April 9, 2025 Z2024012 Page 1 of 3 Report to the Board of Supervisors Prepared by the Maricopa County Planning and Development Department Board Hearing Date: April 9, 2025 Case #/Title: Z2024012 – Saguaro BESS Supervisor District: 4 Applicants/Owner: Jennifer Hall and Ty Utton, Rose Law/Desert Forrest Nursery LLC and FHF LLC Request: Zone Change with Overlay from C-2 CUPD to IND-2 IUPD Site Location: Generally located 1,500’ southeast from the intersection of Olive Ave. and Cotton Ln. in west Glendale area Site Size: Approximately 10.5 acres County Island Status: Yes, City of Glendale Additional Comments: This case was originally sent to the Board on September 12, 2024, with a Commission recommendation for denial. The Board remanded the matter. The applicant modified his project to meet a minimum 500’ separation distance between BESS units and existing residences. Staff considers this separation to be a best practice. Rural Metro Fire Department (RMFD) remains supportive of the request and maintains a fire station within two blocks of the site. There are no outstanding concerns from reviewing agencies. There is no known public opposition. Commission Recommendation: On 3/6/25, the Commission voted 9-0 to adopt a motion recommending the Board of Supervisors approve Z2024012 subject to conditions ‘a’ – ‘h’: a. Development of the site shall be in substantial conformance with the Zoning Exhibit entitled “Saguaro BESS Project“, consisting of 1 full-size sheet, dated January 31, 2025 and except as modified by the following conditions. Staff may determine slight refinements to remain in substantial conformance with the approved site plan. Minor and major amendments to the site plan will be determined in accordance with Chapter 3 of the Maricopa County Zoning Ordinance. b. Development of the site shall be in substantial conformance with the Narrative Report entitled “Saguaro BESS Project”, consisting of 6 pages, dated February 1, 2025, except as modified by the following conditions. April 9, 2025 Z2024012 Page 2 of 3 c. Prior to issuance of initial building permits, all parcels shall be combined to create a single parcel matching the zoning exhibit of Z2024012. d. The following IND-2 IUPD zoning regulations will apply: 1. Allowed uses: MCZO Sec. 902.2.17 2. Prohibited uses: Adult Oriented facilities, Automobile repair shops and garages, and Drive-thrus for restaurants. 3. Setbacks (minimums) A. Min. setback for BESS units from all lot lines: 100’ B. Min. separation for BESS units from from any existing, permitted dwelling units: 500’ 4. Min. Parking: 2 spaces with one ADA accessible space 5. MCZO 902.9.1: The activities and operations associated with the BESS use are not required to be conducted within a completely enclosed building. 6. Standards for Billboards: A. Max. Off-Site Sign Height: Max. 70’ on side directly abutting and oriented to or within 150’ of Loop 303. Max. 45’ on side directly abutting and oriented to Cotton Lane B. Off-Site Sign Separation Distance: Maximum 2 off-site signs oriented to or within 150’ of Loop 303 at minimum 700’ separation distance. C. Off-Site Signs: Maximum of 2 off-site signs permitted on side directly abutting and oriented to Loop 303. A maximum of 1 off-site sign permitted on side directly abutting and oriented to Cotton Lane and setback a minimum of 500’ from the centerline of Olive Avenue. No other off-site signs permitted. D. Off-Site Sign Max Size: 672 square feet E. Min. Rear (East) Yard Setback (billboard only): 0’ F. Min. Setback to RU-43 or R1-6 RUPD: 0’ East and North, 50’ South G. Min. Setback to RU-43 or R1-6 RUPD for illuminated off-site sign: 0’ East and North 50’ South H. Min. 6’ height screening adjacent to rural or residential zoning boundary: Zero screening unless POD submitted for use other than billboard or nursery 7. The IUPD shall limit entitled uses to battery energy storage systems (BESS) and photovoltaic solar power generation and ancillary uses, billboards per condition ‘d.5.3’, and uses permitted in the C-2 CUPD zoning district. e. The following Planning Engineering conditions shall apply: 1. Without the submittal of a precise plan of development, no development approval is inferred by this review, including, but not limited to number of proposed building lots/units, drainage design, access and roadway alignments. These items will be addressed as development plans progress and are submitted to the County for further review and/or entitlement. 2. A traffic impact study must be submitted with future entitlement (POD or Preliminary Plat) application(s). 3. Engineering review of re-zone case is conceptual in nature. All development and engineering design shall be in conformance with Section 1205 of the Maricopa County Zoning Ordinance; Drainage Policies and Standards; Floodplain Regulations for Maricopa County; MCDOT Roadway Design Manual; and current April 9, 2025 Z2024012 Page 3 of 3 engineering policies, standards and best practices at the time of application for construction. f. Noncompliance with any Maricopa County regulation shall be grounds for initiating a revocation of this zone change as set forth in the Maricopa County Zoning Ordinance. g. The property owner/s and their successors waive claim for diminution in value if Maricopa County takes action to rescind approval due to noncompliance with conditions. h. The granting of this change in use of the property has been at the request of the applicant, with the consent of the landowner. The granting of this approval allows the property to enjoy uses in excess of those permitted by the zoning existing on the date of application, subject to conditions. In the event of the failure to comply with any condition, the property shall revert to the zoning that existed on the date of application. It is, therefore, stipulated and agreed that either revocation due to the failure to comply with any conditions, does not reduce any rights that existed on the date of application to use, divide, sell or possess the property and that there would be no diminution in value of the property from the value it held on the date of application due to such revocation of the zone change. The zone change enhances the value of the property above its value as of the date the zone change is granted and reverting to the prior zoning results in the same value of the property as if the zone change had never been granted. Presented by: Joel Landis, Planner Reviewed by: Darren Gérard, AICP, Planning Manager Attachments: 3/6/25 P&Z Packet (64 pages) 3/6/25 PZ Handout Memo (2 pages) Note: 3/6/25 Draft P&Z Minutes are not available as of the writing of this report, but can be provided upon request later when available. Z2024012 Page 1 of 8 Report to the Planning and Zoning Commission Prepared by the Maricopa County Planning and Development Department Case: Z2024012 – Saguaro BESS Hearing Date: March 6, 2025 Supervisor District: 4 Applicants: Jennifer Hall and Ty Utton, Rose Law Group Owners: Desert Forrest Nursery LLC and FHF LLC Request: Zone Change with Overlay from C-2 CUPD to IND-2 IUPD Site Location: Generally located 1,500’ southeast from the intersection of Olive Ave. and Cotton Ln. in west Glendale area Site Size: Approximately 10.5 acres Density: N/A County Island: Yes, City of Glendale County Plan: White Tank/Grand Avenue Area Plan – Single-Family Rural Municipal Plan: City of Glendale – Regional Mixed Use Municipal Comments: None received to date Support/Opposition: One petition with eight signatures in support. The Rural/Metro Fire Marshal supports the request. There is no known opposition. Recommendation: Approve with conditions Z2024012 Page 2 of 8 Project Summary: 1. The applicant is proposing to rezone the site from C-2 CUPD to IND-2 IUPD to develop a 250 MW utility-scale battery energy storage system (BESS) facility and substation on a 10.5-acre portion of a 38.5 acre site located just northwest of the intersection of Loop 303 and Northern Parkway. The project’s intention is to store and release generated power within battery systems to be used in times of excess service demand. This facility would be capable of storing enough electricity to power approximately 80,000 end-users for up to four hours, increasing the overall resiliency of the valley’s power systems. The facility will be connected via a transmission line easement to the under-development APS Parkway Station located north of Olive Ave. within City of Glendale jurisdiction. 2. Historical aerials indicate this site having been used for agriculture for several decades before the development of Loop 303 which lies just east of the site. This use has continued to the present despite recent attempts to redevelop. Most recently, the subject site was part of a larger rezone of 38.5 acres southeast of Cotton Ln. and Olive Ave. from Rural-43 to C-2 CUPD under case Z2019129, ostensibly to allow a retail component for a plant nursery on-site which was operating under a prior approved agricultural exemption. 3. Said rezone only limited a few select incompatible uses while allowing most other C-2 uses. The only new developments on the site were two billboards along Loop 303 on what is currently APN 501-05-006M. As the subject 10.5 acres are split between several parcels, the applicant is currently undergoing the process of redelineating parcels. It is conceivable the rest of the parcel outside of the 10.5-acres could redevelop soon to any number of commercial or residential uses. 4. This application was heard at the September 12, 2024 Planning and Zoning Commission hearing and received a motion for denial by the Commission due to concerns with the proximity of the site to the nearby residential zoning to the south. At the October 23, 2024 Board of Supervisors hearing, the Board motioned to remand this case back to the Commission to allow the applicant to redesign the site such so that it was less noxious to nearby uses. As such, the applicant has presented a new site plan and narrative report in line with the original staff conditions indicating a min. 100’ setback for BESS units to all lot lines and a min. 500’ separation for BESS units from dwelling units. As designed, the nearest BESS unit is 548’ from the northern most parcel line of the southern residential subdivision. The following tables) include the differed site standards under the proposed IND-2 IUPD overlay (changes highlighted in bold): REGULATION BASE ZONING DISTRICT REGULATIONS (C-2) PROPOSED ZONING DISTRICT REGULATIONS (IND-2 IUPD) Minimum Front Yard (w) 10’ 100’ for BESS units Minimum Side Yard (n/s) 10' 100’ for BESS units Minimum Rear Yard (e) 25' 100’ for BESS units Minimum Distance from BESS Cabinets to Existing Residential Dwelling Units N/A 500’ Parking Spaces See parking regulations 2 spaces w. 1 ADA space Screening 6' solid wall Min. 8’ masonry wall MCZO 902.9.1 Regulations All uses except for parking, unloading, or storage shall be conducted within a completely enclosed building The activities and operations associated with the BESS use are not required to be conducted within a completely enclosed building Z2024012 Page 3 of 8 BILL BOARD REGULATIONS BASE ZONING DISTRICT REGULATIONS (C-2) PROPOSED ZONING DISTRICT REGULATIONS (IND-2 IUPD) Max. Off-site Sign Height 30’ Max. 70’ on side directly abutting and oriented to within 150’ of Loop 303. Max 45’ on side directly abutting and oriented to Cotton Ln. Off-Site Sign Separation Distance 1000’ Max. 2 off-site signs oriented to or within 150’ of Loop 303 at minimum 700’ separation distance. Off-site Signs Permitted Maximum of 2 off-site signs permitted on side directly abutting and oriented to Loop 303. A maximum of 1 off-site sign permitted on side directly abutting and oriented to Cotton Lane and setback a minimum of 500’ from the centerline of Olive Ave. No other off-site signs permitted. Off-site Sign Max Size 300 sq. ft. 672 sq. ft. Min. Rear (e) Yard Setback (Only for APN 501-05-006M) (billboard only) 25’ 0’ Min. Setback to RU-43 and R1-7 RUPD (billboard only) 100’ 0’ East and North 50’ South Min. Setback to RU-43 and R1-7 RUPD for illuminated off-site sign 150’ 0’ East and North 50’ South Min. 6’ height screening adjacent to rural or residential zoning boundary 6’ height along residential zoning Zero screening unless POD submitted for use other than billboard or plant nursery Z2024012 Page 4 of 8 Aerial photo of the site circa 2024, oriented north. Zoning exhibit showing proposed conceptual site development. No Plan of Development has been included with this proposal. Z2024012 Page 5 of 8 Existing On-Site and Adjacent Zoning / Land Use: 5. On-site: C-2 CUPD / Plant Nursery North: C-2 CUPD / Plant Nursery South: R1-6 RUPD Single-family residences East: Rural-43 / AZ-303 West: C-2 CUPD/Rural-43 / Plant Nursery/Rural residences Utilities and Services: 6. Water: EPCOR Electric: APS Fire: Rural Metro Police: Maricopa County Sheriff Right-of-Way: 7. The following table includes existing and proposed half-width right-of-way and the future classification based upon the Maricopa County Department of Transportation (MCDOT) Major Streets and Routes Plan. Street Name Half-width Existing R/W Half-width Proposed R/W Future Classification Cotton Ln. 50’ 80’ Major Collector Olive Ave. 50’ 80’ Major Collector Adopted Plans: 8. City of Glendale General Plan (adopted 2016): The Regional Mixed Use designation is designed to encourage new, multi-modal, mixed-use development in regionally significant areas. 9. White Tank/Grand Avenue Plan (adopted 2023): Density of 1 dwelling unit or less per gross acre with Single-family Rural. Public Participation Summary: 10. The applicant complied with the Maricopa County Public Participation Process with the required posting of the property and notification by first class mail to the adjacent property owners within 300’ of the subject site and interested parties. The applicant has provided a list of 8 signatures of property owners from the nearby residential communities indicating support of the project. 11. The applicant provided correspondence from Rural Metro indicating their support for the project. They have indicated the proximity of the site to a nearby station, setbacks, and proposed site design as allowing them to be comfortable in providing their support. Outstanding Concerns from Reviewing Agencies: 12. N/A Z2024012 Page 6 of 8 Staff Analysis: 13. Staff is supportive of this request, noting that Rural Metro has no concerns regarding the development. BESS facilities are still quite new and while there have been limited instances of such facilities causing dangers to surrounding communities, the proximity of this site to such communities raised concerns for staff prior to the first Commission hearing in September of 2024. Staff generally takes the position that 500’ would be an appropriate boundary between a BESS site and nearby residential zoning upon advice from local fire marshals. After redesign, this site is 548’ from the nearest residential parcel boundary. Staff feels the site is in a far more appropriate location than what was prior submitted. There remain concerns regarding the remaining C-2 zoning to the west of the subject site. It is the case that residential uses are allowed in commercially zoned districts. While these concerns are somewhat alleviated by graduated density concept for sites near Luke AFB, staff cannot guarantee that residential will not develop on these sites. Furthermore, such developments could be done administratively without further review by the public, Planning and Zoning Commission, and Board of Supervisors. 