Building Code Amendments (updated 8/22/2025)*
Extracted text (via pymupdf)
111832 characters
1
ORDINANCE NO.
NEW SERIES
AN ORDINANCE OF THE COUNCIL OF THE CITY OF GLENDALE,
MARICOPA COUNTY, ARIZONA, AMENDING GLENDALE CITY CODE,
CHAPTER 9, ARTICLES II AND III, REGARDING THE ADOPTION OF AND
AMENDMENTS TO THE TECHNICAL CODES RELATING TO BUILDINGS,
BUILDING REGULATIONS AND
WATER CONSERVATION; AND
SETTING FORTH AN EFFECTIVE DATE.
BE IT ORDAINED BY THE COUNCIL OF THE CITY OF GLENDALE as follows:
SECTION 1. That the Glendale City Code Chapter 9, Article II is deleted in its entirety and a new
Article II is adopted and shall read as follows:
ARTICLE II. TECHNICAL CODES
Sec. 9-16. Adopted by reference; violation.
(a) The following publications, one (1) copy each of which is on file in the office of the city clerk,
are adopted by reference as if set out at length in this Code.
(1) 2024 International Building Code, as published by the International Code Council, Inc.,
including Appendix Chapters C and I;
(2) 2024 International Residential Code, as published by the International Code Council,
Inc., including Appendix Chapters BB, BC, BF, BO and CF;
(3) 2024 International Existing Building Code, as published by the International Code
Council, Inc.;
(4) 2024 International Mechanical Code, as published by the International Code Council,
Inc.;
(5) 2024 International Plumbing Code, as published by the International Code Council, Inc.,
including Appendix Chapters B, C and E;
(6) 2024 International Fuel Gas Code, as published by the International Code Council, Inc.,
including Appendix Chapters A and B;
(7) 2023 National Electrical Code, as published by the National Fire Protection Association;
(8) 2024 International Property Maintenance Code, as published by the International Code
Council, Inc.;
(9) 2024 International Energy Conservation Code , as published by the International Code
Council, Inc.;
(10) 2024 International Swimming Pool and Spa Code, as published by the International
Code Council, Inc.;
2
(11) 2024 International Green Construction Code, as published by the International Code
Council, Inc. (voluntary compliance);
(12) Arizonans with Disabilities Act , (A.R.S. § 41-1492.03) and the Act's implementing rules
(28 CFR Part 35, and 28 CFR 36);
(13)
2010 Americans with Disabilities Act Standards for Accessible Design;
(14)
Maricopa Association of Governments Fireplace Standard;
(15) Fair Housing Accessibility Guidelines as published by the U.S. Department of Housing and
Urban Development on March 6, 1991.
(b) Any person violating any of the provisions of the publications adopted in subsection (a) shall
be guilty of a misdemeanor.
Sec. 9-17. - Amendments to the 2024 International Building Code.
The 2024 International Building Code is amended in the following respects:
Section 101.1 is amended to read as follows:
101.1 Title. These regulations shall be known as the Building Code of the City of Glendale,
Arizona, hereinafter referred to as "this code."
Section 103.1 is amended to read as follows:
103.1 Creation of Enforcement Agency. The Building Safety Division is hereby created and
the official in charge thereof shall be known as the building official. The function of the
agency shall be the implementation, administration and enforcement of the provisions of this
code.
Section 104.2.3, Alternative materials, design and methods of construction and equipment, delete
the Exception.
Section 104.2.4.1, Flood Hazard Areas is amended as follows:
Replace the words "building official" with "city engineer or functional equivalent"
Section 104.7 Official records is amended to read as follows:
The building official shall keep official records as required as required by Sections 104.7.1
through 104.7.5. Such official records shall be retained in accordance with the regulations of
the State of Arizona and City Clerk’s Office.
Section 104.8, Liability is amended by replacing “member of the board of appeals” with “hearing
officer” in the first sentence.
Section 105.2, Work Exempt from Permit, item 2, is amended to read as follows:
2. Fences, other than swimming pool barriers and perimeter subdivision fences, not over 7 feet
(2134 mm) high.
3
Section 105.2, Work exempt from permit, Building, add the following item:
14. Hoophouses and polyhouses used exclusively for producing and storing live plants,
constructed in accordance with A.R.S. 9-469. Mechanical, plumbing and electrical systems
constructed in these structures shall require the appropriate permits in accordance with this
code.
