION IN ITS ENTIRETY. 
SECTION R322 FLOOD-RESISTANT CONSTRUCTION  
R322.1 General. Buildings and structures constructed in whole or in part in flood hazard 
areas (including A or V Zones) as established in Table R301.2(1), and substantial improvement 
and repair of substantial damage of buildings and structures in hazard areas, shall be designed 
and constructed in accordance with this section THE REGULATIONS OF THE MARICOPA 
COUNTY FLOOD CONTROL DISTRICT. Buildings and structures that are located in more than 
one flood hazard area shall comply with the provisions associated with the most restrictive flood

10 
 
hazard area.  Buildings and structures located in whole or in part in identified floodways shall be 
designed and constructed in accordance with ASCE 24.  
SECTION R328 FIREPLACE RESTRICTIONS 
RESTRCTIONS SHALL BE PURSUANT TO MARICOPA COUNTY AIR QUALITY 
DEPARTMENT REQUIREMENTS. 
SECTION R403 FOOTINGS 
R403.1.1 Minimum size. Minimum sizes for concrete and masonry footings shall be set 
forth in Table R403.1 and Figure R403.1(1). The footing width, W, shall be based on the load-
bearing value of the soil in accordance with Table R401.4.1. Spread footings shall be at least 6 
inches (152 mm) in thickness, T. Footing projections, P, shall be at least 2 inches (51 mm) and 
shall not exceed the thickness of the footing. The size of footings supporting piers and columns 
shall be based on the tributary load and allowable soil pressure in accordance with Table 
R401.4.1. Footings for wood foundations shall be in accordance with the details set forth in 
Section R403.2 and Figures R403.1.(2) and R403.1(3). 
EXCEPTION: FOR ENCLOSURE OF EXISTING CARPORT AND PATIO COVERS, NON-
BEARING WOOD FRAMED EXTERIOR WALLS WITHIN THE PROJECTION OF THE 
EXISTING ROOF MAY BE SUPPORTED ON AN EXISTING, UNCRACKED CONCRETE 
SLAB. THE MINIMUM SLAB THICKNESS SHALL BE 3.5 INCHES AND THE 
CONSTRUCTION SHALL COMPLY WITH THE REQUIREMENTS OF R317 FOR 
PROTECTION AGAINST DECAY. 
SECTION R502 WOOD FLOOR FRAMING 
R502.3.1 Sleeping areas and attic joists. Table R502.3.1(1 2) shall be used to determine 
the maximum allowable span of floor joists that support sleeping areas and attics that are 
accessed by means of a fixed stairway in accordance with Section R311.7 provided that the 
design live load does not exceed 30 40 pounds per square foot (1.44 1.92 kPa). The allowable 
span of ceiling joists that support attics used for limited storage or no storage shall be 
determined in accordance with Section R802.4. 
SECTION N1101 GENERAL 
N1101.1 Scope. This chapter regulates the energy efficiency for the design and 
construction of buildings regulated by this code. GROUP R-2 WHEN DEFINED AS A 
RESIDENTIAL BUILDING BY SECTION R202, SHALL HAVE THE OPTION OF COMPLYING 
UNDER THE COMMERCIAL PROVISIONS OF THE CODE, REGARDLESS OF HEIGHT. 
ONCE DEFINED AS SUCH ON THE SUBMITTAL DOCUMENTS, ALL COMPONENTS OF 
THE COMMERCIAL PROVISIONS SHALL BE FOLLOWED. 
N1103.3 Ducts. Ducts and air handlers shall be in accordance with Sections N1103.2.1 
through N1103.2.3. 
N1103.3.1 Insulation (Prescriptive). Supply ducts in attics shall be insulated to a minimum 
of R-8. Ducts in floor trusses shall be insulated to a minimum of R-6. Supply and return 
ducts in attics shall be insulated to an R-valve of not less than R-8 for ducts 3 inches (76 
mm) in diameter and larger and not less than R-6 for ducts smaller than 3 inches (76 mm) in 
diameter. Supply and return ducts in other portions of the building shall be insulated to not

11 
 
less than R-6 for ducts 3 inches (76 mm) in diameter and to not less than R-4.2 for ducts 
smaller than 3 inches (76.2 mm) in diameter. 
Exceptions: Ducts or portions thereof located completely inside the building thermal 
envelope. 
1. DUCTS OR PORTIONS THEREOF LOCATED COMPLETELY INSIDE THE 
BUILDING THERMAL ENVELOPE. 
2. SUPPLY DUCTS MAY BE INSULATED TO A MINIMUM OF R-6 WHEN ONE OR 
MORE OF THE FOLLOWING CONDITIONS ARE MET; 
2.1 MINIMUM SEER RATING OF SPACE HEATING/COOLING SYSTEM IS 
INCREASED TO 15. 
2.2 MAXIMUM U-FACTOR IS DECREASED TO 0.35 AND MAXIMUM SHGC IS 
DECREASED TO 0.22 FOR ALL FENESTRATION PRODUCTS. 
2.3 RESIDENTIAL BUILDINGS THAT MEET THE REQUIREMENTS OF 
SECTIONS R102.1.1 OR R405. 
2.4 RESIDENTIAL BUILDINGS WITH ATTIC RADIANT BARRIERS IN 
ACCORDANCE WITH ASTM C1313, INSTALLED IN ACCORDANCE WITH 
ASTM C1743. 
SECTION N1103 (R403) SYSTEMS 
N1103.10.3 Covers VARIABLE SPEED POOL PUMPS. Outdoor heated pools and outdoor 
permanent spas shall be provided with a vapor-retardant cover or other approved vapor-
retardant means. MOTORS WITH A TOTAL HORSEPOWER OF ONE OR MORE FOR 
POOLS AND IN-GROUND PERMANENTLY INSTALLED SPAS SHALL HAVE THE 
CAPABILITY OF OPERATING AT TWO OR MORE SPEEDS WITH A LOW SPEED HAVING 
A ROTATION RATE THAT IS NO MORE THAN ONE-HALF OF THE MOTOR'S MAXIMUM 
ROTATION RATE AND SHALL BE OPERATED WITH A PUMP CONTROL WITH THE 
CAPABILITY OF OPERATING THE PUMP AT TWO OR MORE SPEEDS. RESIDENTIAL 
POOL PUMP MOTOR CONTROLS THAT ARE SOLD FOR USE WITH A TWO OR MORE 
SPEED MOTOR SHALL HAVE A DEFAULT CIRCULATION SPEED SETTING NO MORE 
THAN ONE-HALF OF THE MOTOR'S MAXIMUM ROTATION RATE. ANY HIGH SPEED 
OVERRIDE CAPABILITY SHALL BE FOR A TEMPORARY PERIOD NOT TO EXCEED ONE 
TWENTY-FOUR HOUR CYCLE WITHOUT RESETTING TO THE DEFAULT SETTING. 
Exception: Where more than 75 percent of the energy for heating, computed over an 
operation season of not less than three months, is from a heat pump or an on-site renewable 
energy system, covers or other vapor-retardant means shall not be required. 
SECTION P2904 DWELLING UNIT FIRE SPRINKLER SYSTEMS 
DELETE SECTION IN ITS ENTIRETY. 
SECTION E3908 GROUNDING 
E3908.8 Types of equipment grounding conductors.  The equipment grounding 
conductor run with or enclosing the circuit conductors shall be one or more or a combination of