14. Staff does recognize the mitigation of these risks by the proximity of the fire station and support of Rural Metro as the primary factor in recommending approval, but the positive aspects of BESS facilities are important to note as well. BESS facilities provide a unique solution to energy need issues within the local power grid. As the west valley continues to grow, such facilities will be key in preventing service interruptions that could be catastrophic during the hottest parts of the year. Recommendation: 15. Staff recommends the Commission adopt a motion recommending that the Board of Supervisors approve Z2024012 subject to the following conditions ‘a’ – ‘h’: a. Development of the site shall be in substantial conformance with the Zoning Exhibit entitled “Saguaro BESS Project“, consisting of 1 full-size sheet, dated January 31, 2025 and except as modified by the following conditions. Staff may determine slight refinements to remain in substantial conformance with the approved site plan. Minor and major amendments to the site plan will be determined in accordance with Chapter 3 of the Maricopa County Zoning Ordinance. b. Development of the site shall be in substantial conformance with the Narrative Report entitled “Saguaro BESS Project”, consisting of 6 pages, dated February 1, 2025, except as modified by the following conditions. c. Prior to issuance of initial building permits, all parcels shall be combined to create a single parcel matching the zoning exhibit of Z2024012. d. The following IND-2 IUPD zoning regulations will apply: 1. Allowed uses: MCZO Sec. 902.2.17 2. Prohibited uses: Adult Oriented facilities, Automobile repair shops and garages, and Drive-thrus for restaurants. 3. Setbacks (minimums) A. Min. setback for BESS units from all lot lines: 100’ B. Min. separation for BESS units from from any existing, permitted dwelling units: 500’ 4. Min. Parking: 2 spaces with one ADA accessible space Z2024012 Page 7 of 8 5. MCZO 902.9.1: The activities and operations associated with the BESS use are not required to be conducted within a completely enclosed building. 6. Standards for Billboards: A. Max. Off-Site Sign Height: Max. 70’ on side directly abutting and oriented to or within 150’ of Loop 303. Max. 45’ on side directly abutting and oriented to Cotton Lane B. Off-Site Sign Separation Distance: Maximum 2 off-site signs oriented to or within 150’ of Loop 303 at minimum 700’ separation distance. C. Off-Site Signs: Maximum of 2 off-site signs permitted on side directly abutting and oriented to Loop 303. A maximum of 1 off-site sign permitted on side directly abutting and oriented to Cotton Lane and setback a minimum of 500’ from the centerline of Olive Avenue. No other off-site signs permitted. D. Off-Site Sign Max Size: 672 square feet E. Min. Rear (East) Yard Setback (billboard only): 0’ F. Min. Setback to RU-43 or R1-6 RUPD: 0’ East and North, 50’ South G. Min. Setback to RU-43 or R1-6 RUPD for illuminated off-site sign: 0’ East and North 50’ South H. Min. 6’ height screening adjacent to rural or residential zoning boundary: Zero screening unless POD submitted for use other than billboard or nursery 7. The IUPD shall limit entitled uses to battery energy storage systems (BESS) and photovoltaic solar power generation and ancillary uses, billboards per condition ‘d.5.3’, and uses permitted in the C-2 CUPD zoning district. e. The following Planning Engineering conditions shall apply: 1. Without the submittal of a precise plan of development, no development approval is inferred by this review, including, but not limited to number of proposed building lots/units, drainage design, access and roadway alignments. These items will be addressed as development plans progress and are submitted to the County for further review and/or entitlement. 2. A traffic impact study must be submitted with future entitlement (POD or Preliminary Plat) application(s). 3. Engineering review of re-zone case is conceptual in nature. All development and engineering design shall be in conformance with Section 1205 of the Maricopa County Zoning Ordinance; Drainage Policies and Standards; Floodplain Regulations for Maricopa County; MCDOT Roadway Design Manual; and current engineering policies, standards and best practices at the time of application for construction. f. Noncompliance with any Maricopa County regulation shall be grounds for initiating a revocation of this zone change as set forth in the Maricopa County Zoning Ordinance. g. The property owner/s and their successors waive claim for diminution in value if Maricopa County takes action to rescind approval due to noncompliance with conditions. h. The granting of this change in use of the property has been at the request of the applicant, with the consent of the landowner. The granting of this approval allows the property to enjoy uses in excess of those permitted by the zoning existing on the date of application, subject to conditions. In the event of the failure to comply with any condition, the property Z2024012 Page 8 of 8 shall revert to the zoning that existed on the date of application. It is, therefore, stipulated and agreed that either revocation due to the failure to comply with any conditions, does not reduce any rights that existed on the date of application to use, divide, sell or possess the property and that there would be no diminution in value of the property from the value it held on the date of application due to such revocation of the zone change. The zone change enhances the value of the property above its value as of the date the zone change is granted and reverting to the prior zoning results in the same value of the property as if the zone change had never been granted. Presented by: Joel Landis, Planner Reviewed by: Rachel Applegate, Planning Supervisor Attachments: Case Map (1 page) Narrative Report (45 pages) Site Plan (3 pages) Support petition (3 pages) MC Engineering comments (1 pages) / Maricopa County Planning & Development - Phoenix, AZ 4 Gross Acres: 31 approx. Generated February 25, 2025 10:45 AM Z2024012 Application Name: Legal Description Applicant Case Address Applicant Phone/Email Parcel Primary: Map scale 1:5,354 Supervisor District No. Saguaro BESS Project Jennifer Hall, Rose Law Group for Desert Forrest Nursery LLC. jhall@roselawgroup.com 16835 W Olive Ave. Wadell, AZ 85355 S36, T3N, R2W Saguaro BESS Project at Generally at the SEC of Olive Avenue and Cotton Lane ZONE CHANGE with OVERLAY REZONING NARRATIVE Case No: Z2024012 Maricopa County, Arizona February 2025 DEVELOPMENT TEAM Developer/Applicant Saguaro BESS LLC Charles McGovern cmcgovern@aypa.com 203-722-9688 Legal Representative Rose Law Group Jordan Rose, Attorney jrose@roselawgroup.com 480-505-3939 Ty Utton, Planner tutton@roselawgroup.com 480-944-4189 Engineer TRC Companies Inc. 6 Executive Circle Suite 200 Irvine, CA 92614 Fire Consultant TERPconsulting Joseph E. Chacon, PE jchacon@terpconsulting.com TABLE OF CONTENTS Background ........................................................................................................................... 1 Purpose of Request ............................................................................................................... 1 Description of Proposal ......................................................................................................... 2 BESS Use & Equipment ............................................................................................................... 2 On-Site Operations Areas ........................................................................................................... 3 Perimeter Screening ................................................................................................................... 3 On-Site Lighting ........................................................................................................................... 3 Fire & Hazard Mitigation ............................................................................................................. 4 Proposed Development Standards ............................................................................................. 4 Relationship to Surrounding Property ........................................................................................ 6 Location & Accessibility .............................................................................................................. 7 Circulation System ...................................................................................................................... 8 Development Schedule ............................................................................................................... 8 Community Facilities & Services ................................................................................................. 8 Public Utilities & Services ............................................................................................................ 8 Compatibility with City of Glendale General Plan ...................................................................... 8 Conclusion ............................................................................................................................. 9 TABLES Table 1: Permitted Uses .................................................................................................................. 2 Table 2: IND-2 Development Standards Comparison ..................................................................... 5 Table 3: Surrounding Uses, Comprehensive Plan, & Zoning Designations ..................................... 7 EXHIBITS Exhibit A: Aerial Vicinity Map Exhibit B: Example Battery Cabinets Exhibit C: Conceptual Site Plan Exhibit D: Rural Metro Support Letter Exhibit E: Fire Flow Analysis Exhibit F: Hazard Mitigation Plan Page | 1 Background Saguaro BESS LLC (“Saguaro”) is happy to have been able to fully redesign this site so that this resubmittal complies with the county’s requests related to setbacks from existing residential. When this application was originally made and went through the process the first time, the county was in the process of picking a preferred setback for Battery Energy Storage System (“BESS”) uses from neighboring homes. After the original submittal, but prior to the hearings on the Application, the county settled on a 500’ preferred setback. The Planning Commission and Board of Supervisors preferred the 500’ setback and have approved other BESS proposals using that new standard. The Board of Supervisors remanded this Application back to the Planning Commission to allow the applicant to work to increase the setback and meet the county’s new standard 500’ separation requirement. As a result of this request, Saguaro worked with the landowner to reconfigure the site and can now deliver a project that does exactly what the county requested and complies with the settled 500’ setback standard. Saguaro is a renewable energy developer, owner, and operator who is proposing the development of a new 250-MW BESS (the “Project”) on approximately 16.20 acres located generally at the southeast corner of Cotton Lane and Olive Avenue in unincorporated Maricopa County, otherwise identified by Maricopa County Assessor (“MCA”) Parcel Number (“APN”) 501-05-005S, 501-05-005R, 501-05-006R, 501-05-006M, 501-05-005U, and 501-05-006L (collectively, the “Site”) (see Exhibit A – Aerial Vicinity Map attached hereto). A lot division and combination application will be submitted under a separate cover to align the desired property line configuration needed to facilitate the proposed Project as illustrated in Exhibit A. Battery Energy Storage Systems such as the proposed Project are a necessary part of a modern and robust power network. The proposed facility is capable of storing enough electricity to power over 80,000 homes and businesses in the valley for four hours. The Project will serve the electrical grid in multiple ways including immediate power for ‘peak’ demand on hot days, back-up energy to reduce/avoid blackouts, increased grid resiliency, near- instantaneous response to changes in renewable energy generation that help integrate and balance intermittent renewable sources, and storage of excess solar power to be used after the sun goes down. Purpose of Request The Site is currently zoned Intermediate Commercial (“C-2”) and is located within Maricopa County’s White Tank/Grand Avenue Area Plan which designates the Site as “Rural Densities (0- 1)” and within the Olive Avenue Scenic Corridor Plan which designates the Site as “Dev. Master Plan”. The Site is also located within the General Plan planning area of the City of Glendale, which designates the Site as “Regional Mixed Use.” The purpose of this request is to pursue approval of a Zone Change with Overlay from “C-2” to Light Industrial (“IND-2”) with a corresponding Industrial Unit Plan of Development (“IUPD”) Page | 2 to allow for the development of the proposed BESS on the Site. Significant changes were made to the layout and site after the case was remanded back to the Planning and Zoning Commission. These improvements lead to an even more compatible project with the existing neighborhood and ensure that the Project will not have any impacts to its surrounding neighbors. Description of Proposal BESS Use & Equipment The requested Zone Change would specifically provide for the development of a new BESS on the Site. The proposed IUPD will then restrict the permitted uses on the Site to only those that provide for the proposed BESS use as indicated in Table 1: Permitted Uses below as well as to allow the existing billboard located at the southeast corner of the Site to remain in its current conditions. The use types described in Section 902.2.17 of the Maricopa County Zoning Ordinance (“MCZO”) have been determined by the County to include a BESS. Restricting the Site to these uses will prevent other uses that may be considered incompatible with the surrounding area from being constructed on the Site. Any uses not specifically allowed pursuant to MCZO Section 902.2.17 shall not be permitted. Table 1: Permitted Uses Base Zoning District Use Description IND-2 MCZO Section 902.2.17: Public utility treatment and generating plants including sewage, wastewater, water, power, electrical, nuclear and solar, and including ancillary offices. Attendant facilities and appurtenances to the above uses as well as uses associated with service to the public of water, gas, telephone and cable television. Where an electrical generating plant is in operation, evaporation ponds and other appurtenances may be permitted provided such evaporation ponds or appurtenances are associated within the facility being served. Access to the Site will occur through two separate entrance, one from Lawrence Lane and