Section 105.6, Suspension or Revocation is amended by adding the following:
It shall be unlawful to proceed with any work for which a permit was issued after notice of
permit suspension or revocation is served on the permit holder, the owner, or the person having
responsible charge of the work. Reinstatement of a suspended permit shall be by written notice
from the building official authorizing work to resume, with or without conditions. Revoked
permits shall be canceled and the permit fee shall not be refunded.
Section 109 is deleted and replaced by the following:
Section 109 Fees
109.1 Fee Schedule. Fees shall be assessed in accordance with the provisions of this section
and shall be as established by council resolution.
109.2 Permit Fees. Fees shall be as established by council resolution.
109.3 Plan Review Fees. When submittal documents are required by Section 107 of this code,
a plan review fee shall be paid at the time of submitting the documents for plan review. The
plan review fees specified in this section and as by council resolution are separate fees from,
and in addition to, the permit fees specified in Section 109.2 of this code.
109.4 Building Permit Valuations. The determination of valuation under any provisions of the
code shall be made by the building official. The valuation to be used in computing the building
permit and building plan review fees shall be the total value of all construction work including
all materials, labor, overhead and profit for which the permit is issued including all finish
work, painting, roofing, electrical, plumbing, heating, air-conditioning, elevators, fire-
extinguishing systems, and other permanent equipment.
109.5 Work Commencing Before Permit Issuance. Whenever work for which a permit is
required by this code has been commenced without first obtaining a permit, a special
investigation shall be made before a permit may be issued for such work.
An investigation fee, in addition to the permit fee, shall be collected whether or not a permit
is then or subsequently issued. The investigation fee shall be as adopted by council resolution.
The payment of such investigation fee shall not exempt an applicant from compliance with all
other provisions of either this code or other adopted laws and ordinances of this city.
109.6 Reinspection fees. Permit fees provide for customary inspections only. A reinspection
fee may be assessed for each inspection or reinspection when such portion of the work for
which inspection is called is not complete or when corrections called for are not made.
Reinspection fees may be assessed when the inspection record card is not posted or otherwise
4
readily available to the inspector, for failure to provide access on the date for which inspection
is requested, or for deviating from plans requiring the approval of the building official. In
instances where reinspection fees have been assessed, additional inspection of the work will
not be performed until the required fees have been paid.
Section 110.1, Inspections, General is amended by adding the following paragraph:
Property owners shall obtain and display on the residence, business, or otherwise, the correct
building number or numbers as assigned to such property(ies) by the Planning Department or
functional equivalent in accordance with established street assignment policy, prior to final
inspection and /or issuance of a certificate of occupancy. The building numbers shall be of a
durable material, permanently attached to the building and must be readily distinguished and
readable from the nearest paved public/common roadway fronting that property. The size of
the building numbers shall comply with the city’s adopted fire code and its amendments.
Section 110.3.3, Lowest Floor Elevation is amended as follows:
Replace “building official” with “City Engineer or functional equivalent.”
Section 110.3.4, Frame Inspection is amended by adding the following sentence:
The building shall be weather-tight at the time of the frame inspection.
Section 110.3.11 is deleted and amended by the following text:
110.3.11 Special Inspections.
In addition to the inspections required by Section 110, the engineer or architect of record
acting as the owner's agent shall employ one or more special inspectors who shall provide
inspections during construction for types of work outlined in Chapter 17 and as outlined
below:
110.3.11.1 Electrical Special Inspections.
1.
Ground-fault protection performance tests for equipment are required to be provided
with ground-fault protection.
2.
Switchboards, panelboards, motor control centers, and other equipment rated 1,000
amps or more; or over 600 volts.
3.
Emergency and standby power systems, including switchboards, panel boards,
distribution boards, transfer equipment, power source, conductors, fire pumps, and
exhaust and ventilation fans.
110.3.11.2 Electrical Observation. Electrical observation shall be provided for the following
installations:
1.
Installation or alteration of that portion of health care facility electrical systems
which fall within the scope of Article 517, Chapter III of the adopted National
Electric Code where critical care areas are present.
2.
Installations or alterations of high-voltage electrical systems, which exceed 600
volts. Installations or alterations of electrical systems within locations classified as
5
hazardous by the provisions of adopted the National Electric Code, or the
International Fire Code, except for gasoline dispensing installations and systems
located within storage garages, repair garages or lubritoriums.