12 
 
OPTIONS ONE THROUGH EIGHT IN E3908.8 WITH THE FOLLOWING MODIFICATION TO 
OPTION FOUR: 
4. Electrical metallic tubing WITH AN ADDITIONAL EQUIPMENT GROUNDING 
CONDUCTOR SIZED IN ACCORDANCE WITH TABLE E3908.12. 
 
Appendix E 
Local Amendment 
DELETE THIS APPENDIX IN ITS ENTIRETY AND REPLACE AS FOLLOWS: 
MANUFACTURED HOUSING USED AS DWELLINGS SHALL CONFORM TO THE ARIZONA 
DEPARTMENT OF HOUSING’S MANUFACTURED HOUSING & BUILDING DIVISION 
REGULATIONS. 
Appendix I 
Local Amendment 
DELETE THIS APPENDIX IN ITS ENTIRETY AND REPLACE AS FOLLOWS: 
PRIVATE SEWAGE DISPOSAL SYSTEMS SHALL CONFORM TO THE ARIZONA 
DEPARTMENT OF HOUSING’S MANUFACTURED HOUSING & BUILDING DIVISION 
REGULATIONS. 
Appendix K 
SOUND TRANSMISSION 
SECTION AK102 AIRBORNE SOUND 
AK102.2. SOUND ATTENUATION - GENERAL. CONSTRUCTION OUTSIDE THE AREAS 
DESIGNATED AS HAVING A DAY NIGHT AVERAGE SOUND LEVEL 65 DECIBELS OR 
HIGHER AS DETERMINED BY THE USE OF THE 1988 NOISE CONTOUR LINES 
DEVELOPED BY THE MARICOPA COUNTY ASSOCIATION OF GOVERNMENTS (MAG) 
SHALL BE DEEMED TO HAVE ACHIEVED THE INTERIOR NOISE LEVEL OF 45 DECIBELS 
SPECIFIED IN ARS 28-8482 WHEN THE RESIDENCES ARE CONSTRUCTED USING ONE 
OF THE FOLLOWING METHODS: 
1. PRESCRIPTIVE METHOD: 
1.1 EXTERIOR WALL PENETRATIONS BY PIPE DUCTS OR CONDUITS SHALL BE 
SEALED. 
1.2 MAIL BOXES SHALL NOT BE USED THROUGH THE DOOR OR WALL. 
1.3 WINDOWS SHALL HAVE 2 PANES OF GLASS AND A SOUND TRANSMISSION 
RATING OF STC-22. ALL OPERABLE WINDOWS SHALL BE WEATHER STRIPPED 
AND AIR TIGHT IN ACCORDANCE WITH ASTM E283-04 STANDARD. PERIMETER 
WINDOW FRAMES SHALL BE SEALED.