the other from Olive Avenue via a 26’ wide secured access gate. The Project will consist of battery storage units located within enclosed cabinets mounted on outdoor concrete pads situated in rows (see Exhibit B – Example Battery Cabinets attached hereto). This “outdoor use” will require a deviation to the IND-2 development standards as noted in Table 2: IND-2 Development Standards Comparison below. Internal drives and fire lanes will provide maintenance and emergency response access to the entire Site, including the battery storage units and the private substation in the northwest portion of the Site (see Exhibit C – Conceptual Site Plan attached hereto). Page | 3 The on-site private substation will be connected to the APS Parkway substation which will be located on the north side of Olive Ave, north of the Site and will be connected via the existing Palm Valley Transmission Line that runs along the entire length of the western boundary of the Site (North to South). The proximity of the Site to the planned APS substation will minimize the gen-tie length and amount of transmission infrastructure needed in the area minimizing impacts to the surrounding community and neighbors. This interconnection is a critical one for both the proposed Project and the APS electrical grid in multiple ways, potentially including immediate power for ‘peak’ demand on hot days, back-up energy to reduce/avoid blackouts, increased grid resiliency, near-instantaneous response to changes in renewable energy generation that help integrate and balance intermittent renewable sources, and storage of excess solar power to be used after the sun goes down. On-Site Operations Areas The Project will be remotely operated and monitored on a 24/7-hour basis with only routine maintenance visits. Saguaro anticipates the long-term operational workforce will consist of a maximum of four (4) employees visiting every two (2) to three (3) months throughout any given year to perform routine maintenance and inspections. The crew normally consists of one (1) operator, one (1) contracted field engineer, and two (2) mechanical or electrical technicians who arrive on-site together. These employees will continuously monitor the safety and operations of the Project and perform routine Project maintenance, as necessary. There will be no public access to the Site and no daily employees. Perimeter Screening The Site will be enclosed with an 8’ CMU block wall to obscure the proposed facility from the adjacent residential and commercial uses. The proposed perimeter screening will require a deviation to the IND-2 development standards as noted in Table 2: IND-2 Development Standards Comparison below. Dense native landscaping will be provided on the outside of the block wall, to assist with screening the battery cabinets. This landscaping area varies in depths 15’ to 60’ with careful attention to include high quality, dense vegetation along the most prominent portions of the Site. More specifically, the area of the site visible from Olive Avenue will feature dense vegetation as well as along the southern perimeter property line, nearest to the existing residential community. Dense vegetation will also be included along the east portion of the site where it may be visible from the Loop 303. On-Site Lighting Lighting will be limited to bollard lights at the Project entrance/exit and pole mounted lights around the on-site private substation in order to satisfy security needs. All lighting will meet MCZO requirements. Page | 4 Fire & Hazard Mitigation Saguaro has worked closely with Rural Metro to ensure that all fire suppression and other public safety measures and concerns are addressed for the Project. Each battery unit will be equipped with state-of-the-art remote detection and multiple shut down points to ensure that in the event of a safety incident a quick and safe response will take place. Rural Metro has reviewed the revised site plan and has issued a letter of support for the Project, which is attached hereto as Exhibit D. The Project design includes a codified 100’ setbacks along all property lines to all battery storage units, as well as ensures a greater than 500’ setback to any residential zoned properties. The actual distance from the closest BESS accessory to residential property line is 548’. Fire hydrants are spaced throughout the Site to ensure every portion of the Site is within International Fire Code standards. A Fire Flow analysis has been completed since the last submittal to ensure adequate pressure is available for the Project. The complete analysis is attached hereto as Exhibit E. The Site features excessive staging areas for first responders and will connect directly into the existing water line for fire suppression as needed. Additionally, a formal Hazard Mitigation Analysis for the Project has been prepared and is attached hereto as Exhibit F. Proposed Development Standards The Site will comply with all general IND-2 base zoning district regulations. The proposed development standards for the Project, including three (3) minor deviations to the IND-2 development standards, are outlined in Table 2: IND-2 Development Standards Comparison and described below. Additionally, the standards for the existing billboard are included in Table 2: IND-2 Development Standards Comparison. The first development standard deviation proposed for the Site is to provide for the BESS use and related activities to be conducted “outdoors”, outside of a completely enclosed building. MCZO Section 902.9.1 requires that all IND-2 uses except for parking, loading, unloading or storage be conducted within a completely enclosed building. While we believe the proposed BESS use is already very similar in nature to these exceptions, a specific deviation to allow the BESS use to be conducted outdoors is requested. The second development standard deviation proposed for the Site is a reduction in the amount of required parking. As noted above, the Site will be periodically visited by a team every two (2) to three (3) months and will arrive together. At a parking ratio of 1 space per 600 SF for “industrial” (per MCZO Section 1102), the Site would require a total of 8 parking spaces. However, the Site is not open or accessible to the public and Saguaro will have a maximum of four (4) on-site employees. Saguaro is therefore proposing to provide a total of two (2) parking spaces (including one ADA accessible space), based on a ratio of 1 space per 750 SF for “office” and 1 space per 1,200 SF for “industrial”, which is more than sufficient for their on-site employees and operational needs. Page | 5 The third development standard being amended is codifying a much more substantial front, side, and rear yard that is typically required for industrial uses. This IUPD request would ensure that all BESS equipment is located more than 100’ from the property line. An additional standard is being included to give assurances to the existing residential community to the south that no BESS equipment will be located within 500’ of the existing homes. Table 2: IND-2 Development Standards Comparison Regulation Base Zoning District Regulations (IND-2) Proposed Zoning District Regulations (IND-2 IUPD) Maximum Height 40' 40’ Min. Distance from BESS Cabinets to Existing Residential Dwelling Units 500’ Min. Front Yard (West) 15’ (abutting collector street) 100’ Min. Side Yard (North) 5’ (adjacent to rural or residential zoning district) 100’ Min. Side Yard (South) 5’ (adjacent to rural or residential zoning district) 100’ Min. Rear Yard (East) 25' (abutting a rural or residential zoning district) 100’ Minimum Lot Area 6,000 sq ft 6,000 sq ft Min. Lot Width 60' 60’ Maximum Lot Coverage 60% 60% Additional Regulations (MCZO Section 902.9.1) All uses except for parking, loading, unloading or storage shall be conducted within a completely enclosed building The activities and operations associated with the BESS use are not required to be conducted within a completely enclosed building Parking (MCZO Section 1102) Office: 1 space per 250 SF Industrial: 1 space per 600 SF 2 spaces Handicapped Parking (MCZO Section 1102) 5% of parking spaces shall be handicapped parking spaces. 1 space (33%) Perimeter Screening (Side & Rear abutting a rural or residential zoning district) 8’ masonry wall 8’ masonry wall Perimeter Screening (not abutting a rural or residential zoning district) 6’ masonry wall or fence with view obscuring material 8’ masonry wall Page | 6 Billboard Standards Regulation Base Zoning District Regulations (IND-2) Proposed Zoning District Regulations (IND-2 IUPD) Max. Off-Site Sign Height 30’ Max. 70’ on side directly abutting and oriented to or within 150’ of Loop 303. Max. 45’ on side directly abutting and oriented to Cotton Lane Off-Site Sign Separation Distance 1000’ Maximum 2 off-site signs oriented to or within 150’ of Loop 303 at minimum 700’ separation distance. Off-Site Signs Permitted Maximum of 2 off-site signs permitted on side directly abutting and oriented to Loop 303. A maximum of 1 off-site sign permitted on side directly abutting and oriented to Cotton Lane and setback a minimum of 500’ from the centerline of Olive Avenue. No other off-site signs permitted. Off-Site Sign Max Size 300 square feet 672 square feet Min. Rear (East) Yard Setback (Only for parcel 501-05-006M) (billboard only) 25’ 0’ Min. Setback to RU-43 (billboard only) 100’ 0’ East and North 50’ South Min. Setback to RU-43 for illuminated off-site sign 150’ 0’ East and North 50’ South Min. 6’ height screening adjacent to rural or residential zoning boundary 6’ height along residential zoning Zero screening unless POD submitted for use other than billboard or nursery Relationship to Surrounding Property The requested Zone Change is compatible with the surrounding land uses. BESS facilities offer multiple advantages that align well with residential communities. Firstly, BESS facilities do not generate significant daily traffic as they do not require frequent deliveries or a large number of on-site employees. This is particularly beneficial for residential areas where maintaining low traffic volumes is a priority. Additionally, BESS facilities operate quietly, utilizing advanced technology to ensure no noise is emitted from the use, making them unobtrusive neighbors. They also do not emit odors, ensuring the air quality remains unaffected for nearby residents, continuing the status quo for the surrounding neighbors. Page | 7 The operation of BESS facilities does not necessitate permanent on-site staff, minimizing activity on the Site and reducing any disruptions to neighboring residential areas. Furthermore, BESS units enhance the reliability of the electrical grid by storing energy and providing it during peak demand times or outages, contributing to a more stable and reliable power supply for residential areas and enhancing the overall quality of life. Modern BESS facilities are equipped with stringent safety measures, including fire suppression systems, regular maintenance, and monitoring, which mitigate potential risks and ensure the safety of surrounding areas. Additionally, the proposed BESS units create a sense of open space in the surrounding environment, reducing visual impact through landscaping and architectural features to ensure that the facilities do not detract from the aesthetic appeal of the adjacent residential neighborhood. The specific context of the site further supports the compatibility of the BESS Project with surrounding land uses. The Site is bordered on the east by Loop 303, which acts as a buffer and provides separation from residential areas, and on the north by Olive Avenue aligning with the less intrusive nature of BESS. To the west is a 100 ft transmission line corridor, which is a common placement for utility infrastructure and complements the function of a BESS, while to the south the property will remain as an active plan nursery. Further south, a residential community will benefit from the quiet, odorless, and low-traffic nature of BESS ensures minimal disruption to residents. Table 3: Surrounding Uses, Comprehensive Plan and Zoning Designations below provides a summary of existing and surrounding land uses. Table 3: Surrounding Uses, Comprehensive Plan, & Zoning Designations Existing Land Uses Comprehensive Plan Zoning Jurisdiction Site Commercial White Tank/Grand Avenue Area Plan Rural Densities (0-1) C-2 Maricopa County North Commercial White Tank/Grand Avenue Area Plan Rural Densities (0-1) C-2 Maricopa County East Transportation (Loop 303) White Tank/Grand Avenue Area Plan Rural Densities (0-1) N/A Maricopa County South Commercial White Tank/Grand Avenue Area Plan Rural Densities (0-1) C-2 Maricopa County West Residential White Tank/Grand Avenue Area Plan Large Lot Residential (1-2) RU-43 / C-2 Maricopa County Location & Accessibility Access to the Site will occur from two (2) entrances; the existing Lawrence Lane that connects directly to Cotton Lane as well as an entrance off of Olive Avenue. Any necessary improvements and or widening of Lawrence Lane will be paid for and provided by Saguaro. Lawrence Lane will end at the entrance gate to the new BESS facility. Again, this Site is not open to the public so the entrance gate will be secured and only allow access to Saguaro maintenance crew and Emergency Responders. Page | 8 The BESS use will generate virtually zero traffic and relatively low traffic volumes exist today on Cotton Lane and Olive Avenue. Because the Project has no frontage on Cotton Lane, right-of- way dedications and half-street improvements are not necessary and not anticipated with this Project as discussed with Maricopa County Department of Transportation (“MCDOT”). Circulation System As noted above, access to the Site will occur from Lawrence Lane, an existing private road, and Olive Avenue that both will connect to a gated entry at the Project boundary. A 26ft internal road will then allow employees and maintenance and emergency vehicles to access all areas of the Site, including the battery storage cabinets and the on-site electrical substation. The internal drives will allow for these vehicles to move safely around the site in a circular pattern, meeting all fire access width and turning radii requirements. Development Schedule The Project will begin site plan approval and permitting commencing after the County’s approval of the Zone Change. Construction will most likely begin in late 2028 or early 2029 and last for a period of approximately 12-15 months. Community Facilities & Services As noted above, the proposed BESS use will not have any daily employees, only sporadic maintenance visits. Additionally, the use is remotely operated with 24/7 observation; thus, the proposed BESS use will have no impact whatsoever on community facilities and services in the area such as schools, parks, libraries, etc. Public Utilities & Services Sewer: None Proposed Water: EPCOR Refuse: None Proposed Electric: APS Fire Protection: Rural Metro Police Service: Maricopa County Sheriff Compatibility with City of Glendale General Plan The Site is located within the City of Glendale’s planning area and is designated “Regional Mixed-Use” under