3.
When such observation is specifically required by the building official.
The owner shall employ the engineer responsible for the electrical design, or another engineer
designated by the engineer responsible for the electrical design to perform visual observation
of complex electrical equipment and systems for general conformance to the interconnection
of equipment. Electrical observation shall be performed at significant stages of the
construction and when the installation is complete and ready to be inspected by the building
official.
Section 110.3.13 is added as follows:
110.3.13 Building Service Equipment Inspections. All building service equipment inspections
for which a permit is required by this code shall be inspected by the building official. No
portion of any building service equipment intended to be concealed by any permanent portion
of the building shall be concealed until inspected and approved. When the installation of any
building service equipment is complete, an additional and final inspection shall be made.
Building service equipment regulated by the technical codes shall not be connected to the
water, fuel or power supply or sewer system until authorized by the building official.
1.
Electrical inspections. A rough-in inspection is required for all conduit, semi-rigid
piping or wiring after installation but prior to being concealed. Final inspection is
required when all conduit, wires, fixtures and equipment including covers, have been
installed and connected.
2.
Mechanical inspections. All mechanical equipment and systems for which a permit
is required by the code, including all associated ductwork, flues, condensate and
refrigeration lines, shall be subject to inspection and shall remain accessible and
exposed for inspection purposes until approved.
3.
Plumbing inspections. A rough-in or underground inspection is required for all
sewer, drainage and vent piping, and for all water and gas distribution systems prior
to their being buried or concealed. A final inspection is required when all fixtures are
set and operating or ready to operate. Tests shall be performed as required by the
currently adopted plumbing code.
Section 111.5 is added as follows:
111.5 Certificate of Completion for Shell Buildings. The building official is authorized to
issue a Certificate of Completion for all commercial shell/ non-occupied buildings and/ or
structures. This document will be utilized to indicate the building official’s approval and
completion of non-occupied buildings and/or structures also defined or labeled as “Shell
Buildings, Vanilla Shell, Grey Shell, Equipment Installation and Spec Suites.”
The Certificate of Completion document must specify the following:
1. Specify “No occupancy” or “Occupancy of one (1) person allowed only for
maintenance, security or fire watch”
2. Certificate/ permit number
6
3. Date
4. Premises, address, suite number
5. Legal description, Assessor’s Parcel Number (APN)
6. Type of construction
7. Occupancy group: UNOCCUPIED
8. Owner
9. General contractor
10. Date of permit
11. Valuation
12. Comments (building area, AFES, occupant load)
13. Other conditions (specified by the building official)
Section 113 is deleted and replaced by the following:
113 MEANS OF APPEALS
113.1 General. Decisions of the building official shall be appealed to Glendale City Court.
An application for an appeal of any order, decision or interpretation made by the building
official shall be filed in writing, along with the appropriate fee established by resolution or
pursuant to Glendale City Code Sec. 2-3, and shall be delivered to the Court and to the building
official within thirty (30) calendar days of the date of the order, decisions or interpretation.
The fee shall not be refundable. The decision of the building official may be reversed or
modified by the Court upon finding that:
a.
The decision of the building official is not supported by a reasonable interpretation
and application of the city code to the specific facts presented, or the city code does
not apply to the facts presented.
b.
The reversal or modification of the building official's decision will not create or
manifest injustice or affect the intent of the city code.
c.
The reversal of the building official's decision will not be detrimental to the public
health, safety and welfare.
113.2 Limitations of Authority. The Court shall have no authority relative to interpretation of
the administrative provisions of the codes set forth in Sec. 9-16, nor shall the Court be
empowered to waive the requirements of the codes set forth in Sec. 9-16.
Section 116, Unsafe Structures and Equipment is amended as follows:
Section 116.1, Unsafe conditions. The requirements for the abatement of unsafe buildings,
structures and equipment shall be governed by the 2024 International Property Maintenance
Code and its related amendments.
The balance of the text of IBC Section 116 is deleted.
7
Section 201.4, Terms Not Defined is amended by adding to the end of this subsection:
Mirriam-Webster's Unabridged Dictionary of the English Language shall be considered as
providing ordinarily accepted meanings.
Section 202, Definitions is amended by revising the following definition:
ELECTRIC VEHICLE CHARGING STATION. One or more vehicle spaces served by an
electric vehicle charging system, including the vehicle charging system.