13 
 
1.4 ALL EXTERIOR SIDE HINGE DOORS SHALL BE SOLID CORE WOOD OR 
INSULATED HOLLOW METAL, AT LEAST 1”, INCHES THICK AND FULLY 
WEATHER STRIPPED. ALL EXTERIOR DOORS OTHER THAN SIDE HINGE DOORS 
SHALL BE SOLID WOOD, FOAM FILLED FIBERGLASS OR METAL 
CONSTRUCTION. 
1.5 FIREPLACES SHALL BE PROVIDED WITH WELL-FITTING DAMPERS. 
1.6 EXTERIOR WALLS SHALL ACHIEVE A MINIMUM OVERALL THERMAL 
RESISTANCE RATING OF 18. (EXTERIOR WALLS SHALL BE AT LEAST FOUR 
INCHES IN NOMINAL THICKNESS AND SHALL BE FINISHED ON THE OUTSIDE 
WITH BLOCK, SIDING, SHEATHING, OR STUCCO ON ONE INCH STYROFOAM. A 
MINIMUM OF R-13 FIBERGLASS OR CELLULOSE INSULATION SHALL BE 
INSTALLED CONTINUOUSLY THROUGHOUT THE CAVITY SPACE WITHIN THE 
WALL.) 
1.7 ALL ROOF SPACES SHALL ACHIEVE A MINIMUM OVERALL THERMAL 
RESISTANCE RATING OF 30. 
2. PERFORMANCE METHOD: 
A CERTIFIED STATEMENT BY A LICENSED ARCHITECT OR ENGINEER CERTIFYING 
THAT THE RESIDENCE ACHIEVES THE REQUIREMENT OF A MAXIMUM INTERIOR 
NOISE LEVEL OF 45 DECIBELS. THE CERTIFIED STATEMENT SHALL INCLUDE TESTING 
AND ANALYSIS DOCUMENTATION SUPPORTING THE STATEMENT.  
AK102.2.1 SOUND ATTENUATION WITHIN THE 65 DECIBEL CONTOUR. 
CONSTRUCTION INSIDE THE AREAS DESIGNATED AS HAVING A DAY-NIGHT AVERAGE 
SOUND LEVEL 65 DECIBELS AS DETERMINED BY THE USE OF THE1988 NOISE 
CONTOUR LINES DEVELOPED BY THE MARICOPA COUNTY ASSOCIATION OF 
GOVERNMENTS SHALL BE DEEMED TO HAVE ACHIEVED THE INTERIOR NOISE LEVEL 
OF 45 DECIBELS SPECIFIED IN ARS 28-8482 WHEN THE RESIDENCES ARE 
CONSTRUCTED USING ONE OF THE FOLLOWING METHODS: 
1. PRESCRIPTIVE METHOD: 
BUILDING SYSTEMS AND COMPONENTS THAT COMPLY WITH THE MARICOPA 
COUNTY ASSOCIATION OF GOVERNMENTS 2013 BUILDING CODE 
AMENDMENTS AND STANDARDS MANUAL, SECTION 1229, APPENDIX A. 
2. PERFORMANCE METHOD: 
A CERTIFIED STATEMENT BY A LICENSED ARCHITECT OR ENGINEER 
CERTIFYING THAT THE RESIDENCE ACHIEVES THE REQUIREMENT OF A 
MAXIMUM INTERIOR NOISE LEVEL OF 45 DECIBELS. THE CERTIFIED 
STATEMENT SHALL INCLUDE TESTING AND ANALYSIS DOCUMENTATION 
SUPPORTING THE STATEMENT.

14 
 
AMENDMENTS TO THE 
ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES 
ICC/ANSI 117.1-2009 
SECTION 502 PARKING SPACES 
502.7 Identification. Where accessible parking spaces are required to be identified by 
signs, the signs shall include the International Symbol of Accessibility complying with Section 
703.6.3.1 OR THE ACCESSIBILITY ICON COMPLYING WITH SECTION 703.6.3.2. Signs 
identifying van parking spaces shall contain the designation "van accessible." Such signs shall 
be 60 inches (1525 mm) minimum above the floor of the parking space, measured to the bottom 
of the sign. 
SECTION 703 SIGNS 
703.6.3.1 International Symbol of Accessibility. The International Symbol of 
Accessibility shall comply with Figure 703.6.3.1. 
 
FIG. 703.6.3.1 INTERNATIONAL SYMBOL OF ACCESSIBILITY 
703.6.3.2 Accessibility Icon. The Accessibility Icon shall comply with Figure 703.6.3.2. 
 
FIG. 703.6.3.2 ACCESSIBILITY ICON

15 
 
AMENDMENTS TO THE 
2018 INTERNATIONAL MECHANICAL CODE 
SECTION 109 MEANS OF APPEAL 
[A] 109.1 Application for appeal GENERAL. APPEALS SHALL BE IN ACCORDANCE 
WITH SECTION 96.01 OF WITH THE EL MIRAGE MUNICIPAL CODE. A person shall have 
the right to appeal a decision of the code official to the board of appeals. An application for 
appeal shall be based on a claim that the true intent of this code or the rules legally adopted 
thereunder have been incorrectly interpreted, the provisions of this code do not fully apply; or an 
equally good or better form of construction is proposed. The application shall be filed on a form 
obtained from the code official within 20 days after the notice was served.  
[A] 109.1.1 Limitation of authority. The board of appeals shall not have authority relative to 
interpretation of the administration of this code nor shall such board be empowered to waive 
requirements of this code. 
SUBSECTIONS 109.2 THROUGH 109.7 ARE DELETED IN THEIR ENTIRETY. 
SECTION 307 CONDENSATE DISPOSAL 
307.2.2 Drain pipe materials and sizes. Components of the condensate disposal system 
shall be cast iron, galvanized steel, copper, cross-linked polyethylene, polybutylene, 
polyethylene, ABS, CPVC or PVC pipe or tubing. NONMETALLIC PIPING SHALL NOT BE 
INSTALLED IN EXPOSED LOCATIONS. All components shall be selected for the pressure and 
temperature rating of the installation. Joints and connections shall be made in accordance with 
the applicable provisions of Chapter 7 of the International Plumbing Code relative to the material 
type. Condensate waste and drain line size shall be not less than 3/4-inch (19 mm) internal 
diameter and shall not decrease in size from the drain pan connection to the place of 
condensate disposal. Where the drain pipes from more than one unit are manifolded together 
for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2. 
SECTION 309 TEMPERATURE CONTROL 
[B] 309.1 Space heating systems HEATING AND COOLING SYSTEMS. Interior 
HABITABLE spaces intended for human occupancy shall be provided with active or passive 
space-heating AND SPACE-COOLING systems capable of maintaining an MINIMUM indoor 
temperatureS of not less than BETWEEN 68 70 °F (20 21°C) AND 90°F (32°C) at a point 3 feet 
(914 mm) above the floor on the design heating day. The installation of portable space heaters 
OR COOLERS shall not be used to achieve compliance with this section. 
SECTION 403 MECHANICAL VENTILATION 
403.3.1.5 Balancing. The ventilation air distribution system shall be provided with means to 
adjust the system to achieve at least the minimum ventilation airflow rate as required by 
Sections 403.3 and403.4. Ventilation systems shall be balanced Sections 403.3 and 403.4. by 
an approved method. Such balancing shall verify that the ventilation system is capable of 
supplying and exhausting the airflow rates required by this code.  A FINAL REPORT SHALL 
BE PROVIDED TO THE ENGINEER OF RECORD AND THE MECHANICAL INSPECTOR.