the City’s General Plan, as is all the surrounding area on the East and West side of Loop 303. While the Site will not be a mixed-use project, is does further the City and County’s goals of developing the area as with cohesive, large‐scale, mixed‐use planned development fostering urban, multi‐modal opportunities as the proposed use will provide the Page | 9 necessary critical infrastructure needed for future development in the area. The proposed BESS provides critical energy infrastructure needed to support sustainable development and additional green infrastructure projects that are often incorporated into new developments. The proposed use will complement the envisioned future for the area as it is a quiet, non- impactful, and non-traffic generating use services, a necessary function for the County and the City of Glendale. In order to ensure compatibility with the surrounding land uses (both existing and planned), the IUPD associated with this Zone Change request proposes to limit the permitted uses on the Site to those related to the BESS (see Table 1 above). Conclusion Approval of this rezoning request will allow the development of a much-needed sustainable energy support use in this area which complements the existing community. The Site is an ideal location for this use as it will connect directly into the existing Palm Valley Transmission line and provide direct support to the Parkway substation located on the north side of Olive Avenue. BESS storage is a quiet neighbor and will not have any negative impacts to the surrounding uses. Rather it will support the continued development of the area and will complement any roof top solar installed by the surrounding neighborhoods. Saguaro is an experienced operator and will be a good partner in the local community as it continues to grow. When the Board of Supervisors remanded the case back to the Planning and Zoning Commission, they asked the applicant to attempt to reconfigure the site to comply with the new internal policy of having a 500’ separation from existing residential homes. Saguaro was able to 100% satisfy this request by reconfiguring the site and acquiring more land. This proposal is in full compliance and solves the issue articulated in the remand. Saguaro is pleased to present a conforming project for your consideration. Exhibit “A” Aerial Vicinity Map Exhibit “B” Example Battery Cabinets Rendering of the proposed Powin Centipede BESS enclosure. Photo courtesy of Powin. Rendering of the proposed Powin Centipede BESS system block. Photo courtesy of Powin. Exhibit “C” Conceptual Site Plan Exhibit “D” Rural Metro Support Letter Rural Metro Fire Prevention Fire Marshal Kenneth Diamond Kenneth.Diamond@GMR.Net 28353 E. Main St | San Tan Valley, AZ 85140 | (480) 869‐2340 To: Ty Utton From: Kenneth Diamond RE: Proposed BESS Project (Rezoning Case#: Z2024012) Date: July 1, 2024 To: Ty Utton Re: Proposed BESS Project (Rezoning Case#: Z2024012) We are writing to express our support for the proposed Battery Energy Storage System (BESS) rezoning project on the site located at the SEC of Olive Avenue and Cotton Lane. Rural Metro Fire Department Fire Prevention has thoroughly reviewed the site plan, including the fire flow tests and fire hydrant layouts, and we are pleased to confirm that we have no concerns regarding this development. The setbacks and road layout provided on the site plan meet our safety standards, and we are comfortable with the layout as proposed. Additionally, the proximity of the site to our station enhances our ability to respond promptly in case of any emergency, further supporting our confidence in the safety and feasibility of this project. We believe this development will be a beneficial addition to the area and are happy to provide our full support. Should you require any further information or assistance, please do not hesitate to contact us. Thank you! Kenneth Diamond Fire Marshal Fire Plans Examiner Central Arizona Fire Operations kenneth.diamond@gmr.net (480) 869‐2340 Exhibit “E” Fire Flow Analysis Fire Flow Report Technical Memorandum Page 1 Date: May 7, 2024 To: Charles McGovern, Saguaro BESS, LLC From: Scott Horowitz, P.E. – Project Engineer CC: Dagmawi Geremew, P.E. – Project Manager Project: 563842.0DMS.0000 (TRC) Subject: Fire Flow Report Saguaro BESS Project Maricopa County, Arizona Introduction Saguaro BESS, LLC (Saguaro) is pursuing development of a 250MW battery energy storage system (BESS) in Maricopa County, Arizona. The Saguaro BESS (Site) is located south of W Olive Ave, East of N. Cotton Lane, and West of Loop 303 in Waddell, Arizona. The site intersects multiple parcels as shown in the location map in Figure 1. TRC Engineers, Inc. (TRC) was retained to perform a fire flow analysis to confirm the adequacy of proposed fire hydrants. This memorandum summarizes the findings of existing hydrant test results, hydraulic calculations, and analysis of proposed hydrants. Figure 1 (Location Map) W. DIANA AVE PROJET SITE W OLIVE AVE ARIZONA STATE RTE 303 W. ALICE AVE N COTTON LN Fire Flow Report Technical Memorandum Page 2 Fire Flow Analysis Existing Fire Hydrant Flow Test Foothills Fire Protection, Inc. performed flow test of existing nearby fire hydrants as per the request of TRC. The location of tested hydrants are shown in Figure 2, and the result are shown in below: Figure 2 (Fire Hydrant Test Location Map) Fire Flow Report Technical Memorandum Page 3 Fire Hydrant Test Resluts Fire Hydrant Flow Test Results Project : Date: 5/20/2024 Location: Project # 24-053 Test Date: Test Time: Performed By: Witnessed By: Test Info: Static 78 psi Pitot 11 psi Residual 48 psi GPM 1,270 gpm Pressure Drop 30 psi Coefficient 0.80 Drop % 38.5% Outlet Dia. 4 in. GPM @ 20 psi 1,812 gpm GPM @ 0 psi 2,127 gpm Hydrant #1 Hydrant #2 Saguaro Bess Project 16835 W. Olive Ave. - Waddell, AZ 85355 5/29/2024 FFPI 8:00a EPCOR (E Coppinger) 0 10 20 30 40 50 60 70 80 90 0 500 1000 1500 2000 2500 Pressure (psi) Flow (gpm) CAUTION: Results of this flow test identify water system characteristics for the date, time, and locations of this test only. Pressure and flows within the water system vary of time, it is expected and should be considered when preparing designs based upon fire flow test data. Numerous factors affect the water system, such as water level fluctuations in reservoirs, operating pressure ranges at booster pump stations, elevations at point of use, daily demand fluctuations, seasonal demands, emergency demands, water treatment plant availability, increased demands due to growth, operation/maintenance schedules, etc. AZ Cmrl. No. 111750 AZ Res. No. 111742 NM Lic. 363210 Foothills Fire Protection, Inc. 7435 E. Karen Drive Scottsdale, AZ 85260 (480) 951-3434 (480) 951-2299 (Fax) Fire Flow Report Technical Memorandum Page 4 Hydraulics Analysis Existing Water line The existing water main as shown in site plan Appendix A is as per the ALTA survey performed by Land Survey Service PLC. The pipe size of existing water line is unknown and the contractor will need to field verify pipe size, location, and flowline elevation during construction. Proposed Fire Water line The proposed water line will be 6 inch PVC pipe and will connect to the existing water main at two locations with ductile iron Tee fittings as shown in the site plan Appendix A. The proposed fire water line approximately 1,800 feet forms a turnaround loop along the proposed access road. The access road will be 26 feet wide with turning radius of 25 feet, which is adequate for allowing the ingress/egress of a pumper truck 8 feet in width and 40 feet in length. An AutoCAD Vehicle tracking model of fire truck turning was prepared as shown in Appendix B. The proposed water line will include fire hydrants installed with maximum spacing of 500 feet. Proposed Fire Hydrant Flow Calculations: A proposed fire hydrant flow is estimated by using the nearby tested fire hydrants capacity. The proposed fire hydrant being analyzed is 1,540 feet apart from the tested fire hydrant (FH1), and 1,395 feet apart from the second tested fire hydrant (FH2). This fire hydrant was selected due to the elevation difference between it and the tested fire hydrants created presented with the worst case scenario for pressure. The existing water main pipe is assumed to be 8 inch with a flow rate of 1,270 gallons per minute (gpm) at 11 psi, the same can be anticipated at FH2. This pipe size and flow is also assumed for the proposed new fire hydrant. The total head loss of 13.74 psi (31.74ft) is calculated by using the Hazen-Williams equations. After considering major and minor head loss, the residual pressure of 64.59 psi is estimated at the proposed fire hydrant which is higher than the minimum residual pressure required by NFPA 291. The proposed fire hydrant fire flow at 20 psi is calculated to be 2,773 gpm. Fire Flow Report Technical Memorandum Page 5 Fire Flow Calculations: Tested Fire Hydrant (FH1) Static Pressure Ps1 78 psi Residual Pressure Pr1 48 psi Flow at 20 psi Q 1,812 gpm 4.04 ft3/sec Surface Elevation h1 1,172.76 ft Distance from Prop FH L1 1540 ft Tested Fire Hydrant (FH2) Pitot Pressure Pt 11 psi Flow at 11 psi QPt 1,270 gpm Outlet Diameter D 4 inch Coefficient Cd 0.8 Flow at 0 psi Q 2,127 gpm Ground Surface Elevation h2 1,176.8 ft Distance from Prop FH L2 1,395 ft Assumptions: Projected flow at Proposed FH Q 1270 gpm 2.83 ft3/sec Water Main Pipe Diameter (Existing and Proposed) D 8 inch 0.67 ft Pipe C-Area A 0.35 ft2 Velocity v 8.11 ft/sec Constants: Specific Weight of Water Ƴ 62.4 lbf/ft3 Acceleration due to gravity g 32.2 ft/sec2 Hazen William Coefficient C 150 Friction Head Loss Head Loss (Friction loss) per linear feet hf 0.0094 psi Total Friction Loss hf 13.12 psi Minor Loss Fitting Type C Qty 90° Bend 0.6 2 1.2 Gate Valve 0.2 1 0.2 Total 1.4 Minor Loss (fittings) hfitting 1.43 ft 0662 psi Total Head Loss 55.21 psi 127.54 ft Proposed Fire Hydrant Ground Surface Elevation hp 1172.01 ft Static Pressure Ps2 78.32 psi Residual Pressure Pr2 23.11 psi Hr = Ps-20 58.3 psi Hf = Ps-Pr 55.21 psi Flow Rate at 20 psi Qr 2773 gpm Fire Flow Report Technical Memorandum Page 6 References 1. NFPA 291, Recommended Practice for Fire Flow Testing AND Marking of Hydrants, 2019 edition. Fire Flow Report Technical Memorandum Page 7 Appendix A Site Plan PARCEL NO. 1 APN 501-05-006M FAMILY FIRST INVESTMENTS LLC DEED #20200412155 ZONING: C-2 PARCEL NO. 2A APN 501-05-005R FHF LLC DEED #20210530444 ZONING: C-2 PARCEL NO. 3 APN 501-05-0055 DESERT FORREST NURSERY LLC DEED #20230101265 ZONING: C-2 PARCEL NO. 4 APN 501-05-005U CROMER LLC DEED #20120230773 ZONING: C-2 APN 501-05-006L 303 INVESTMENTS ZONING: C-2 APN 501-050006Q FHF LLC ZONING: RU-43 APN 501-05-005L COMER LLC ZONING: RU-43 APN 501-05-005M COMER LLC ZONING: RU-43 APN 501-05-005N CROMER LLC ZONING: RU-43 APN 501-05-005G FAMILY FIRST INVESTMENTS LLC ZONING: RU-43 05D RSERY LLC 43 PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL 30' INGRESS/EGRESS ESMT DOC 2006-729581 & BOOK 895 MAPS, PG 9 20' SEWER ESMT DOC #2021-454610 100' ELEC ESMT DOC #2005-1613945 60' x 60' BILLBOARD ESMT ARIZONA D.O.T. R/W CONDEMNATION DOC #2013-1073662 RESTRICTED ACCESS DOC #2017-1073662 8' ELEC ESMT PER DOC 2022-701401 60' x 60' BILLBOARD ESMT 100' ELEC ESMT PER DOC #2007-775338 MARICOPA COUNTY R/W CONDEMNATION DOC #2019-0244870 11' DRAINAGE ESMT DOC 32020-445663 CORNERS FALL ON CHAIN LINK FENCE POSTS 8' ELEC ESMT PER DOC #2022-701401 XX XX XX XX XX F F F F F F F F F F F F F F F F F F F F F PROPOSED ONSITE SUBSTATION PROPOSED CONTROL HOUSE GRAVEL 24' PRIVATE DRIVEWAY AND FIRE LANE PROPOSED PROJECT BOUNDARY W. LAWRENCE LN (EXTENSION) PROPOSED RETENTION BASIN 1 EXISTING PARCEL BOUNDARY PROPOSED RETENTION BASIN 2 EL = 1176.80 W W W W W W W EL = 1172.76 EL = 1171.91 S 6 Executive Circle Suite 200 Irvine, CA 92614 Phone: 949.727.9336 DATE: DRAWN BY: CHECKED BY: APPROVED BY: PROJECT: PROJ. NO.: TITLE: REVISION DATE NO. BY APP'D. SAGUARO BESS PROJECT 16835 W. OLIVE AVENUE WADDELL, AZ 85355 563842 TSS DG SH 6/5/2024 SEAL: DATE: PROFESSIONAL ENGINEER: 6 Executive Circle Suite 200 Irvine, CA 92614 Phone: 949.727.9336 DATE: DRAWN BY: CHECKED BY: APPROVED BY: PROJECT: PROJ. NO.: TITLE: REVISION DATE NO. BY APP'D. SAGUARO BESS PROJECT 16835 W. OLIVE AVENUE WADDELL, AZ 85355 563842 TSS DG SH 6/5/2024 SEAL: DATE: PROFESSIONAL ENGINEER: GRAPHIC SCALE 0 60' 1" = 60' NORTH FIRE FLOW EXHIBIT 1 N LEGEND EXISTING MINOR CONTOUR SIGN MANHOLE FIRE HYDRANT STREET LIGHT OVERHEAD ELECTRIC PROPOSED FIRE HYDRANT (TYP.) CONNECT PROJECT FIRE WATER SUPPLY TO EXISTING WATERLINE EXISTING WATER LINE EXISTING FIRE HYDRANT (1) STATIC = 78 PSI RESIDUAL = 48 PSI PRESSURE DROP = 30 PSI DROP = 38.5% GPM @ 20 PSI = 1,812 GPM EXISTING FIRE HYDRANT (2) PITOT = 11 PSI GPM = 1,270 GPM COEFFICIENT = 0.80 OUTLET DIA = 4 INCH GPM @ 0 PSI = 2,127 GPM OE EASEMENT LINE CHAIN LINK FENCE X PROPOSED TELCOM LINE TEL PROPOSED SUBSTATION CHAIN LINK FENCE XX XX EDGE OF PAVEMENT / CURB LINE AND GUTTER SEWER MANHOLE STORM DRAIN MANHOLE F PROPOSED ELECTRIC LINE PROPOSED WATER LINE WATER VALVE UTILITY BOX UTILITY POLE SIDEWALK PROPOSED CHAIN LINK FENCE X F PROPOSED FIRE HYDRANT PROPOSED MAJOR CONTOUR PROPOSED MINOR CONTOUR EXISTING MAJOR CONTOUR (SL) (EP) (WV) (UB) (UP) (S/W) (MH) (OH) ELECTRIC MANHOLE ELE SD UNKNOWN UTILITY (UTIL) CENTERLINE PROPOSED SETBACK PROPOSED LANDSCAPE BUFFER 60' VICINITY MAP NTS PROPOSED 8' BLOCK WALL PROPERTY BOUNDARY E PROPOSED GRAVEL DRIVEWAY EXISTING PROPOSED FIRE LINES NOTE: 1. BOUNDARY SURVEY CONDUCTED BY LAND SURVEY SERVICES PLC (JULY 2023) 2. PROPOSED STORAGE CAPACITY: 250MW 3. LOT SPLIT/COMBINATION WILL BE COMPLETED AFTER REZONING APPROVAL. PROPOSED PAVED ROAD EXTENSION PL PROPOSED PROPERTY LINE EXISTING SEWER LINE EXISTING WATER LINE W DRAINAGE GRATE these bends and a tee should be included in the head loss calculations 2,768.59 ft are the bends to route under these headwalls accounted for? are the bends to route under these pipes accounted for? Fire Flow Report Technical Memorandum Page 8 Appendix B Vehicle Tracking Exhibit PARCEL NO. 1 APN 501-05-006M FAMILY FIRST INVESTMENTS LLC DEED #20200412155 ZONING: C-2 PARCEL NO. 2A APN 501-05-005R FHF LLC DEED #20210530444 ZONING: C-2 PARCEL NO. 3 APN 501-05-0055 DESERT FORREST NURSERY LLC DEED #20230101265 ZONING: C-2 PARCEL NO. 4 APN 501-05-005U CROMER LLC DEED #20120230773 ZONING: C-2 APN 501-05-006L 303 INVESTMENTS ZONING: C-2 APN 501-050006Q FHF LLC ZONING: RU-43 APN 501-05-005L COMER LLC ZONING: RU-43 APN 501-05-005M COMER LLC ZONING: RU-43 APN 501-05-005N CROMER LLC ZONING: RU-43 APN 501-05-005G FAMILY FIRST INVESTMENTS LLC ZONING: RU-43 05D RSERY LLC 43 PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL 30' INGRESS/EGRESS ESMT DOC 2006-729581 & BOOK 895 MAPS, PG 9 20' SEWER ESMT DOC #2021-454610 100' ELEC ESMT DOC #2005-1613945 60' x 60' BILLBOARD ESMT ARIZONA D.O.T. R/W CONDEMNATION DOC #2013-1073662 RESTRICTED ACCESS DOC #2017-1073662 8' ELEC ESMT PER DOC 2022-701401 60' x 60' BILLBOARD ESMT 100' ELEC ESMT PER DOC #2007-775338 MARICOPA COUNTY R/W CONDEMNATION DOC #2019-0244870 11' DRAINAGE ESMT DOC 32020-445663 CORNERS FALL ON CHAIN LINK FENCE POSTS 8' ELEC ESMT PER DOC #2022-701401 XX XX XX XX XX