Section 202, Definitions is amended by revising the following definitions:
EXISTING BUILDING. A building erected prior to the date of adoption of the appropriate
code, or one for which a legal building permit has been issued and all required inspections
have been approved.
EXISTING STRUCTURE. A structure erected prior to the date of adoption of the
appropriate code, or one for which a legal building permit has been issued and all required
inspections have been approved.
Section 406.3 is amended by adding the following subsection:
406.3.4 Open Carports. Carports for other than single family residential use which are open
on all sides and constructed entirely of noncombustible materials, except for an approved
fascia, shall not exceed 5,000 square feet and shall be located no closer than 3 feet to an
adjacent lot line, nor closer than 6 feet to any projecting element of an adjacent building or
structure. The edge of the carport roof shall be used to measure the separation distance to
adjacent lot lines, buildings or structures.
Section 406.3, Private Garages and Carports is amended by adding the following subsection:
406.3.5 Electric vehicle (EV) receptacle outlets in private garages. In a minimum of 10% of
the attached private, enclosed garages and in a minimum of 10% of the detached private,
enclosed garages, associated with Group R-2 occupancy dwelling units, provide a minimum
of one EV-ready receptacle outlet in each garage, not more than 48 inches above and not less
than 18 inches above the floor. EV receptacle outlets serving accessible parking spaces shall
be installed in accordance with Section 1107 and ANSI A117.1. Each EV-ready receptacle
outlet installation shall include a junction box, conductors, raceway and a dedicated minimum
50-ampere, 240-volt circuit breaker. All components shall be installed in compliance with
the National Electrical Code.
Section 420.4 Automatic sprinkler system. Revise the first sentence to read:
Other than where preempted by Arizona State Law, Group R occupancies shall be equipped
throughout with an automatic sprinkler system in accordance Section 903.2.8 and Glendale
City Code Section 16-52.
8
Section 707.3.12 Electrical Rooms with Service Entrance Equipment is added and shall read as
follows:
Fire barrier walls and/ or fire-resistance-rated horizontal assemblies with a fire-resistance
rating of one hour shall be provided to separate an electrical room containing service entrance
equipment from adjacent rooms and spaces.
Section 708.3, Fire-resistance rating; the first paragraph is amended as follows:
Fire partitions shall have a fire-resistance rating of not less than 1 hour except when required
by Section 420.2 in a building that does not have an automatic sprinkler system in accordance
with Section 903.2.8. Where fire partitions are required by Section 420.2 and the building
does not have an automatic sprinkler system the fire-resistance rating shall be not less than
2 hours. Where the fire partitions have a required fire-resistance rating of more than 1 hour,
opening protectives shall be provided in accordance with Table 716.1(2) for fire barriers
having a fire- resistance rating greater than 1 hour.
(The Exceptions shall remain unchanged.)
Section 903.2, Automatic Sprinkler Systems is amended by replacing the first sentence with the
following:
Approved automatic sprinkler systems in new buildings and structures, and in existing
buildings and structures, that are modified, expanded, remodeled, renovated or change
occupancy classifications, shall be provided in accordance with the Glendale City Code,
Chapter 16, Article III. Where preempted by Arizona State Law, automatic fire sprinkler
systems shall not be required in newly constructed three-family dwellings (triplexes) and in
newly constructed four-family dwellings (fourplexes).
Section 1010.2.8.2, Rooms with Electrical Equipment is amended to read as follows:
Exit or exit access doors serving transformer vault, rooms designated for batteries or
energy storage systems, or modular data centers shall be equipped with panic hardware or
fire exit hardware. Exit or exit access doors serving rooms containing electrical equipment
rated 800 amperes or more that contain overcurrent devices, switching devices or control
devices shall be equipped with panic hardware or fire exit hardware. The doors shall swing
in the direction of exit travel.
Section 1028.3 Exit discharge width or capacity, add the following sentence:
The minimum width of an exterior sidewalk serving as a component of the exit discharge
shall be 60 inches (effective sidewalk width) or as determined by Section 1005.3, whichever
is greater. Effective sidewalk width is defined as the usable sidewalk area for pedestrian
travel, excluding obstructions such as building walls, trees, poles, or other elements that
might restrict pedestrian movement. Typically, 1 foot is subtracted from each side in which
one of these listed obstructions is present. Sidewalks adjacent to parking stalls shall be a
minimum of 72 inches wide or can be 60 inches wide if a landscape buffer is present.