16 
 
EXCEPTION: RESIDENTIAL OCCUPANCIES SHALL BE EXEMPT FROM THIS 
PROVISION. 
SECTION 407 AMBULATORY CARE FACILITIES AND GROUP I-2 OCCUPANCIES 
407.1 General. Mechanical ventilation for ambulatory care facilities and Group I-2 
occupancies shall be designed and installed in accordance with this code and ASHRAE 170.  
407.1.1 MECHANICAL SYSTEMS DESIGNED AND INSTALLED IN ACCORDANCE WITH 
IMC 407.1 AND ASHRAE 170-2017 SHALL BE VERIFIED BY A QUALIFIED THIRD 
PARTY SPECIAL INSPECTOR. THE SPECIAL INSPECTOR/TESTING AGENCY SHALL 
BE AN INDEPENDENT THIRD PARTY INDIVIDUAL OR FIRM AND SHALL NOT BE THE 
INSTALLING CONTRACTOR. A REPORT SHALL BE GENERATED BY THE THIRD 
PARTY INDIVIDUAL OR FIRM SHOWING COMPLIANCE. SPECIAL INSPECTIONS 
SHALL BE AS SPECIFIED IN CHAPTER 17 OF THE INTERNATIONAL BUILDING CODE 
AS AMENDED. 
SECTION 408 MARIJUANA RELATED OCCUPANCIES 
408.1 GENERAL. ANY BUILDING USED TO CULTIVATE, PRODUCE, INFUSE OR 
DISPENSE MARIJUANA SHALL BE DESIGNED SUCH THAT THERE SHALL BE NO 
EMISSION OF DUST, FUMES, VAPORS, OR ODORS INTO THE ENVIRONMENT FROM THE 
PREMISE. A VENTILATION SYSTEM SHALL BE DESIGNED TO PREVENT THE 
DISTRIBUTION OF ODORS TO OTHER OCCUPIED PARTS OF THE BUILDING OR 
ADJACENT PROPERTIES. DESIGN OF THE ODOR CONTROL SYSTEM SHALL BE BASED 
ON ACCEPTED ENGINEERING PRACTICES. ALL EQUIPMENT AND FILTER MEDIA 
SHALL BE LISTED AND LABELED FOR THE APPLICATION. EXHAUST SYSTEMS USED 
IN ODOR CONTROL SYSTEMS SHALL MEET THE REQUIREMENTS OF SECTION 501.  
408.1.1 EXHAUST OUTLETS. THE TERMINATION POINT FOR EXHAUST OUTLETS 
SHALL BE IN ACCORDANCE WITH SECTION 501.3. EXHAUST FROM CULTIVATION AND 
PRODUCTION FACILITIES SHALL BE IN ACCORDANCE WITH SECTION 501.3.1(2) AND 
FOR DISPENSARIES IN ACCORDANCE WITH SECTION 501.3.1(3). 
SECTION 502 REQUIRED SYSTEMS 
502.14 Motor vehicle operation. In areas where motor vehicles operate, mechanical 
ventilation shall be provided in accordance with Section 403. Additionally, areas in which 
stationary motor vehicles are operated shall be provided with a source capture system that 
connects directly to the motor vehicle exhaust systems. Such system shall be engineered by a 
registered design professional or shall be factor-built equipment designed and sized for the 
purpose. MAKEUP AIR FOR THE REQUIRED EXHAUST SYSTEMS IN AREAS WHERE 
MOTOR VEHICLES OPERATE SHALL BE PROVIDED THROUGH PERMANENT 
UNOBSTRUCTED OPENINGS TO THE OUTDOORS, SUCH AS LOUVERS AND GRILLS. 
MECHANICAL EQUIPMENT AND LOUVERS USED FOR MAKEUP AIR PURPOSES SHALL 
BE ELECTRICALLY INTERLOCKED WITH THE EXHAUST SYSTEM. 
Exceptions: 
1. This section shall not apply where the motor vehicles being operated or repaired are 
electrically powered.

17 
 
2. This section shall not apply to one- and two-family dwellings. 
3. This section shall not apply to motor vehicle service areas where engines are operated 
inside the building only for the duration necessary to move the motor vehicles in and out of 
the building. 
502.21 STORAGE AND USE OF LIQUID CARBON DIOXIDE SYSTEMS - MUST 
CONFORM TO THE 2018 IFC REQUIREMENTS. 
SECTION 928 EVAPORATIVE COOLING EQUIPMENT 
928.1 General. Evaporative cooling equipment shall: 
1. Be installed in accordance with the manufacturer’s instructions. 
2. Be installed on level platforms in accordance with Section 304.10. AN EVAPORATIVE 
COOLER SUPPORTED BY THE BUILDING STRUCTURE SHALL BE INSTALLED ON A 
SUBSTANTIAL LEVEL BASE AND SHALL BE SECURED DIRECTLY OR INDIRECTLY 
TO THE BUILDING STRUCTURE BY SUITABLE MEANS TO PREVENT DISPLACEMENT 
OF THE COOLER. MODIFICATIONS MADE TO THE SUPPORTING FRAMEWORK OF 
BUILDINGS AS A RESULT OF THE INSTALLATION SHALL BE MADE IN 
ACCORDANCE WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING 
CODE AS AMENDED. 
3. Have openings in exterior walls or roofs flashed in accordance with the International 
Building Code as amended. 
4. Be provided with potable water backflow protection in accordance with Section 608 of the 
International Building Code. 
5. Have air intake opening locations in accordance with Section 401.4. 
6. A PERMANENT RELIEF OPENING OR OTHER ENGINEERED DESIGN SUFFICIENT 
TO ASSURE POSITIVE AIRFLOW SHALL BALANCE INTAKE AIR. 
7. OUTSIDE AIR SHALL BE PROVIDED AS SPECIFIED IN SECTION 403.2. 
8. AIR DUCTS AND DAMPERS, WHICH ARE A PORTION OF AN EVAPORATIVE 
COOLING SYSTEM, SHALL COMPLY WITH CHAPTER 6. 
9. OVERFLOW DRAINS SHALL BE PROVIDED THAT DISCHARGE TO AN APPROVED 
DISPOSAL LOCATION. 
SECTION 930 WOODSTOVE/FIREPLACE INSTALLATION 
DEFINITIONS. FOR PURPOSES OF THIS SECTION, THE FOLLOWING WORDS AND 
TERMS SHALL HAVE THE MEANING ASCRIBED THERETO: 
FIREPLACE: A BUILT-IN-PLACE MASONRY HEARTH AND FIRE CHAMBER OR A 
FACTORY-BUILT APPLIANCE, DESIGNED TO BURN SOLID FUEL OR TO 
ACCOMMODATE GAS OR ELECTRIC LOG INSERT OR SIMILAR DEVICE, AND WHICH 
IS INTENDED FOR OCCASIONAL RECREATIONAL OR AESTHETIC USE, NOT FOR 
COOKING, HEATING, OR INDUSTRIAL PROCESSES.