PROPOSED ONSITE SUBSTATION PROPOSED CONTROL HOUSE GRAVEL 24' PRIVATE DRIVEWAY AND FIRE LANE PROPOSED PROJECT BOUNDARY W. LAWRENCE LN (EXTENSION) PROPOSED RETENTION BASIN 1 EXISTING PARCEL BOUNDARY PROPOSED RETENTION BASIN 2 Pumper Fire Truck Pumper Fire Truck Pumper Fire Truck PUMPER FIRE TRUCK OVERALL LENGTH = 40.0 FT OVERALL WIDTH = 8.167 FT OVERALL BODY HEIGHT = 7.745 FT MIN BODY GROUND CLEARANCE = 0.656 FT TRACK WIDTH = 8.167 FT LOCK-TO-LOCK TIME = 5.00S MAX WHEEL ANGLE = 45° VEHICLE TRACKING MODEL PATH #1 VEHICLE TRACKING MODEL PATH #2 VEHICLE TRACKING MODEL PATH #2 6 Executive Circle Suite 200 Irvine, CA 92614 Phone: 949.727.9336 DATE: DRAWN BY: CHECKED BY: APPROVED BY: PROJECT: PROJ. NO.: TITLE: REVISION DATE NO. BY APP'D. SAGUARO BESS PROJECT 16835 W. OLIVE AVENUE WADDELL, AZ 85355 563842 TSS DG SH 6/5/2024 SEAL: DATE: PROFESSIONAL ENGINEER: 6 Executive Circle Suite 200 Irvine, CA 92614 Phone: 949.727.9336 DATE: DRAWN BY: CHECKED BY: APPROVED BY: PROJECT: PROJ. NO.: TITLE: REVISION DATE NO. BY APP'D. SAGUARO BESS PROJECT 16835 W. OLIVE AVENUE WADDELL, AZ 85355 563842 TSS DG SH 6/5/2024 SEAL: DATE: PROFESSIONAL ENGINEER: GRAPHIC SCALE 0 60' 1" = 60' NORTH VEHICLE TRACKING EXHIBIT 1 N LEGEND EXISTING MINOR CONTOUR SIGN MANHOLE FIRE HYDRANT STREET LIGHT OVERHEAD ELECTRIC OE EASEMENT LINE CHAIN LINK FENCE X PROPOSED TELCOM LINE TEL PROPOSED SUBSTATION CHAIN LINK FENCE XX XX EDGE OF PAVEMENT / CURB LINE AND GUTTER SEWER MANHOLE STORM DRAIN MANHOLE F PROPOSED ELECTRIC LINE PROPOSED WATER LINE WATER VALVE UTILITY BOX UTILITY POLE SIDEWALK PROPOSED CHAIN LINK FENCE X F PROPOSED FIRE HYDRANT PROPOSED MAJOR CONTOUR PROPOSED MINOR CONTOUR EXISTING MAJOR CONTOUR (SL) (EP) (WV) (UB) (UP) (S/W) (MH) (OH) ELECTRIC MANHOLE ELE SD UNKNOWN UTILITY (UTIL) CENTERLINE PROPOSED SETBACK PROPOSED LANDSCAPE BUFFER 60' VICINITY MAP NTS PROPOSED 8' BLOCK WALL PROPERTY BOUNDARY E PROPOSED GRAVEL DRIVEWAY EXISTING PROPOSED FIRE LINES NOTE: 1. BOUNDARY SURVEY CONDUCTED BY LAND SURVEY SERVICES PLC (JULY 2023) 2. PROPOSED STORAGE CAPACITY: 250MW 3. LOT SPLIT/COMBINATION WILL BE COMPLETED AFTER REZONING APPROVAL. PROPOSED PAVED ROAD EXTENSION PL PROPOSED PROPERTY LINE EXISTING SEWER LINE EXISTING WATER LINE W DRAINAGE GRATE S R25' R25' R25' R25' R25' R26' R25' R25' R25' 24' 24' recommend showing fire truck template and vehicle information Exhibit “F” Hazard Mitigation Plan Page 1 of 14 AYPA POWER Proposal EMERGENCY RESPONSE PLAN SECTION 1 – GENERAL INFORMATION SecƟon 1.1 – Product Name XXXX Manufacturer SecƟon 1.2 – Owner and Operator AYPA Power 11801 Domain Blvd, Suite 450 AusƟn, TX 78758 SecƟon 1.3 – Emergency Contact Number Emergency Contact Contact Number To be provided by AYPA once a ROC provided is onboarded. SecƟon 1.4 – Scope This document is an Emergency Response Plan (ERP) for the BESS facility. The scope of the ERP focuses on the hazards and response tacƟcs associated with BESS emergencies, and the failure of supporƟng electrical components resulƟng in class b/c fire hazards. The document also discusses post-fire operaƟons and provides disposal guidance. The project is under the jurisdicƟon of xxxx County. SecƟon 1.5 – Purpose The purpose of this emergency response plan is to provide an overview of the facility along with an explanaƟon of the equipment contained therein. The plan outlines failure scenarios, detecƟon capabiliƟes, system safety features, hazards and response tacƟcs that define the response posture associated with BESS emergencies and the failure of supporƟng electrical components. Canadian Solar SESS has fully integrated numerous safety soluƟons to manage the risk of first responders operaƟng at the scene of an energy storage system emergency. These designs have incorporated lessons learned, industry best pracƟces, research, and development efforts to conƟnuously enhance safety. SECTION 2 – DEFINITIONS SecƟon 2.1 Batery Management System (BMS) A system that monitors, controls, and opƟmizes performance of an individual or mulƟple batery modules in an energy storage system and has the ability to control the disconnecƟon of the module(s) from the system in the event of abnormal condiƟons. Each string of modules has a dedicated BMS at the rack level. Page 2 of 14 AYPA POWER Proposal SecƟon 2.2 Local Controller The local controller is used for the communicaƟon integraƟon of different equipment in the energy storage system, faults and alarms management, parallel control of two or more energy storage inverters, the design offers one universal communicaƟon interface of the system. As shown in the following picture, the local controller collects and uploads the real-Ɵme informaƟon of PCSs, batery system and other equipment in the energy storage system through an ethernet connecƟon. At the same Ɵme, the Energy Management System (EMS) can control the storage system through the local controller. Within the control scope of the local controller, it processes the startup and shutdown procedure, protecƟons, and alarms. SecƟon 2.3 Cell The basic funcƟonal electrochemical unit contains an assembly of electrodes, electrolyte, separators, container, and terminals. It is a source of electrical energy by direct conversion of chemical energy. SecƟon 2.4 Module A subassembly which is a component of a BESS that consists of a group of cells or electrochemical capacitors connected together either in a series and/or parallel configuraƟon with or without protecƟve devices and monitoring circuitry. There are sixty-nine cells in each module. SecƟon 2.5 Batery Rack A batery rack is comprised of twenty-four modules. Modules are connected in series to produce the required usable voltage/potenƟal. SecƟon 2.6 BESS Container The BESS houses eight batery racks each with six modules. The voltage output of the container is 1,324.8 VDC. The BMS exists at the string level within racks and provides autonomous oversight to disconnect strings or the container for condiƟons outside of the defined operaƟng parameters. This is achieved through the BMS contactor and a dedicated disconnect switch has been provided that allows the container to be electrically isolated from the facility. The container has been ouƞited with a liquid cooled thermal management system, fire detecƟon, gas detecƟon, and NFPA 69 venƟlaƟon system that is acƟvated upon 10% LEL for explosion control. E-Stops have been provided on the terminal ends of each container to facility an emergency shutdown if necessary. SecƟon 2.7 Medium Voltage Skid (MV Skid) An MV Skid is provided for each group of up to 6 BESS containers. Batery containers supply the inverter at 1,324.8 VDC. The inverter transforms DC from bateries to AC when discharging, and it turns AC from the grid to DC while charging. Power then passes through the step-up transformer where voltage is raised to 34,500V. Each MV Skid has an E-Stop, dedicated breaker with a disconnect switch and a ground. Page 3 of 14 AYPA POWER Proposal SecƟon 2.8 E-Stop Emergency Stop’s or E-Stops are located locally on the terminal ends of each BESS container and there is one site level E-Stop as required by NFPA 855 that is capable of shuƫng down the enƟre facility. The site level E-Stop is located in the control enclosure or can be iniƟated remotely. The operaƟon of an E-Stop will stop the charging and discharging of bateries within the system. However, the operaƟon of an E- Stop will not dissipate the electrical potenƟal remaining within the batery cells referred to as stranded energy. The operaƟon of a BESS Container e-stop will open the PCS Inverter breaker which will island the BESS Container. The MV Skid has also been provided with an E-Stop buton located 50 inches above grade. SecƟon 2.9 Cell VenƟng In this iniƟal stage of failure, a flammable electrolyte vents from the module in gaseous state. Based upon UL9540a tesƟng the criƟcal temperature where sustained venƟng begins is 147 C/297 F. Gas venƟng is oŌen a precursor of thermal runaway. SecƟon 2.10 Thermal Runaway The incident when an electrochemical cell’s temperature increases at an acceleraƟng rate in an uncontrollable fashion sufficient to result in damage to the cell. The thermal runaway progresses when the cell’s generaƟon of heat is at a higher rate than the heat it can dissipate. Based on UL9540a TesƟng Thermal Runaway begins at 150°C/302°F. SecƟon 2.11 Stranded Energy During an emergency at a BESS facility E-Stops may be operated to stop charging and discharging of modules. However, the E-Stop feature does not discharge the electrical potenƟal remaining in the cells/modules which is known as Stranded Energy. SecƟon 2.12 CriƟcal Temperatures Temperature plays a significant role in the health of bateries. Manufacturers provide thermal operaƟng guidelines and UL9540a tesƟng serves to inform on CriƟcal Temperature thresholds that result in cell venƟng and thermal runaway. SecƟon 2.13 Explosion Control • Explosion ProtecƟon by DeflagraƟon VenƟng (NFPA68): This standard applies to the design, locaƟon, installaƟon, maintenance, and use of devices and systems that vent the combusƟon gases and pressures resulƟng from a deflagraƟon within an enclosure so that structural and mechanical damage is minimized. • Explosion PrevenƟon Systems (NFPA 69): This standard provides requirements for installing systems for the prevenƟon and control of explosions in enclosures that contain flammable concentraƟons of flammable gases, vapors, mists, dusts, or hybrid mixtures. Page 4 of 14 AYPA POWER Proposal SecƟon 2.14 AlternaƟng Current / Direct Current (AC/DC) Energy produced by the Modules can be categorized as DC. During electrical emergencies, the fire services tradiƟonally use non-contact voltage testers to idenƟfy energized equipment. It should be noted that non-contact voltage detectors cannot detect the presence of Direct Current (DC) and should never be used. SecƟon 2.15 BESS – Subject Mater Expert The code requires the facility owner/operator to designate and train staff to respond 24/7 within a Ɵmely manner to invesƟgate all batery energy storage system incidents. They will serve as the site subject mater expert (SME) and work closely with the fire services to invesƟgate and miƟgate condiƟons while ensuring the safety of fire service members operaƟng at the scene. SecƟon 2.16 Site Operator At the direcƟon of the BESS/SME the Site Operator will conduct or coordinate field switching to isolate equipment not automaƟcally isolated by the BMS. Switching may involve the operaƟon of breakers, disconnects and the applicaƟon of grounds to facilitate suppression, and inspecƟon. SECTION 3 – ENERGY STORAGE SYSTEM OVERVIEW SecƟon 3.1 Energy Storage System Concept Energy Storage Systems (green containers below) are charged from renewable energy such as wind, solar or to grid Ɵes. These systems can be charged at night when the cost to produce power is lower and discharged at peak loading Ɵmes during the day for grid sustainability. SECTION 4 – BATTERY MANAGEMENT SYSTEM The BMS has wide reaching oversight to control charging, discharging fault detecƟon and equipment isolaƟon. The BMS has design parameters that evaluate the state of charge & state of health for bateries along with criƟcal temperature thresholds that generate alarms accordingly. The system plays a key role in the Ɵmely response to system emergencies such as cell venƟng and thermal runaway. The BMS has the ability to isolate trouble modules or strings as necessary to miƟgate emergencies. The BMS exists at a rack level and system level for layered control. In order to make informed decisions during system emergencies the BMS should be reviewed with an emphasis on the state of charge for cells/modules on the trouble string. A full state of charge will increase the duraƟon of the emergency. In addiƟon, the temperature of cells will be an indicaƟon of fire propagaƟon within the trouble module or adjacent modules. SECTION 5 – FIRE PROTECTION SYSTEM SecƟon 5.1 Fire Alarm Panel (FACP) The site is provided with a tradiƟonal FACP that monitors the local fire alarm panels within the BESS enclosures. In this design these alarms can be seen from the FACP in the control enclosure or the graphic Page 5 of 14 AYPA POWER Proposal annunciator at the main entrance. This system is monitored by a central staƟon and reports to the site SCADA system. SecƟon 5.2 Fire Alarm Annunciator A fire alarm graphic annunciator is provided at the gate entrance where the fire department will enter the facility. The annunciator will provide the fire alarm system status and indicate any zones that are in alarm or trouble. SecƟon 5.3 DetecƟon System • Smoke and Heat DetecƟon: BESS containers have been ouƞited with smoke and heat detecƟon. The generaƟon of smoke or heat within a container will generate a fire alarm. This will iniƟate the containers E-Stop interrupƟng the charging and discharging of cells/modules in the container, alert the fire department, and acƟvate noƟficaƟon appliances. H2 Gas DetecƟon: When Hydrogen Gas (H2) is detected and an alarm is generated, purge venƟng is acƟvated to maintain the concentraƟon of H2 gas under the LEL of 4% or 40,000PPM. Once purge venƟng begins all equipment within the container is remotely isolated through the BMS. o CombusƟble Gas Level 1: DetecƟon of combusƟble gas concentraƟons above 10% LEL will trigger a Level 1 alarm, sounding the audible alarm bell on the BESS container and stopping batery charging or discharging. The venƟlaƟon system controller will receive the signal and acƟvate the exhaust venƟlaƟon system, reducing concentraƟons of flammable gas within the BESS enclosure. An alarm indicaƟon is sent through the BMS system noƟfying the control room and UI of the operator. o CombusƟble Gas Level 2: DetecƟon of combusƟble gas concentraƟons above 20% LEL will trigger a Level 2 alarm, sounding the audible and visual noƟficaƟon device (horn strove) on the BESS system. A control signal is sent to isolate the affected BESS by opening all BMS contactors and turning off the auxiliary power. The venƟlaƟon system controller will receive the signal and acƟvate the exhaust venƟlaƟon system, reducing concentraƟons of flammable gas within the BESS enclosure. An alarm indicaƟon is sent through the BMS system noƟfying the control room and UI of the operator. o UPS Supply for NFPA 69 system: As required by code, upon the interrupƟon of auxiliary power supplying the NFPA 69 system a UPS back shall be provided with adequate capacity to operate the system for two hours. SECTION 6 HAZARDS SecƟon 6.1 Chemical This secƟon will outline the predominate chemicals hazards along with the recommended personal protecƟve equipment. SecƟon 6.1.1 Lithium-Ion Phosphate Page 6 of 14 AYPA POWER Proposal Toxicity Gasses are evaluated during UL9540a Large Scale Fire TesƟng to idenƟfy the producƟon of IDLH condiƟons. Carbon Monoxide was the only target IDLH gas idenƟfied. The risk from Carbon Monoxide under this situaƟon does not pose a health hazard since the ESS Container cannot be occupied. In addiƟon, Carbon Monoxide is simply managed through AdministraƟve Controls such as staging upwind and engineering controls in the form of an SCBA to manage the respiratory hazard. Note: there is no dermal hazard posed by Carbon