9
Section 1101.1 Scope, revise to read as follows:
The provisions of this chapter and the Arizona Revised Statutes Section ARS 41-1492 shall
control the design and construction of facilities for accessibility for individuals with
disabilities.
Section 1102.1 Design, revise to read as follows:
Buildings and facilities shall be designed and constructed to be accessible in accordance
with this code and ICC A117.1-17 and in accordance with provisions State of Arizona
Attorney General Administrative Rules R10-3-401 through R-10-3-404 (2010 ADA
Standards for Accessible Design, referred to as “2010 Standards”, adopted by the U.S.
Department of Justice), whichever standard provides the greatest degree of accessibility.
Section 1104.1 Site arrival points, revise the first paragraph to read as follows:
All pedestrian routes within the site provided from public transportation stops, accessible
parking, accessible passenger loading zones, and public streets or public sidewalks to all
building entrances shall be accessible. The minimum width of sidewalks serving as
accessible routes shall be 60 inches (effective sidewalk width). Effective sidewalk width is
defined as the usable sidewalk area for pedestrian travel, excluding obstructions such as
building walls, trees, poles, or other elements that might restrict pedestrian movement.
Typically, 1 foot is subtracted from each side in which one of these listed obstructions is
present. Sidewalks adjacent to parking stalls shall be a minimum of 72 inches wide or can
be 60 inches wide if a landscape buffer is present.
Section 1109.2 Assembly area seating, revise the last sentence to read:
Dining areas shall comply with Section 1109.2.9 and Section 1110.14.
Section 1110.2 Toilet and bathing facilities. Amend Exception #3 by deleting the words “or
bathing rooms.” Revise to read as follows:
3. Where multiple single-user toilet rooms are clustered at a single location, at least 50
percent but not less than one room at each cluster shall be accessible.
Section 1607.1, Table 1607.1. Amend this table by revising item #27, Residential habitable attics
and sleeping areas uniform live load value to 40 psf.
Section 1609.4.3 Exposure Categories is amended by adding the following:
The City of Glendale is predominantly categorized as exposure category C. Deviating from
this shall require additional proof and verification from the registered design professional in
responsible charge. The engineer shall provide a surface roughness analysis, provide aerials,
etc. proving that the proposed site meets exposure category B as defined in ASCE 7-22,
Section 26.7.3.
Exception: Single story one- and two-family dwellings are permitted to use exposure category
10
B for wind design.
Section 1705.4 Masonry Construction is amended by deleting Exception 2.
Section 1806.1 Load Combinations is amended by adding the following:
In lieu of the presumptive load-bearing values of Table 1806.2, a geotechnical investigation
report is required for all new construction.
Section 1806.2 Presumptive Load- Bearing Values is amended by adding the following:
In lieu of the presumptive load-bearing values of Table 1806.2, a geotechnical investigation
report is required for all new construction.
Section 1809.4 Depth and width of footings is amended by revising the first sentence to read as
follows:
The minimum depth of footings below the undisturbed ground surface shall be 18 inches (458
mm), unless otherwise recommended by a geotechnical investigation report.
Table 2902.1 Minimum Number of Required Plumbing Fixtures is amended as follows. These
amendments also apply to Table 403.1 of the 2024 International Plumbing Code.
Revise footnote “e” to “50 or fewer.”
Add new footnote “g” to read as follows:
g.
24 inches (610 mm) of wash sink or 18 inches (457 mm) of a circular wash basin
shall be considered equivalent to one lavatory.
Section 2902.6, Small Occupancies (Minimum Plumbing Facilities) is amended by revising “15”
to “50.”
Sec. 9-18. - Amendments to the 2024 International Residential Code.
The International Residential Code, 2024 Edition is amended in the following respects:
Section R101.1 Title is amended to read as follows:
These provisions shall be known as the Residential Code for One-and Two-family
Dwellings of Glendale, Arizona, and shall be cited as such and will be referred to herein as
“this code.”
Chapter 1. Administration is amended by the deletion of Sections R102 through R114.
For the administration of this code, see the 2024 International Building Code and related
amendments.
Section R201.4, Terms Not Defined is amended by adding to the end of this subsection:
Mirriam-Webster's Unabridged Dictionary of the English Language shall be considered as
providing ordinarily accepted meanings.