18 
 
SOLID FUEL: INCLUDES, BUT IS NOT LIMITED TO, WOOD, COAL, OR OTHER NON-
GASEOUS OR NON-LIQUID FUELS, INCLUDING THOSE FUELS DEFINED BY THE 
MARICOPA COUNTY AIR POLLUTION CONTROL OFFICER AS "INAPPROPRIATE 
FUEL" TO BURN IN RESIDENTIAL WOOD BURNING DEVICES. 
WOODSTOVE: A SOLID-FUEL BURNING HEATING APPLIANCE INCLUDING A 
PELLET STOVE, WHICH IS EITHER FREESTANDING OR DESIGNED TO BE INSERTED 
INTO A FIREPLACE. 
930.2 GENERAL. IN ACCORDANCE WITH MARICOPA COUNTY REGULATIONS, ON 
OR AFTER DECEMBER 31, 1998, NO 
PERSON, FIRM OR CORPORATION SHALL CONSTRUCT OR INSTALL A FIREPLACE OR 
A WOOD STOVE, AND THE BUILDING OFFICIAL SHALL NOT APPROVE OR ISSUE A 
PERMIT TO CONSTRUCT OR INSTALL A FIREPLACE OR A WOOD STOVE, UNLESS THE 
FIREPLACE OR WOOD STOVE COMPLIES WITH ONE OF THE FOLLOWING: 
1. A FIREPLACE WHICH HAS A PERMANENTLY INSTALLED GAS OR ELECTRIC LOG 
INSERT; 
2. A FIREPLACE, WOOD STOVE OR OTHER SOLID FUEL BURNING APPLIANCE 
WHICH HAS BEEN CERTIFIED BY THE UNITED STATES ENVIRONMENTAL 
PROTECTION AGENCY AS CONFORMING TO 40 CODE OF FEDERAL REGULATIONS 
PART 60, SUBPART AAA; 
3. A FIREPLACE, WOODSTOVE OR OTHER SOLID FUEL BURNING APPLIANCE THAT 
HAS BEEN TESTED AND LISTED BY A NATIONALLY RECOGNIZED TESTING 
AGENCY TO MEET PERFORMANCE STANDARDS EQUIVALENT TO THOSE 
ADOPTED BY40 CODE OF FEDERAL REGULATIONS PART 60, SUBPART AAA; 
4. A FIREPLACE, WOOD STOVE OR OTHER SOLID FUEL BURNING APPLIANCE 
WHICH HAS BEEN DETERMINED BY THE MARICOPA COUNTY AIR POLLUTION 
CONTROL OFFICER TO MEET PERFORMANCE STANDARDS EQUIVALENT TO 
THOSE ADOPTED BY 40 CODE OF FEDERAL REGULATIONS PART 60, SUBPART 
AAA, AS IN EFFECT ON JULY 1, 1990. 
5. A FIREPLACE WHICH HAS A PERMANENTLY INSTALLED WOOD STOVE INSERT 
WHICH COMPLIES WITH SUBPARAGRAPH2, 3, OR 4 ABOVE. 
EXCEPTIONS: THE FOLLOWING INSTALLATIONS ARE NOT REGULATED AND 
ARE NOT PROHIBITED BY THIS SECTION: 
1. FURNACES, BOILERS, INCINERATORS, KILNS, AND OTHER SIMILAR SPACE 
HEATING OR INDUSTRIAL PROCESS EQUIPMENT. 
2. COOK STOVES, BARBECUE GRILLS, AND SIMILAR APPLIANCES DESIGNED 
PRIMARILY FOR COOKING. 
3. FIRE PITS, BARBECUE GRILLS, AND OTHER OUTDOOR FIREPLACES.

19 
 
AMENDMENTS TO THE 
2018 INTERNATIONAL PLUMBING CODE 
APPENDICES B, C and E ARE EXPRESSLY ADOPTED AND INCORPORATED HEREIN BY 
THIS REFERENCE.  
SECTION 109 MEANS OF APPEAL 
[A] 109.1 Application for appeal GENERAL. APPEALS SHALL BE IN ACCORDANCE 
WITH THE EL MIRAGE MUNICIPAL CODE. Any person shall have the right to appeal a 
decision of the code official to the board of appeals. An application for appeal shall be based on 
a claim that the true intent of this code or the rules legally adopted thereunder have been 
incorrectly interpreted, the provisions of this code do not fully apply; or an equally good or better 
form of construction is proposed. The application shall be filed on a form obtained from the code 
official within 20 days after the notice was served. 
SUBSECTIONS 109.2 THROUGH 109.7 ARE DELETED IN THEIR ENTIRETY. 
 