Monoxide. UL9540a Data Cells are ouƞited with a vent that ejects flammable electrolyte during elevated thermal condiƟons. This safety feature serves to manage the risk of internal pressurizaƟon resulƟng in a catastrophic failure. Lithium-Ion Phosphate (LFP) bateries are more stable than other batery chemistries and are less likely to undergo thermal runaway and are not suscepƟble to violent failures of the outer shell. Test data indicates that cell failure will not propagate beyond the module level. There was no indicaƟon of flying debris, explosive discharge of gas or sparks and electrical arcing. Hazards of Vented Electrolyte: Cell vent gas composiƟon will depend upon a number of factors, including cell composiƟon, cell state of charge, and the cause of cell venƟng. Vent gases may include volaƟle organic compounds (VOCs) such as alkyl-carbonates, methane, ethylene, and ethane; hydrogen gas; carbon dioxide; carbon monoxide; soot; and parƟculates containing oxides of nickel, aluminum, lithium, copper, and cobalt. AddiƟonally, phosphorus pentafluoride, POF3, and HF vapors may form. Vented gases may irritate the eyes, skin, and throat. Cell vent gases are typically hot; upon exit from a cell, vent gas temperatures can exceed 600°C/1,110°F. Contact with hot gases can cause thermal burns. Vented electrolyte is flammable and may ignite on contact with a competent igniƟon source such as an open flame, flame, spark, or a sufficiently heated surface. Vented electrolyte may also ignite on contact with cells undergoing a thermal runaway reacƟon. Hazards of Leaked Electrolyte: Leaked electrolyte soluƟon is flammable and corrosive / irritaƟng to the eyes and skin. If a liquid is observed that is suspected electrolyte, venƟlate the area and avoid contact with the liquid unƟl a posiƟve idenƟficaƟon can be made and sufficient protecƟve equipment can be obtained (eye, skin, and respiratory protecƟon). Chemical classifier strips can be used to idenƟfy the spilled liquid (electrolyte will contain petroleum/organic solvent and fluoride compounds). SecƟon 6.1.2 Hydrogen When the temperature of a cell reaches the venƟng stage, the primary hazard is the producƟon of Hydrogen Gas (H2). The gas is odorless & colorless which requires internal sensors or external meters for detecƟon. It is an extremely flammable gas which is lighter than air. Any H2 Gas accumulaƟon within the Container will be found in the upper one-third of the unit. SecƟon 6.1.3 Carbon Monoxide Page 7 of 14 AYPA POWER Proposal Carbon monoxide (CO) is an odorless, colorless flammable gas formed by the incomplete combusƟon of fuels. The failure and subsequent arcing /burning of electrical components and cables can readily produce Carbon Monoxide. Sampling for CO should begin at the upper one-third in a sealed enclosure as the gas tends to straƟfy based on its vapor density. SecƟon 6.1.4 Recommended PPE All chemicals associated with the failure of BESS equipment and ancillary electrical components present dermal and respiratory hazards. The failure of the BESS or electrical components can produce smoke and liquid runoff. The recommended PPE for the aforemenƟoned hazards is NFPA 1971 structural firefighƟng gear and the use of an SCBA. Note: The PPE recommendaƟon are for emergency response operaƟons/ life safety. PPE recommendaƟons for the post-fire removal of damaged modules will be defined by condiƟons found at the Ɵme of decommissioning. SecƟon 6.2 Electrical • Shock & ElectrocuƟon: These terms are oŌen misunderstood. Shock is an injury that can either be minor or major which results from inadvertent contact with an electrically energized object. Whereas electrocuƟon results in death from contact with an energized conductor. The difference between shock and electrocuƟon is defined by several factors such as how well the vicƟm was grounded which facilitates current flow through the body, the path the current flows such as across the heart or head, and duraƟon of contact with the energized object. • Non-Contact Voltage Tester: These devices are commonly used in the fire services to idenƟfy energized equipment/objects. However, the devices are only capable of idenƟfying equipment/objects energized by AlternaƟng Current (AC). To assess a surface for the presence of Direct Current (DC) a tradiƟonal meter will be required along with a ground reference. Note: Do not use a non-contact voltage detector at a BESS facility without guidance from a BESS subject mater expert. • Energized Equipment: Electrical equipment within the BESS Cabinet such as modules and cables can be energized. However, these components are shielded or insulated in a manner that there is no chance of shock or electrocuƟon from casual contact. • Equipment NOT Normally Energized: In a post fire scenario, protecƟve shielding or insulaƟon may be damaged resulƟng in equipment/objects that are not normally energized to become energized. Examples may be the metal container, batery racks and modules. • Stranded Energy: Electrical components such as transformers, breakers and cables can be made safe once the connecƟon to an energized electrical source has been interrupted. However, in the case of energy storage, the operaƟon of process safety stops will interrupt the charging and discharging of bateries but will NOT discharge the electrical potenƟal leŌ in the cells referred to as stranded energy. SecƟon 6.3 Explosion Flammable Gas: During cell venƟng, the prevalent flammable gas is Hydrogen. Hydrogen Gas (H2) is detected at 10% of the LEL or 0.4% / 4,000 PPM, at which Ɵme an alarm is generated. Purge venƟng is acƟvated at 10% of the LEL to maintain the concentraƟon of H2 gas under the LEL of 4% or 40,000PPM. Page 8 of 14 AYPA POWER Proposal SECTION 7 NOTIFICATIONS SecƟon 7.1 NoƟficaƟon Flow SECTION 8 UNIFIED COMMAND SecƟon 8.1 Subject Mater Expert (SME) The BESS SME will play a criƟcal role guiding members of the fire services through the response posture associated with a BESS emergency. The SME will fall under the Unified Command structure where they will collaborate with members of the fire services to bring the incident under control. The SME will be responsible for coordinaƟng the following: • Review FACP • Review and interpret BMS data, such as gas alarms, module isolaƟon and cell temperature. • OperaƟon of E-Stops and Disconnect switches. • Coordinate Field Switching • Coordinate IsolaƟon of auxiliary power supply • If and when BESS Container doors should be opened • Recommended suppression agents. • Post-Incident OperaƟons • Administering Decommissioning Plan Page 9 of 14 AYPA POWER Proposal SecƟon 8.2 Unified Command Structure Sample Unified Command Structure. Low frequency / high hazard incidents such as a BESS Emergency will not be managed by one individual Incident Commander. The command structure will include all the stakeholders necessary to miƟgate risk and ensure the safety of first responders. Admin/Finance Chief LogisƟcs Chief Planning Chief OperaƟons Chief Public Information Officer FRA SME Remote Safety Officer Fire Department AYPA BESS SME Police Department Page 10 of 14 AYPA POWER Proposal SecƟon 8.3 Incident Command Structure Sample Incident Command Structure SecƟon 9 – RESPONSE TACTICS SecƟon 9.1 Site Plan MAP Fire Dept Suppression BESS RestoraƟon Decommissioning Vendor Establish Decommissioning Area Insurance Carrier Establish Investigation Area BESS Engineering Field Switching Admin/Finance Chief LogisƟcs Chief Planning Chief OperaƟons Chief Public Information Officer CSI (SESS) Remote Safety Officer Fire Department AYPA BESS SME Police Department Page 11 of 14 AYPA POWER Proposal SecƟon 9.2 EvacuaƟon Site Personnel: The BESS facility is not normally staffed, however, once an alarm is received all personnel shall exit the facility. They should proceed to the main entrance or predesignated rally point to conduct an accountability rollcall as required by OSHA 29 CFR 1910.38 or local regulaƟons. Upon arrival of the fire services, the primary concern is life safety. Note: Personnel should not re-enter the site unƟl the arrival of the fire department. SecƟon 9.3 Staging • Site Personnel: Personnel should not encroach within 100 feet of the Container that is in alarm mode when within the site walls. • Fire Department: Upon arrival, fire department units should stage all apparatus unƟl the scene size-up has been completed. Staging should be upwind at a minimum of 100 feet from the doors on the trouble container. • ConsideraƟon should be given to assigning a Staging Officer within the Incident Command Structure to manage parking. Impeding roadway traffic can have significant consequences if an injury were to occur and an ambulance could not access or leave the site. SecƟon 9.4 Personal ProtecƟve Equipment (PPE) • Electrical Switching: OSHA requires a hazard assessment under 29 CFR 1910.269 to idenƟfy FR clothing and insulated PPE required to conduct switching operaƟons. Follow relevant local regulaƟons for non-OSHA regulated countries. • Fire OperaƟons: Fire services personnel engaged in operaƟons that can expose members to heat, flame, flammable gas and chemical hazards shall use NFPA 1971 structural firefighƟng equipment along with an SCBA for respiratory protecƟon. SecƟon 9.5 Exposure Control • UL9540a Large Scale Fire TesƟng suggests that cell failure will not propagate beyond the module. In the remote event that a container becomes fully involved in fire, consideraƟon may be given to providing exposure protecƟon to adjacent BESS containers or MV Skids as required. During the applicaƟon of water streams for exposure protecƟon, the potenƟal exists to contact energized electrical components in the trouble container. SecƟon 9.6 Size-Up Status Briefing: Upon arrival, the fire officer will look for the BESS SME to obtain a status briefing which should provide a snapshot of exisƟng condiƟons and at a minimum should cover the following: • Accountability: Locate and evacuate all non-essenƟal site personnel. • Exclusion Zone: Establish an exclusion zone of 100 feet around the trouble container to manage the safety of members if an explosion should occur. Containers have been ouƞited with an explosion Page 12 of 14 AYPA POWER Proposal control measure however, we must assume if this system was to fail the doors on the Container can be come projecƟles. • Exposures: Conduct a visual assessment to idenƟfy fire impingement on surrounding equipment, similar should be done with a thermal imaging gun and record temperatures. Reading should be taken every 15 minutes unƟl readings begin to decrease. UƟlize the BMS system to idenƟfy any rise in temperature of surrounding equipment that would require exposure control. Tank water from the apparatus may be applied in intermitent burst and should follow the guidance provided in Table 8. • Electrical Hazards: BESS/SME shall ensure the troubled equipment has been electrically isolated through SCADA or field switching. • Chemical Hazards: Stage all department members and apparatus upwind of the incident and remain cognizant of changing wind condiƟons and manage accordingly. A fully involved container can result in the failure of the thermal management system which will introduce freon into the fire scenario and discharge plume. • Batery Management System: BMS shall be reviewed to determine trending rise in temperature of cells/modules surrounding the trouble module. Temperature should be recorded and evaluated every 15 minutes to determine if propagaƟon into adjacent modules has occurred. SecƟon 10 – POST INCIDENT OPERATIONS SecƟon 10.1 PPE While operaƟng near trouble equipment, the fire services personnel should remain in NFPA 1971 structural firefighƟng gear with respiratory protecƟon and facility personnel should don the appropriate PPE for arc flash hazards associated with potenƟal stranded energy condiƟons and an SCBA unƟl a Post- Fire Assessment has been completed. SecƟon 10.2 Lock Out / Tag Out Once emergency condiƟons have concluded, prior to accessing the trouble container or removing any modules. E-Stops and disconnect switches shall be locked or tagged out as required by OSHA 29 CFR 1910.147 or local regulaƟons. SecƟon 10.3 Stray Voltage • DC/AC Stray Voltage: Prior to removing modules, the container enclosure, racks, and modules should be assessed for stray voltage. In the event that stray voltage is idenƟfied; standard response tacƟcs would focus on isolaƟng the source potenƟal. However, stranded energy may be the source of the stray voltage. In response, rubberized PPE outlined under 29 CFR 1910.269 or local electrical safety standards should be used unƟl the source of the stray voltage has been eliminated. • Stray Voltage TesƟng: To accurately assess this condiƟon a mulƟmeter must be used along with a ground reference. SecƟon 10.4 Thermal Exposure Assessment Page 13 of 14 AYPA POWER Proposal • IniƟal Thermal Scan: Scan and record with a thermal imaging camera module temperature in each rack. The batery management system (BMS) will serve as an excellent guide in terms of evaluaƟng thermal impact on cells/modules within the trouble container. If this system is not viable use a thermal imaging camera. • Thermal Trending: Rescan and record every 15 minutes over the course of 1 hour to idenƟfy any rise in temperature above 20 F. Module(s) that have greater than a 20 F rise in temperature may have cells beginning to vent causing the increased temperature. If this condiƟon is observed, leave the area and stage upwind maintaining a 50-foot standoff distance. Let modules stand for 1-hour and rescan temperature. • End of Useful Life: Although Cells/Modules may not have reached a VenƟng or Thermal Runaway temperature we must evaluate Modules that were operaƟng outside their normal range. Modules that are beyond their useful life must be idenƟfied so that are not re-energized during the repair / restoraƟons process. Cells/Modules with temperatures above 40C/104F should be removed for disposal. SecƟon 10.5 Air Sampling • Air sampling will serve as an excellent indicator to determine if there is sƟll acƟve venƟng of cells within the BESS. The prevalent off gases observed during 9540a TesƟng are Hydrogen, Carbon Monoxide and Carbon Dioxide. The absence of those gases within the BESS container or the downward trending of gas concentraƟons would be an indicator that the situaƟon may be placed under control thus releasing the fire services and entering the decommissioning phase. Page 14 of 14 AYPA POWER Proposal SecƟon 11 Training As required by code, training and familiarizaƟon tours should be conducted annually for members of the first response community along with BESS response personnel. The following topics should be covered in the training program: • System Overview o Equipment & DefiniƟons o Batery Types, Chemistry & Geometry • Batery Management System • DetecƟon & Suppression • Emergency System Shutdown • Hazards o Chemical o Electrical o Explosion (NFPA 68/69) • Suppression Agents o Product/Pattern/Pressure o Safe Standoff Distances o Agents & Fires o Exposure Control • Response TacƟcs o Module VenƟng/Fire o PCS Inverter Failure/Fire o Step-Up Transformer Fire o Breaker Failure • Post-Fire OperaƟons o Lock-Out Tag-Out o Stray Voltage TesƟng o Thermal Assessment o Air Monitoring © 2023 Microsoft Corporation © 2023 Maxar ©CNES (2023) Distribution Airbus DS © 2023 Microsoft Corporation © 2023 TomTom © 2023 Microsoft Corporation © 2023 Maxar ©CNES (2023) Distribution Airbus DS 6 Executive Circle Suite 200 Irvine, CA 92614 Phone: 949.727.9336 DATE: DRAWN BY: CHECKED BY: APPROVED BY: PROJECT: PROJ. NO.: TITLE: REVISION DATE NO. BY APP'D. SAGUARO BESS PROJECT 16835 W. OLIVE AVENUE WADDELL, AZ 85355 563842.0DMS TSS JT AW 1/31/2025 SEAL: DATE: PROFESSIONAL ENGINEER: a E n g i n e e r l n o i s s e f o r P R e g d e r e t s i ) L I V I ( C E C E R T I F I C A T . O N D d e n g i S e t a 0 1 . 