SECTION 202 GENERAL DEFINITIONS 
GREASE INTERCEPTOR 
Gravity. Plumbing appurtenances of not less than 500 gallons (1893 L) capacity that are 
installed in the sanitary drainage system to intercept free-floating fats, oils and grease from 
waste water discharge.  Separation is accomplished by gravity during a retention time of not 
less than 30 minutes APPROVED BY THE AUTHORITY HAVING JURISDICTION. 
GREASE REMOVAL DEVICE, AUTOMATIC (GRD). A plumbing appurtenance that is installed 
in the sanitary drainage system to intercept free-floating fats, oils and grease from waste water 
discharge. Such a device operates on a time-or event-controlled basis and has the ability to 
remove free-floating fats, oils and grease automatically without intervention from the use except 
for maintenance. THESE DEVICES MUST BE ABLE TO PERFORM AS A GRAVITY 
INTERCEPTOR IF MECHANICAL OR ELECTRICAL POWER IS LOST AND PROVIDE 
CONTINUOUS SEPARATION. 
SECTION 410 DRINKING FOUNTAINS 
410.2 Small occupancies. Drinking fountains shall not be required for an occupant load of 
50 or fewer. 
410.4 Substitution. Where restaurants provide drinking water in a container free of charge, 
drinking fountains shall not be required in those restaurants. In other occupancies, where 
drinking fountains are required, WATER COOLERS OR BOTTLED water dispensers shall be 
permitted to be substituted for not more than 50 percent of the required number of drinking 
fountains. IN OTHER OCCUPANCIES, WHERE DRINKING FOUNTAINS ARE REQUIRED, 
BOTTLED WATER DISPENSERS OR WATER COOLERS SHALL BE PERMITTED TO BE 
SUBSTITUTED.

20 
 
SECTION 1003 INTERCEPTORS AND SEPARATORS 
1003.2 Approval. The size, type, and location of each interceptor and of each separator 
shall be designed and installed in accordance with the manufacturer’s instructions and the 
requirements of this section based on the anticipated conditions of use AND PURSUANT TO 
THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. Wastes that do not 
require treatment or separation shall not be discharged into any interceptor or separator. 
SECTION 1106 SIZE OF CONDUCTORS, LEADERS AND STORM DRAINS 
1106.1 General. The size of the vertical conductors and leaders, building storm drains, 
building storm sewers, and any horizontal branches of such drains or sewers shall be based on 
the 100 year hourly rainfall rate indicated in Figure 1106.1 or on other rainfall rates determined 
from approved local weather data AN HOURLY RAINFALL RATE OF THREE (3) INCHES 
PER HOUR.  
 
AMENDMENTS TO THE 
2018 INTERNALTIONAL FUEL GAS CODE  
 
SECTION 109 MEANS OF APPEAL 
[A] 109.1 Application for appeal GENERAL. APPEALS SHALL BE IN ACCORDANCE 
WITH THE EL MIRAGE MUNICIPAL CODE. A person shall have the right to appeal a decision 
of the code official to the board of appeals. An application for appeal shall be based on a claim 
that the true intent of this code or the rules legally adopted thereunder have been incorrectly 
interpreted, the provisions of this code do not fully apply; or an equally good or better form of 
construction is proposed. The application shall be filed on a form obtained from the code official 
within 20 days after the notice was served. 
SUBSECTIONS 109.2 THROUGH 109.7 ARE DELETED IN THEIR ENTIRETY. 
SECTION 404 (IFGC) PIPING SYSTEM INSTALLATION 
404.12 Minimum burial depth. Underground piping systems shall be installed a minimum 
depth of 12 inches (305 mm) below grade, except as provided for in Section 404.12.1 for metal 
piping and 18 inches (457mm) for plastic piping. 
 
AMENDMENTS TO THE 
2018 INTERNATIONAL ENERGY CONSERVATION CODE  
 
SECTION C101 SCOPE AND GENERAL REQUIREMENTS(COMMERCIAL) 
C101.2 Scope. This code applies to commercial buildings and the building sites and 
associated systems and equipment. GROUP R-2 WHEN DEFINED AS A COMMERCIAL 
BUILDING BY SECTION C202, SHALL HAVE THE OPTION OF COMPLYING UNDER THE

21 
 
RESIDENTIAL PROVISIONS OF THE CODE, REGARDLESS OF HEIGHT. ONCE DEFINED 
AS SUCH ON THE SUBMITTAL DOCUMENTS, ALL COMPONENTS OF THE RESIDENTIAL 
PROVISIONS SHALL BE FOLLOWED. 
SECTION C109 BOARD OF APPEALS 
C109.1 General. APPEALS SHALL BE IN ACCORDANCE WITH THE EL MIRAGE 
MUNICIPAL CODE. In order to hear and decide appeals of orders, decisions or determinations 
made by the code official relative to the application and interpretation of this code, there shall be 
and is hereby created a board of appeals. The Code Official shall be an ex officio member of 
said board but shall have no vote on any matter before the board. The board of appeals shall be 
appointed by the governing body and shall hold office at its pleasure. The board shall adopt 
rules of procedure for conducting its business and shall render all decisions and findings 
inwriting to the appellant with a duplicate copy to the Code Official.  
SUBSECTIONS 109.2 THROUGH 109.3 ARE DELETED IN THEIR ENTIRETY. 
SECTION C401 GENERAL 
C401.2 Application. Commercial buildings shall comply with one of the following: 
1. The requirements of ANSI/ASHRAE/IESNA 90.1. 
2. The requirements of Sections C402 through C405 and C408. In addition, commercial 
buildings shall comply with Section C406 and tenant spaces shall comply with Section 
C406.1.1. 
3. The requirements of Sections C402.5, C403.2, C403.3 through C403.3.2, C403.4 
through C403.4.2.3, C403.5.5, C403.7, C403.8.1 through C403.8.4, C403.10.1 through 
C403.10.3, C403.11, C403.12, C404, C405, and C407 and C408. The building energy cost shall 
be equal to or less than 85 percent of the standard reference design building. 
4. COMPLIANCE WITH THE PROVISIONS OF SECTION C408 ARE OPTIONAL. 
SECTION R101 SCOPE AND GENERAL REQUIREMENTS 
R101.2 Scope. This code applies to residential buildings and the building sites and 
associated systems and equipment. GROUP R-2 WHEN DEFINED AS A RESIDENTIAL 
BUILDING BY SECTION R202, SHALL HAVE THE OPTION OF COMPLYING UNDER THE 
COMMERCIAL PROVISIONS OF THE CODE, REGARDLESS OF HEIGHT. ONCE DEFINED 
AS SUCH ON THE SUBMITTAL DOCUMENTS, ALL COMPONENTS OF THE COMMERCIAL 
PROVISIONS SHALL BE FOLLOWED. 
SECTION R109 BOARD OF APPEALS 
R109.1 General. APPEALS SHALL BE IN ACCORDANCE WITH SECTION 96.01 OF THE 
EL MIRAGE MUNICIPAL CODE. In order to hear and decide appeals of orders, decisions or 
determinations made by the code official relative to the application and interpretation of this 
code, there shall be and is hereby created a board of appeals. The Code Official shall be an ex 
officio member of said board but shall have no vote on any matter before the board. The board 
of appeals shall be appointed by the governing body and shall hold office at its pleasure. The

22 
 
board shall adopt rules of procedure for conducting its business and shall render all decisions 
and findings inwriting to the appellant with a duplicate copy to the Code Official. 
SUBSECTIONS 109.2 THROUGH 109.3 ARE DELETED IN THEIR ENTIRETY 
SECTION R403 SYSTEMS 
R403.3 Ducts. Ducts and air handlers shall be in accordance with Sections R403.3.1 
throughR403.3.7.  
R403.3.1 Insulation (Prescriptive). SUPPLY DUCTS IN ATTICS SHALL BE 
INSULATED TO A MINIMUM OF R-8. DUCTS IN FLOOR TRUSSES SHALL BE 
INSULATED TO A MINIMUM OF R-6. Supply and return ducts in attics shall be 
insulated to an R-value of not less than R-8 for ducts 3 inches (76 mm) in diameter and 
larger and not less than R-6 for ducts smaller than 3 inches (76 mm) in diameter.  
Supply and return ducts in other portions of the building shall be insulated to not less 
than R-6 for ducts 3 inches (76 mm) in diameter and not less than R-4.2 for ducts 
smaller than 3 inches (76 mm) in diameter. 
Exceptions: Ducts or portions thereof located completely inside the building thermal 
envelope. 
1. DUCTS OR PORTIONS THEREOF LOCATED COMPLETELY INSIDE THE 
BUILDING THERMAL ENVELOPE. 
2. SUPPLY DUCTS MAY BE INSULATED TO A MINIMUM OF R-6 WHEN ONE 
OR MORE OF THE FOLLOWING CONDITIONS ARE MET; 
2.1 MINIMUM SEER RATING OF SPACE HEATING/COOLING 
SYSTEM IS INCREASED TO 15. 
2.2 MAXIMUM U-FACTOR IS DECREASED TO 0.35 AND MAXIMUM 
SHGC IS DECREASED TO 0.22 FOR ALL FENESTRATION 
PRODUCTS. 
2.3 WALL CAVITY INSULATION MINIMUM R-VALUE IS INCREASED 
TO R-19. 
2.4 RESIDENTIAL BUILDINGS THAT MEET THE REQUIREMENTS OF 
SECTIONS R102.1.1 OR R405. 
Section R403.10.3 Covers VARIABLE SPEED POOL PUMPS. 
Outdoor heated pools and outdoor permanent spas shall be provided with a vapor-retardant 
cover or other approved vapor-retardant means. 
Exception: Where more than 75 percent of the energy for heating, computed over an 
operation season of not less than three calendar months, is from a heat pump or an on-site 
renewable energy system, covers or other vapor-retardant means shall not be required. 
MOTORS WITH A TOTAL HORSEPOWER OF ONE OR MORE FOR POOLS AND IN-
GROUND PERMANENTLY INSTALLED SPAS SHALL HAVE THE CAPABILITY OF 
OPERATING AT TWO OR MORE SPEEDS WITH A LOW SPEED HAVING A ROTATION

23 
 
RATE THAT IS NO MORE THAN ONE-HALF OF THE MOTOR'S MAXIMUM ROTATION 
RATE AND SHALL BE OPERATED WITH A PUMP CONTROL WITH THE CAPABILITY OF 
OPERATING THE PUMP AT TWO OR MORE SPEEDS. RESIDENTIAL POOL PUMP MOTOR 
CONTROLS THAT ARE SOLD FOR USE WITH A TWO OR MORE SPEED MOTOR SHALL 
HAVE A DEFAULT CIRCULATION SPEED SETTING NO MORE THAN ONE-HALF OF THE 
MOTOR'S MAXIMUM ROTATION RATE. ANY HIGH SPEED OVERRIDE CAPABILITY 
SHALL BE FOR A TEMPORARY PERIOD NOT TO EXCEED ONE TWENTY-FOUR HOUR 
CYCLE WITHOUT RESETTING TO THE DEFAULT SETTING. 
 