3 1 . 2 0 2 5 . 76261 ALLYSON WILLIAMSON A N O Z I R A , A U S A . . . 1/31/2025 VICINITY MAP NTS SITE LOCATOR NTS MARICOPA COUNTY, ARIZONA NTS PRELIMINARY SITE PLANS SAGUARO ENERGY STORAGE PROJECT (ZONE CHANGE APPLICATION) 16835 W OLIVE AVE WADDELL, AZ 85335 PREPARED FOR: PREPARED BY: DATE: SAGUARO BESS, LLC 11801 DOMAIN BLVD SUITE 450 AUSTIN, TX 78758 TRC COMPANIES, INC. 6 EXECUTIVE CIRCLE, SUITE 200 IRVINE, CA 92614 JANUARY 2025 PROPERTY OWNER DESERT FORREST NURSERY, LLC (APN:501-05-005S) FHF, LLC (APN:501-05-005R, 501-05-006R) FAMILY FIRST INVESTMENTS, LLC (APN:501-05-006M) CROMER, LLC (APN: 501-05-005U) INVESTMENT HOLDINGS, LLC (APN: 501-05-006L) APPLICANT SAGUARO BESS, LLC 11801 DOMAIN BLVD, SUITE 450 AUSTIN, TX 78758 ANDREW BREYER ABREYER@AYPA.COM PROJECT ENGINEER TRC ENGINEERS, INC. 700 HIGHLAND BLVD, SUITE 210 ARLINGTON, TX 76015 ALLYSON WILLIAMSON AWILLIAMSON@TRCCOMPANIES.COM 504-258-0791 SUMMARY TABLE PROPOSED STORAGE CAPACITY: 250MW ASSESSOR'S PARCEL NUMBERS: 501-05-005S, 501-05-005R, 501-05-006R, 501-05-006M, 501-05-005U AND 501-05-006L CURRENT USE: NURSERY CURRENT/PROPOSED ZONING: COMMERCIAL (C-2)/ INDUSTRIAL (IND-2) NET ACREAGE: 16.20 AC SITE GROSS ACREAGE(DEVELOPED): 12.35 AC PERCENTAGE OF DEVELOPED AREA: 76.23% DISTURBED AREA: 16.20 AC EXISTING IMPERVIOUS AREA: 0 AC PROPOSED IMPERVIOUS AREA: 5.46 AC %OF PROPOSED IMPERVIOUS AREA: 32.69% REMAINING PERVIOUS AREA: 10.74 AC UTILITIES AND SERVICES IRRIGATION: MARICOPA COUNTY WATER DISTRICT WATER: LIBERTY UTILITIES ELECTRICITY: CITY OF WADDELL FIRE: RURAL METRO POLICE: MARICOPA COUNTY SHERIFF'S OFFICE SCHOOL DISTRICT: DYSART UNIFIED SCHOOL DISTRICT NO. 89 PROJECT SUMMARY THESE PRELIMINARY SITE PLANS ARE SUBMITTED FOR LAND USE PERMITTNG REVIEW INCLUDING ZONE CHANGE APPLICATION PROCESSING FOR DEVELOPMENT OF A PROPOSED BATTERY ENERGY STORAGE SYSTEM (BESS) ON AN APPROXIMATELY 16.20 ACRE SITE CURRENTLY IN AGRICULTURAL USE. THE DEVELOPMENT WILL INCLUDE ARRAYS OF PURPOSE-BUILT OUTDOOR ENCLOSURES CONTAINING BATTERIES AND CONTROL EQUIPMENT, AND ANCILLARY FACILITIES INCLUDING INVERTERS, TRANSFORMERS, ONSITE ACCESS ROADS, DRAINAGE CONTROLS, AN 8-FOOT HIGH PERIMETER MASONARY WALL, AN ONSITE SUBSTATION, PROPOSED TO CONNECT TO THE PARKWAY SUBSTATION VIA A 0.3 MILE LONG 230KV OVERHEAD ELECTRIC TIE-LINE. THE DEVELOPMENT WILL OCCUR IN ONE PHASE. THE FACILITY WILL NOT BE OCCUPIED AND IS DESIGNED FOR FULL REMOTE OPERATION WITH PERIODIC VISITS FOR INSPECTIONS AND MAINTENANCE. NO BUILDINGS WITH POTABLE WATER SUPPLY, OR SANITARY FACILITIES ARE PROPOSED. COVER SHEET C-001 N. 168TH DR W. ALICE AVE ARIZONA STATE RTE 303 W. OLIVE AVE W. DIANA AVE COMMERCIAL AND INDUSTRIAL PLANS OF DEVELOPMENT (CUPD AND IUPD) REGULATION BASE ZONING DISTRICT REGULATIONS (C-2) PROPOSED ZONING DISTRICT REGULATIONS (IND-2) MAXIMUM HEIGHT 40' 40' MINIMUM FRONT YARD 10' 20' MINIMUM SIDE YARD 10' 10' MINIMUM STREET-SIDE YARD 10' 10' MINIMUM REAR YARD 25' 25' MINIMUM LOT AREA 6,000 SQ. FT. 6,000 SQ.FT. MINIMUM LOT WIDTH 60' 60' MINIMUM LOT COVERAGE 60% 60% PARKING SPACES SEE PARKING REGULATIONS N/A SCREENING 6' SOLID WALL 8' SOLID WALL SHEET LIST TABLE SHEET NUMBER SHEET TITLE C-001 COVER SHEET C-002 SITE PLAN C-003 HORIZONTAL CONTROL PLAN C-004 GRADING & DRAINAGE PLAN C-005 SITE CROSS SECTIONS C-006 PROJECT DETAILS LS-003 LANDSCAPE DETAILS LS-001 LANDSCAPE LAYOUT LS-002 LANDSCAPE DETAILS F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F EXISTING 60' X 60' BILLBOARD ESMT PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PARCEL NO. 3 APN 501-05-0055 DESERT FORREST NURSERY LLC DEED #20230101265 ZONING: C-2 LOT 2 APN 501-050006Q FHF LLC ZONING: RU-43 APN 501-05-005L COMER LLC ZONING: RU-43 APN 501-05-005M COMER LLC ZONING: RU-43 APN 501-05-005N CROMER LLC ZONING: RU-43 APN 501-05-005G FAMILY FIRST INVESTMENTS LLC ZONING: RU-43 APN 501-05-005D DESERT FORREST NURSERY LLC ZONING: RU-43 30' INGRESS/EGRESS ESMT DOC 2006-729581 & BOOK 895 MAPS, PG 9 20' SEWER ESMT DOC #2021-454610 100' ELEC ESMT DOC #2005-1613945 ABANDONED 30' INGRESS/EGRESS ESMT DOC #2007-661275 DOC #2007-661227 60' x 60' BILLBOARD ESMT ARIZONA D.O.T. R/W CONDEMNATION DOC #2013-1073662 RESTRICTED ACCESS DOC #2017-1073662 8' ELEC ESMT PER DOC 2022-701401 100' ELEC ESMT PER DOC #2007-775338 MARICOPA COUNTY R/W CONDEMNATION DOC #2019-0244870 11' DRAINAGE ESMT DOC 32020-445663 S S S S EXISTING FENCE EXISTING BLOCK FENCE EXISTING DRAINAGE GRATE (TYP) CORNERS FALL ON CHAIN LINK FENCE POSTS EXISTING BLOCK FENCE EXISTING GATE 8' ELEC ESMT PER DOC #2022-701401 EXISTING DRAINAGE GRATE (TYP ) FUTURE 60'x60' BILLBOARD EASEMENT OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE EXISTING POWER POLE (TYP) 8' ELEC ESMT PER DOC #2022-701401 LOT 2 87' ELEC ESMT DOC #2007-775338 139' 186' LOT 1 24' 15' VEGATATIVE BUFFER 11' PROPOSED ONSITE SUBSTATION PROPOSED CONTROL HOUSE GRAVEL 26' PRIVATE DRIVEWAY AND FIRE LANE PROPOSED 8' BLOCK WALL FOR SCREENING ALL PROPOSED VEHICULAR ACCESS GATES SHALL BE PROVIDED WITH A FIRE DEPARTMENT APPROVED LOCKING DEVICE (TYP.) W. LAWRENCE LN (EXTENSION) (PROPOSED ASPHALT PVMT) EXISTING PARCEL BOUNDARY PROPOSED AUXILIARY PAD (20'X20') TYP PROPOSED 8' BLOCK WALL FOR SCREENING CONNECT TO EXISTING W. LAWRENCE LN (20' WIDTH) R25' (TYP.) 16' UTILITY ACCESS ROAD 548' 100' SETBACK FROM WEST PROPERTY LINE TO BESS 100' SETBACK (TYP) 134' 26' 100' ELEC ESMT DOC #2005-1613945 HDPE PIPE 24" HDPE CULVERT AND HEADWALL FOR OFFSITE FLOWS PROPOSED 24" HDPE CULVERT WITH HEADWALLS (TYP) PROPOSED RETENTION BASIN GRAVEL 26' PRIVATE DRIVEWAY AND FIRE LANE GRAVEL 26' PRIVATE DRIVEWAY AND FIRE LANE PROPOSED 8' X 40' SPARE PARTS CONNEXES (TYP.) PROPOSED 40' X 60' O&M BUILDING CONNECT TO EXISTING ASPHALT PAVEMENT CONNECT TO EXISTING ASPHALT PAVEMENT OLIVE AVENUE PROPOSED UTILITY EASEMENT ACCESS ROAD RIPRAP OUTLET PROTECTION PROPOSED SWALE R25'(TYP) 6' 8' 50' TAPER PROPOSED AUGMENTATION BATTERY PROPOSED INVERTER (TYP) PROPOSED BATTERY PRIVATE DRIVE PROPOSED ASPHALT PVMT 66' OF ASPHALT PVMT 132' 532' 141' PROPOSED 2-24" HDPE CULVERT WITH HEADWALLS (TYP) CONNECT TO EXISTING ASPHALT PAVEMENT ADOT ROW (WIDTH VARIES) 60' VEGETATIVE BUFFER 24' 26' R25' R25' R51' (TYP) R51' PROPOSED PARKING (1) 9'x20' STANDARD (1) 10'X20' ACCESSIBLE 22' ALL PROPOSED VEHICULAR ACCESS GATES SHALL BE PROVIDED WITH A FIRE DEPARTMENT APPROVED LOCKING DEVICE (TYP.) ALL PROPOSED VEHICULAR ACCESS GATES SHALL BE PROVIDED WITH A FIRE DEPARTMENT APPROVED LOCKING DEVICE (TYP.) 500' SETBACK 100' SETBACK (TYP) 105' 6 Executive Circle Suite 200 Irvine, CA 92614 Phone: 949.727.9336 DATE: DRAWN BY: CHECKED BY: APPROVED BY: PROJECT: PROJ. NO.: TITLE: REVISION DATE NO. BY APP'D. SAGUARO BESS PROJECT 16835 W. OLIVE AVENUE WADDELL, AZ 85355 563842.0DMS TSS JT AW 1/31/2025 SEAL: DATE: PROFESSIONAL ENGINEER: a E n g i n e e r l n o i s s e f o r P R e g d e r e t s i ) L I V I ( C E C E R T I F I C A T . O N D d e n g i S e t a 0 1 . 3 1 . 2 0 2 5 . 76261 ALLYSON WILLIAMSON A N O Z I R A , A U S A . . . 1/31/2025 6 Executive Circle Suite 200 Irvine, CA 92614 Phone: 949.727.9336 DATE: DRAWN BY: CHECKED BY: APPROVED BY: PROJECT: PROJ. NO.: TITLE: REVISION DATE NO. BY APP'D. SAGUARO BESS PROJECT 16835 W. OLIVE AVENUE WADDELL, AZ 85355 563842.0DMS TSS JT AW 1/31/2025 SEAL: DATE: PROFESSIONAL ENGINEER: a E n g i n e e r l n o i s s e f o r P R e g d e r e t s i ) L I V I ( C E C E R T I F I C A T . O N D d e n g i S e t a 0 1 . 3 1 . 2 0 2 5 . 76261 ALLYSON WILLIAMSON A N O Z I R A , A U S A . . . 1/31/2025 GRAPHIC SCALE 0 60' 1" = 60' NORTH N LEGEND EXISTING MINOR CONTOUR EXISTING SIGN EXISTING MANHOLE EXISTING FIRE HYDRANT EXISTING STREET LIGHT EXISTING OVERHEAD ELECTRIC OE EASEMENT LINE EXISTING CHAIN LINK FENCE X PROPOSED TELCOM LINE TEL PROPOSED SUBSTATION CHAIN LINK FENCE XX XX EXISTING SEWER MANHOLE EXISTING STORM DRAIN MANHOLE PROPOSED ELECTRIC LINE EXISTING WATER VALVE EXISTING UTILITY BOX EXISTING UTILITY POLE PROPOSED CHAIN LINK FENCE X F PROPOSED FIRE HYDRANT EXISTING MAJOR CONTOUR EXISTING ELECTRIC MANHOLE ELE SD EXISTING UNKNOWN UTILITY CENTERLINE PROPOSED SETBACK PROPOSED VEGETATIVE BUFFER 60' PROPOSED 8' BLOCK WALL EXISTING PROPERTY BOUNDARY E PROPOSED GRAVEL DRIVEWAY(SEE DETAIL) PROPOSED FIRE LINE NOTE: 1. BOUNDARY SURVEY CONDUCTED BY LAND SURVEY SERVICES PLC (NOV 2024). 2. PROPOSED STORAGE CAPACITY: 250MW 3. FENCED IN SUBSTATION SHALL HAVE GRAVEL SURFACE. PROPOSED PAVED ROAD EXTENSION PL PROPOSED PROPERTY LINE EXISTING SEWER LINE EXISTING WATER LINE EXISTING DRAINAGE GRATE PROPOSED STORM DRAIN LINE VICINITY MAP NTS SITE PLAN C-002 PROPOSED FLOWLINE OE EXISTING OVERHEAD ELECTRIC PROPOSED STORM DRAIN MANHOLE PROPOSED CATCH BASIN F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F EXISTING 60' X 60' BILLBOARD ESMT PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PARCEL NO. 3 APN 501-05-0055 DESERT FORREST NURSERY LLC DEED #20230101265 ZONING: C-2 LOT 2 APN 501-050006Q FHF LLC ZONING: RU-43 APN 501-05-005L COMER LLC ZONING: RU-43 APN 501-05-005M COMER LLC ZONING: RU-43 APN 501-05-005N CROMER LLC ZONING: RU-43 APN 501-05-005G FAMILY FIRST INVESTMENTS LLC ZONING: RU-43 APN 501-05-005D DESERT FORREST NURSERY LLC ZONING: RU-43 30' INGRESS/EGRESS ESMT DOC 2006-729581 & BOOK 895 MAPS, PG 9 20' SEWER ESMT DOC #2021-454610 100' ELEC ESMT DOC #2005-1613945 ABANDONED 30' INGRESS/EGRESS ESMT DOC #2007-661275 DOC #2007-661227 60' x 60' BILLBOARD ESMT ARIZONA D.O.T. R/W CONDEMNATION DOC #2013-1073662 RESTRICTED ACCESS DOC #2017-1073662 8' ELEC ESMT PER DOC 2022-701401 100' ELEC ESMT PER DOC #2007-775338 MARICOPA COUNTY R/W CONDEMNATION DOC #2019-0244870 11' DRAINAGE ESMT DOC 32020-445663 CORNERS FALL ON CHAIN LINK FENCE POSTS SET COTTON PICKER SPINDLE W/TAG LS 21081 8' ELEC ESMT PER DOC #2022-701401 FUTURE 60'x60' BILLBOARD EASEMENT OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE 8' ELEC ESMT PER DOC #2022-701401 LOT 2 87' ELEC ESMT DOC #2007-775338 139' 186' LOT 1 PROJECT BOUNDARY EXISTING PARCEL BOUNDARY 26' (TYP) 20' SETBACK 11' 15' TYP 109' 62' 68' 211' 196' 100' N: 932985.45 E: 545847.48 N: 932985.45 E: 546793.24 N: 933009.78 E: 546793.98 N: 933587.25 E: 546803.50 N: 933790.96 E: 545847.48 24' 272' 165' W. LAWRENCE LN (EXTENSION) N: 933591.04 E: 546653.49 N: 933720.99 E: 546655.69 N: 933723.03 E: 546572.56 N: 933743.02 E: 546572.96 N: 933744.09 E: 546534.17 N: 933790.75 E: 546024.36 N: 933743.69 E: 546024.36 12' 6' 10' TYP 23' R28' (TYP) 41' 103' 157 186 N90° 00' 00.00"W 945.76' N0° 00' 00.00"E 805.51' N90° 00' 00.00"E 176.91' S0° 00' 00.00"E 47.19' N89° 58' 25.12"E 289.83' N89° 55' 49.98"E 219.98' S88° 37' 19.26"E 38.81' S1° 31' 39.09"W 20.00' S88° 31' 52.32"E 83.22' S0° 56' 21.09"W 130.14' S88° 37' 30.59"E 150.03' S0° 55' 46.80"W 197.20' S1° 00' 00.44"W 404.82' RETENTION BASIN PROPOSED CONTROL HOUSE PROPOSED 8' X 40' SPARE PARTS CONNEXES (TYP) R28' (TYP) 229' OLIVE AVENUE LOT 2 LOT 1 S1° 00' 00.44"W 404.82' 6 Executive Circle Suite 200 Irvine, CA 92614 Phone: 949.727.9336 DATE: DRAWN BY: CHECKED BY: APPROVED BY: PROJECT: PROJ. NO.: TITLE: REVISION DATE NO. BY APP'D. SAGUARO BESS PROJECT 16835 W. OLIVE AVENUE WADDELL, AZ 85355 563842.0DMS TSS JT AW 1/31/2025 SEAL: DATE: PROFESSIONAL ENGINEER: a E n g i n e e r l n o i s s e f o r P R e g d e r e t s i ) L I V I ( C E C E R T I F I C A T . O N D d e n g i S e t a 0 1 . 3 1 . 2 0 2 5 . 76261 ALLYSON WILLIAMSON A N O Z I R A , A U S A . . . 1/31/2025 6 Executive Circle Suite 200 Irvine, CA 92614 Phone: 949.727.9336 DATE: DRAWN BY: CHECKED BY: APPROVED BY: PROJECT: PROJ. NO.: TITLE: REVISION DATE NO. BY APP'D. SAGUARO BESS PROJECT 16835 W. OLIVE AVENUE WADDELL, AZ 85355 563842.0DMS TSS JT AW 1/31/2025 SEAL: DATE: PROFESSIONAL ENGINEER: a E n g i n e e r l n o i s s e f o r P R e g d e r e t s i ) L I V I ( C E C E R T I F I C A T . O N D d e n g i S e t a 0 1 . 3 1 . 2 0 2 5 . 76261 ALLYSON WILLIAMSON A N O Z I R A , A U S A . . . 1/31/2025 GRAPHIC SCALE 0 60' 1" = 60' NORTH N 60' LEGEND HORIZONTAL CONTROL PLAN C-003 VICINITY MAP NTS EXISTING MINOR CONTOUR EXISTING SIGN EXISTING MANHOLE EXISTING FIRE HYDRANT EXISTING STREET LIGHT EXISTING OVERHEAD ELECTRIC OE EASEMENT LINE EXISTING CHAIN LINK FENCE X PROPOSED TELCOM LINE TEL PROPOSED SUBSTATION CHAIN LINK FENCE XX XX EXISTING SEWER MANHOLE EXISTING STORM DRAIN MANHOLE PROPOSED ELECTRIC LINE EXISTING WATER VALVE EXISTING UTILITY BOX EXISTING UTILITY POLE PROPOSED CHAIN LINK FENCE X F PROPOSED FIRE HYDRANT EXISTING MAJOR CONTOUR EXISTING ELECTRIC MANHOLE ELE SD EXISTING UNKNOWN UTILITY CENTERLINE PROPOSED SETBACK PROPOSED VEGETATIVE BUFFER PROPOSED 8' BLOCK WALL EXISTING PROPERTY BOUNDARY E PROPOSED GRAVEL DRIVEWAY PROPOSED FIRE LINE PROPOSED PAVED ROAD EXTENSION PL PROPOSED PROPERTY LINE EXISTING SEWER LINE EXISTING WATER LINE EXISTING DRAINAGE GRATE PROPOSED STORM DRAIN LINE PROPOSED FLOWLINE OE EXISTING OVERHEAD ELECTRIC PROPOSED STORM DRAIN MANHOLE PROPOSED CATCH BASIN LOT 1: A PORTION OF THE NORTH HALF OF THE NORTHWEST QUARTER OF SECTION 36, TOWNSHIP 3 NORTH, RANGE 2 WEST OF THE GILA AND SALT RIVER BASE AND MERIDIAN, MARICOPA COUNTY, ARIZONA, DESCRIBED AS FOLLOWS: COMMENCING AT THE NORTHWEST CORNER OF SAID SECTION 36, FROM WHENCE THE NORTH QUARTER CORNER OF SECTION 36 BEARS NORTH 90° 00' 00” EAST (BASIS OF BEARINGS) A DISTANCE OF 2631.41 FEET; THENCE NORTH 90° 00' 00” EAST ALONG THE NORTH LINE OF SAID SECTION 36 A DISTANCE OF 1952.49 FEET; THENCE SOUTH 00° 00' 11” EAST A DISTANCE OF 185.76 FEET TO THE WESTERLY RIGHT-OF-WAY LINE OF STATE ROUTE LOOP 202 AS DESCRIBED IN FINAL ORDER OF CONDEMNATION RECORDED IN DOCUMENT NO. 2013-1073662, OFFICIAL RECORDS AND THE POINT OF BEGINNING; THENCE ALONG SAID WESTERLY RIGHT-OF-WAY LINE FOR THE NEXT SEVEN (7) COURSES: THENCE SOUTH 88° 33' 47" EAST A DISTANCE OF 38.80 FEET; THENCE SOUTH 01° 26' 13" WEST A DISTANCE OF 20.00 FEET; THENCE SOUTH 88° 33' 47" EAST A DISTANCE OF 83.17 FEET; THENCE SOUTH 00° 56' 52" WEST A DISTANCE OF 130.00 FEET; THENCE SOUTH 88° 33' 47" EAST A DISTANCE OF 150.01 FEET; THENCE SOUTH 00° 56' 52" WEST A DISTANCE OF 577.62 FEET TO THE BEGINNING OF A TANGENT CURVE, WHOSE RADIUS BEARS NORTH 89° 03' 08" WEST A DISTANCE OF 995.00 FEET; THENCE SOUTHERLY ALONG SAID CURVE THROUGH A CENTRAL ANGLE OF 01° 24' 30" A DISTANCE OF 24.46 FEET TO A NON-TANGENT LINE; THENCE NORTH 90° 00' 00" WEST A DISTANCE OF 945.81 FEET TO THE CENTERLINE OF AN EXISTING 100 FOOT WIDE ELECTRIC EASEMENT AS DESCRIBED IN DOCUMENT NO. 2005-1613945, OFFICIAL RECORDS; THENCE NORTH 00° 00' 12" EAST ALONG SAID CENTERLINE A DISTANCE OF 242.43 FEET TO THE CENTERLINE OF AN EXISTING 100 FOOT WIDE ELECTRIC EASEMENT AS DESCRIBED IN DOCUMENT NO. 