AMENDMENTS TO THE 
2018 INTERNATIONAL EXISTING BUILDING CODE 
 
SECTION 112 BOARD OF APPEALS 
[A] 112.1 General. APPEALS SHALL BE IN ACCORDANCE WITH SECTION 96.01 OF 
THE EL MIRAGE MUNICIPAL CODE. In order to hear  and decide appeals of orders, 
decisions, or determinations made by the Code Official relative to the application and 
interpretation of this Code, there shall be and is hereby created a board of appeals. The board 
of appeals shall be appointed by the governing body and shall hold office at its pleasure. The  
board shall adopt rules of procedure for conducting its business.  
SUBSECTIONS 112.2 THROUGH 112.3 ARE DELETED IN THEIR ENTIRETY 
 
 
AMENDMENTS TO THE 
2018 INTERNATIONAL GREEN CONSTRUCTION CODE 
 
SECTION 101 GENERAL 
101 General. THE USE OF THIS CODE IS OPTIONAL, UNLESS SPECIFICALLY 
REQUIRED THROUGH ORDINANCE BY THE CITY OF EL MIRAGE. This code is an overlay 
document to be used in conjunction with the other codes and standards adopted by the 
jurisdiction. This code is not intended to be used as a standalone construction regulation 
document and permits are not to be issued under this code. This code is not intended to abridge 
or supersede safety, health or environmental requirements under other applicable codes or 
ordinances.

24 
 
AMENDMENTS TO THE 
2018 INTERNATIONAL PROPERTY MAINTENANCE CODE 
 
101.1 Title. These regulations shall be known as the International Property Maintenance 
Code of [NAME OF JURISDICTION] THE CITY OF EL MIRAGE hereinafter referred to as “this 
code.” 
SECTION 111 MEANS OF APPEAL 
THE APPEAL PROCESS SHALL BE AS OUTLINED IN SECTION 96.01 OF THE EL MIRAGE 
MUNICIPAL CODE.  
THE REMAINDER OF THIS SECTION IS DELETED IN ITS ENTIRETY. 
SECTION 303 SWIMMING POOLS, SPAS AND HOT TUBS 
303.2 Enclosures.  
THIS SUBSECTION IS DELETED IN ITS ENTIRETY. 
 
AMENDMENTS TO THE 
2017 NATIONAL ELECTRICAL CODE 
 
Article 250 – Grounding and Bonding 
250.118 Types of Equipment Grounding Conductors. 
Each equipment grounding conductor run with or enclosing the circuit conductors shall be one 
or more or a combination of the following: 
(1) A copper, aluminum, or copper-clad aluminum conductor. This conductor shall be solid or 
stranded; insulated, covered, or bare; and in the form of a wire or a busbar of any shape. 
(2) Rigid metal conduit. 
(3) Intermediate metal conduit. 
(4) Electrical metallic tubing WITH AN ADDITIONAL EQUIPMENT GROUNDING 
CONDUCTOR. 
(5) Listed flexible metal conduit meeting all the following conditions: 
a. The conduit is terminated in listed fittings. 
b. The circuit conductors contained in the conduit are protected by overcurrent devices 
rated at 20 amperes or less. 
c. The combined length of flexible metal conduit and flexible metallic tubing and liquid 
tight flexible metal conduit in the same ground-fault current path does not exceed 1.8 m 
(6 ft).

25 
 
d. If used to connect equipment where flexibility is necessary to minimize the 
transmission of vibration from equipment or to provide flexibility for equipment that 
requires movement after installation, an equipment grounding conductor shall be 
installed. 
(6) Listed liquid tight flexible metal conduit meeting all the following conditions: 
a. The conduit is terminated in listed fittings. 
b. For metric designators 12 through 16 (trade sizes 3/8 through 1/2), the circuit 
conductors contained in the conduit are protected by overcurrent devices rated at 20 
amperes or less. 
c. For metric designators 21 through 35 (trade sizes 3/4 through 1-1/4), the circuit 
conductors contained in the conduit are protected by overcurrent devices rated not more 
than 60 amperes and there is no flexible metal conduit, flexible metallic tubing, or liquid 
tight flexible metal conduit in trade sizes metric designators 12 through 16 (trade sizes 
3/8 through 1/2) in the ground-fault current path. 
d. The combined length of flexible metal conduit and flexible metallic tubing and liquid 
tight flexible metal conduit in the same ground-fault current path does not exceed 1.8 m 
(6 ft). 
e. If used to connect equipment where flexibility is necessary to minimize the 
transmission of vibration from equipment or to provide flexibility for equipment that 
requires movement after installation, an equipment grounding conductor shall be 
installed. 
(7) Flexible metallic tubing where the tubing is terminated in listed fittings and meeting the 
following conditions: 
a. The circuit conductors contained in the tubing are protected by overcurrent devices 
rated  20 amperes or less. 
b. The combined length of flexible metal conduit and flexible metallic tubing and liquid 
tight flexible metal conduit in the same ground-fault current path does not exceed 1.8 m 
(6 ft). 
(8) Armor of Type AC cable as provided in 320.108. 
(9) The copper sheath of mineral-insulated, metal-sheathed cable. 
(10) Type MC cable that provides an effective ground-fault current path in accordance with one 
or more of the following: 
a. It contains an insulated or uninsulated equipment grounding conductor in compliance 
with 250.118(1) 
b. The combined metallic sheath and uninsulated equipment grounding/bonding 
conductor of interlocked metal tape–type MC cable that is listed and identified as an 
equipment grounding conductor

26 
 
c. The metallic sheath or the combined metallic sheath and equipment grounding 
conductors of the smooth or corrugated tube-type MC cable that is listed and identified 
as an equipment grounding conductor 
(11) Cable trays as permitted in 392.10 and 392.60. 
(12) Cable bus framework as permitted in 370.3. 
(13) Other listed electrically continuous metal raceways and listed auxiliary gutters. 
(14) Surface metal raceways listed for grounding.