2007-775338, OFFICIAL RECORDS; THENCE NORTH 00° 00' 20” EAST ALONG SAID CENTERLINE A DISTANCE OF 563.12 FEET TO THE TO THE SOUTH RIGHT-OF-WAY LINE OF OLIVE AVENUE AS DESCRIBED IN FINAL JUDGMENT IN CONDEMNATION RECORDED IN DOCUMENT NO. 2019-244870, OFFICIAL RECORDS; THENCE ALONG SAID RIGHT-OF-WAY LINE FOR THE NEXT THREE (3) COURSES: THENCE NORTH 90° 00' 00" EAST A DISTANCE OF 176.83 FEET; THENCE SOUTH 00° 00' 00" WEST A DISTANCE OF 47.00 FEET; THENCE NORTH 90° 00' 00" EAST A DISTANCE OF 289.93 FEET TO THE SOUTH RIGHT-OF-WAY LINE OF OLIVE AVENUE AS DESCRIBED IN FINAL JUDGMENT IN CONDEMNATION RECORDED IN DOCUMENT NO. 2019-258794, OFFICIAL RECORDS; THENCE NORTH 89° 56' 24" EAST ALONG SAID RIGHT-OF-WAY LINE A DISTANCE OF 220.00 FEET TO THE POINT OF BEGINNING; LOT 2: A PORTION OF THE NORTH HALF OF THE NORTHWEST QUARTER OF SECTION 36, TOWNSHIP 3 NORTH, RANGE 2 WEST OF THE GILA AND SALT RIVER BASE AND MERIDIAN, MARICOPA COUNTY, ARIZONA, DESCRIBED AS FOLLOWS: COMMENCING AT THE NORTHWEST CORNER OF SAID SECTION 36, FROM WHENCE THE NORTH QUARTER CORNER OF SECTION 36 BEARS NORTH 90° 00' 00” EAST (BASIS OF BEARINGS) A DISTANCE OF 2631.41 FEET; THENCE SOUTH 00° 01' 20” WEST ALONG THE WEST LINE OF SAID SECTION 36 A DISTANCE OF 673.98 FEET; THENCE NORTH 89° 06' 48” EAST A DISTANCE OF 58.88 FEET TO THE EAST RIGHT-OF-WAY LINE OF COTTON LANE AS DESCRIBED IN ORDER FOR POSSESSION AS DESCRIBED IN DOCUMENT NO. 2017-805516, OFFICIAL RECORDS AND THE MOST WESTERLY NORTHWEST CORNER OF PARCEL NO. 1 OF “MINOR LAND DIVISION” AS RECORDED IN BOOK 1445 OF MAPS, PAGE 9, OFFICIAL RECORDS AND THE POINT OF BEGINNING; THENCE CONTINUING NORTH 89° 06' 48" EAST ALONG THE NORTH LINE OF SAID PARCEL NO. 1 A DISTANCE OF 603.77 FEET; THENCE NORTH 00° 00' 39" EAST ALONG THE WEST LINE OF SAID PARCEL NO. 1 AND OF PARCEL NO. 2 OF SAID “MINOR LAND DIVISION” A DISTANCE OF 340.31 FEET TO THE SOUTHWEST CORNER OF THAT PARCEL DESCRIBED IN SPECIAL WARRANTY DEED RECORDED IN DOCUMENT NO. 2019-647421, OFFICIAL RECORDS; THENCE NORTH 89° 56' 00" EAST ALONG THE SOUTH LINE THEREOF A DISTANCE OF 225.90 FEET TO THE SOUTHEAST CORNER OF SAID PARCEL; THENCE NORTH 00° 00' 39" EAST ALONG THE EAST LINE THEREOF A DISTANCE OF 188.53 FEET TO THE SOUTH RIGHT-OF-WAY LINE OF OLIVE AVENUE AS DESCRIBED IN FINAL JUDGMENT IN CONDEMNATION RECORDED IN DOCUMENT NO. 2019-244870, OFFICIAL RECORDS, BEING ON A NON-TANGENT CURVE, WHOSE RADIUS BEARS NORTH 01° 41' 21" EAST A DISTANCE OF 10,055.00 FEET; THENCE EASTERLY ALONG SAID CURVE AND SAID RIGHT-OF-WAY LINE THROUGH A CENTRAL ANGLE OF 01° 41' 21" A DISTANCE OF 296.44 FEET TO A TO A POINT OF TANGENCY; THENCE NORTH 90° 00' 00" EAST ALONG SAID RIGHT-OF-WAY LINE A DISTANCE OF 81.05 FEET TO THE CENTERLINE OF AN EXISTING 100 FOOT WIDE ELECTRIC EASEMENT AS DESCRIBED IN DOCUMENT NO. 2007-775338, OFFICIAL RECORDS; THENCE SOUTH 00° 00' 20” WEST ALONG SAID CENTERLINE A DISTANCE OF 563.12 FEET TO THE CENTERLINE OF AN EXISTING 100 FOOT WIDE ELECTRIC EASEMENT AS DESCRIBED IN DOCUMENT NO. 2005-1613945, OFFICIAL RECORDS; THENCE SOUTH 90° 00' 00” EAST A DISTANCE OF 945.81 FEET TO THE WESTERLY RIGHT-OF-WAY LINE OF STATE ROUTE LOOP 202 AS DESCRIBED IN FINAL ORDER OF CONDEMNATION RECORDED IN DOCUMENT NO. 2013-1073662, OFFICIAL RECORDS, SAID POINT BEING ON A NON-TANGENT CURVE WHOSE RADIUS BEARS NORTH 87° 38' 38” WEST A DISTANCE OF 955.00 FEET; THENCE SOUTHERLY ALONG SAID RIGHT-OF-WAY LINE THROUGH A CENTRAL ANGLE OF 22° 33' 05” A DISTANCE OF 391.63 FEET TO THE SOUTH LINE OF THE NORTH HALF OF THE NORTHWEST QUARTER OF SECTION 36; THENCE SOUTH 89° 58' 03" WEST ALONG SAID SOUTH LINE A DISTANCE OF 919.29 FEET TO THE SOUTHEAST CORNER OF PARCEL “B” AS SHOWN ON “RESULTS OF SURVEY/MINOR LAND DIVISION” AS RECORDED IN BOOK 895 OF MAPS, PAGE 9, OFFICIAL RECORDS; THENCE NORTH 00° 01' 20" EAST ALONG THE EAST LINE THEREOF A DISTANCE OF 310.67 FEET TO THE NORTHEAST CORNER OF SAID PARCEL “B”; THENCE SOUTH 89° 58' 33" WEST ALONG THE NORTH LINE OF PARCEL “A” AND PARCEL “B” OF SAID “MINOR LAND DIVISION” A DISTANCE OF 1146.00 FEET TO THE EAST RIGHT-OF-WAY LINE OF COTTON LANE AS DESCRIBED IN FINAL ORDER OF CONDEMNATION RECORDED IN DOCUMENT NO. 2019-215665, OFFICIAL RECORDS; THENCE NORTH 00° 01' 20" EAST ALONG SAID EAST LINE A DISTANCE OF 310.56 FEET TO THE NORTH LINE OF PARCEL “C” OF SAID “MINOR LAND DIVISION”; THENCE NORTH 00° 01' 12” EAST A DISTANCE OF 2.32 FEET; THENCE NORTH 08° 08' 58” EAST A DISTANCE OF 27.35 FEET TO THE POINT OF BEGINNING. Saguaro BESS Project CITIZEN PARTICIPATION PLAN FOR ZONE CHANGE WITH OVERLAY (C-2 CUPD TO IND-2 IUPD) Generally at the SEC of Olive Avenue and Cotton Lane CASE # Z202412 First Submittal: February 8, 2023 Second Submittal: July 8, 2024 Citizen Participation Plan This Citizen Participation Plan is being implemented in conjunction with a proposed Zone Change with Overlay from C-2 CUPD to IND-2 IUPD (the “Zone Change”) to facilitate the development of a new battery energy storage system. The proposed project is located generally at the southeast corner of Olive Avenue and Cotton Lane (the “Site”) in un-incorporated Maricopa County. This Citizen Participation Plan is meant to open the lines of communication between the residents and property owners in the surrounding area of the Site, and to facilitate the meaningful inclusion of all interested parties in the development of this Zone Change application. A. Parties Affected by the Application The area affected by this Zone Change application can be defined as a 300’ area around the boundary of the Site. The development team has notified the property owners within this area as well as all HOA’s and the 22 “Area of Interest” groups identified by the County during the Pre-Application process. The applicant has also post the Site with all required information regarding the details of the request for the Zone Change. B. Notification and Information Procedures The required letters, posting and personal contact with interested parties are the most appropriate notification techniques for this type of request. These various forms of communication will occur on an on-going basis beginning with the approval of this Citizen Participation Plan. The development team is committed to ensuring that all interested parties are advised of the pending request and understand all issues relative thereto. Information will be made available in the following ways: 1. As set forth above, letters will be sent to (i) property owners within 300 feet of the Site boundary, (ii) all adjacent HOAs, and (iii) the 22 “Area of Interest” groups identified by the County during the Pre-Application process. Enclosed with the letter is a map of the Site, an explanation of the uses proposed with the Zone Change, and the applicant’s contact information. Recipients will be encouraged to call, email, or otherwise contact the applicant or the County with any questions. 2. For all contact made with interested parties to discuss this Zone Change application, a record of that contact will be sent to the County. This record will include names of those involved, time, date, place, and method of contact as well as the issues discussed. 3. At least 30 days prior to the first public hearing, and within 30 days of submittal of the official Zone Change application, a Public Notification Sign will be erected on or near the Site stating the type of application requested, a general description of the proposed request, the dates, times, and locations of public hearings, and the applicant’s and County’s contact information. C. Response Procedures Through the notification techniques described above, all interested parties will be able to gain a full understanding of the Zone Change application and will be able to contact the development team to voice their issues and concerns. The ways in which interested parties will be able to contact the development team include, but are not limited to, telephone, US Mail, personal contact, and/or email. The issues and concerns brought to the attention of the development team will be taken into consideration and further communication will be initiated by the development team to fully consider those comments and, wherever possible, integrate them into the application and proposal throughout the application process. D. Schedule of Completion 1. In November 2023, this Citizen Participation Plan will be submitted, along with the formal Zone Change application, for review by the Maricopa County Planning and Development Department Staff. The development team will make appropriate changes according to Maricopa County Staff’s comments. 2. Following Maricopa County Staff’s approval of this Citizen Participation Plan, notification to all interested parties will be sent out and verification of this via a notarized affidavit will be provided to the County. 3. The Site will be posted with the required signage at least 30 days prior to the first public hearing and within 30 days of submitting the official application. The Site will be posted according to the sign specifications of the Maricopa County Planning and Development Department. E. Status Procedure As interested parties reply to the letters and signage, communication will be opened between those citizens and the development team to address all questions, concerns, and comments. The results of those discussions and the feedback gained will be taken into consideration with the application. This will be an ongoing aspect of the Citizen Participation Plan from first notification through to the Board of Supervisors public hearing. As a part of the application process, the development team will be in close communication with the Maricopa County Planning and Development Department to ensure that they are fully apprised of the progress and inclusiveness of the citizen participation process. Prior to Maricopa County providing official notice of public hearing, a written report will be submitted detailing the results of the Citizen Participation Plan. This report will include; (i) a summary of all contact with interested parties, (ii) a description of the approximate number of people that participated in the public participation process, and where they are located in relation to the Subject Property, (iii) a discussion of the results of the citizen participation process, including major issues and concerns identified by interested parties and how the development team has and will address them, and (iv) an appendix of information, including mailings and other pertinent materials that were used to help describe the public participation program. F. Update on Outreach Since the notice letters have gone out to adjacent neighbors per the procedure outlined above, no comments, calls, or emails have been received. The application team has made two visits to the Site to engage neighbors along Lawrence lane, on March 6th from 5:30pm to 6pm and on June 12th from 5pm to 6pm. The application team spoke with two residents, one of whom signed the support petition and the other took the representative card and a copy of the notice letter and indicated they would call if they had any questions. A support petition has been signed by eight (8) residents and businesses owners from the surrounding neighborhoods and this is attached to this plan as Exhibit A. Exhibit “A” Support Petition Page 1 of 1 Anh Harambasic, PE Planning & Development 301 W. Jefferson St., Suite 170 Phoenix, Arizona 85003 Phone: (602) 506-3611 www.maricopa.gov/planning Email address: anh.harambasic@maricopa.gov Planning & Development Engineering Plan Review Date: February 27, 2024 Memo To: Darren Gerard, AICP, Planning Manager, Department of Planning & Development Attn: Joel Landis, Planner, Planning & Development Services From: Anh Harambasic, P.E., Engineering Reviewer, Planning & Development Services cc: Bob Fedorka, P.E., Engineering Manager, Planning & Development Subject: Z2024012 - Zone Change with Overlay Battery Storage. From C-2 to Light Industrial (IND-2) Job Site Address: SEC of Olive Avenue and Cotton Lane APN(s): 501-05-005S,501-05-005U,501-05-005R,501-05-005M This application is to specify zoning with overlay for future development and does not include a Plan of Development. PND Engineering Plan Review (DPR, FCD and PND Transportation) has reviewed the 1st submittal of the Zone Change application routed for review and has no objections subject to the following conditions: 1. Without the submittal of a precise plan of development, no development approval is inferred by this review, including, but not limited to number of proposed building lots/units, drainage design, access and roadway alignments. These items will be addressed as development plans progress and are submitted to the County for further review and/or entitlement. 2. A traffic impact study must be submitted with future entitlement (POD or Preliminary Plat) application(s). 3. Engineering review of re-zone cases is conceptual in nature. All development and engineering design shall be in conformance with Section 1205 of the Maricopa County Zoning Ordinance; Drainage Policies and Standards; Floodplain Regulations for Maricopa County; MCDOT Roadway Design Manual; and current engineering policies, standards and best practices at the time of application for construction. Please contact me if you have any questions or require any additional information. DATE: March 6, 2025 TO: Planning & Zoning Commission From: Joel Landis, Planner SUBJECT: Z2024012 – Saguaro BESS Agenda Item: 2 Since the publication of the staff report for the referenced case, staff received a letter from Sandra Watson, President & CEO of the Arizona Commerce Authority in support of the Saguaro BESS case. Attachment: Letter of Support (1 page) March 5, 2025 To Whom It May Concern, I am writing to express my support for Aypa Power’s battery energy storage project (Saguaro BESS) in Maricopa County. With a rapidly growing energy storage industry and unbeatable business environment, Arizona is well positioned to support this project’s long-term success. Arizona’s robust battery ecosystem has attracted leaders across manufacturing, recycling, suppliers, mineral development and more to include LG Energy Solution, American Battery Factory, Sion Power, and Li-Cycle. In addition, Arizona is at the forefront of clean energy development with over $10 billion in private industry investment announcements since 2023. The state is home to a diverse ecosystem of clean energy leaders - from battery manufacturers and to hydrogen producers, solar manufacturers and more. The state also is home to one of the nation’s largest power producers of any kind - the Palo Verde Generating Station. Aypa Power will benefit from Arizona’s relative lack of natural disasters, reliable and affordable energy grid, dependable water resources, and modern transportation infrastructure. I am confident Aypa Power will find Arizona an excellent location for its new $200 million battery energy storage facility, which will provide energy capacity to help fuel Arizona’s growing economy. Thank you for considering Arizona for this exciting project. Our team stands ready to support at every step to ensure Arizona remains the location of choice. Sincerely, Sandra Watson President & CEO Arizona Commerce Authority