11
Section R202, Definitions, FIRE SEPARATION DISTANCE, revise the last sentence to read as
follows:
The distance shall be measured at a right angle from the exterior face of the foundation.
Section R202, Definitions, GRAYWATER. Revise this definition to read as follows:
Wastewater that has been collected separately from a sewage flow and that originates from
a clothes washer or a bathroom tub, shower or sink, but that does not include wastewater
from a kitchen sink, dishwasher or toilet.
Section R301, Design Criteria is amended by adding this subsection:
R301.1.5 Lot Corner Identification. In construction applications where legally surveyed lot
corner identification markers are not readily verifiable or are missing, the building official,
when deemed necessary, shall require lot boundary markers to be surveyed and permanently
identified in accordance with State law at the owner’s or applicant’s expense. The survey
shall be executed by a registrant licensed to do such work by the Arizona State Board of
Technical Registration.
Table R301.2(1) is amended to read as follows:
GROUND
SNOW
LOAD
WIND DESIGN
SEISMIC
DESIGN
CATEGORY
SUBJECT TO DAMAGE FROM
WINTER
DESIGN
TEMP
ICE BARRIER
UNDERLAYM'T
REQUIRED
FLOOD
HAZARDS
AIR
FREEZ'G
INDEX
MEAN
ANNUAL
TEMP
Speed
(mph)
Topographic
effects
Weather'g
Frost
line
depth
Termite
N/A
115
mph
ultimate
89 mph
ASD
None
B
Negligible
N/A
Moderate
to Heavy
32oF
No
FEMA
N/A
72.6oF
Table R301.5 Minimum Uniformly Distributed Live Loads is amended with the following values:
Habitable attics and attics served with fixed stairs
40 psf
Sleeping areas
40 psf
Section R302.2, Townhouses is amended by adding this sentence:
No plumbing, mechanical, electrical, piping, or other services in any form are allowed to
traverse from one side to the other side of the wall or walls separating townhouse units.
Section R302.2.6, Townhouses, Structural independence is amended by deleting Exceptions 5
and 6.
Section R308.1 is deleted it its entirety and replaced with the following:
12
R308.1 Address Numbers. Property owners shall obtain and display on the residence, the
correct building number or numbers as assigned to such property(ies) by the Planning
Department or functional equivalent in accordance with established street assignment policy,
prior to final inspection and /or issuance of a certificate of occupancy. The address numbers
shall be of a durable material, permanently attached to the building and must be readily
distinguished and readable from the nearest paved public/common roadway fronting that
property. The size of the address numbers shall comply with the city’s adopted fire code and
its amendments.
Section R309.1 Townhouses automatic sprinkler systems. Revise this section to read as follows:
Other than where preempted by Arizona State Law, an automatic sprinkler system shall be
installed in townhouses.
Exception: An automatic sprinkler system shall not be required where additions or
alterations are made to existing townhouses that do not have an automatic sprinkler system
installed.
R309.1.1 Design and installation. Automatic sprinkler systems shall be designed and
installed in accordance with NFPA 13D.
Section R309.2 One- and two-family dwellings automatic sprinkler systems. In accordance with
A.R.S. § 9-807, delete this section in its entirety. In accordance with A.R.S. § 9-461, accessory
dwelling units shall not be required to have automatic sprinkler systems.
Section R310.2.2 Smoke Alarms. Alterations, repairs and additions; add the following to the list
of Exceptions:
3. Swimming pools.
4. Electrical panel replacements.
5. Covered patios and shade structures (porches or decks)
6. Detached garages or other detached accessory structures. This does not exempt
Accessory Dwelling Units.
7. Photovoltaic solar systems
Section R317.6, Electric vehicle (EV) charging receptacle outlets and systems. Amend this section
to read as follows:
In attached garages, provide a minimum of one EV-ready receptacle outlet, not more than 48
inches above and not less than 18 inches above the floor. This installation shall include a
junction box, conductors, raceway and a minimum 50-ampere, 240-volt circuit breaker
installed in the electrical service panel. Electric vehicle charging branch circuits shall be
installed in accordance with Section E3702.14. The EV-ready receptacle outlet shall be
provided in addition to the general use receptacle outlets required by Section 3901.9.
Exception. Garage additions and garage remodels.
13
Electric vehicle charging systems shall be installed in accordance with the National Electrical
Code. Electric vehicle charging equipment shall be listed and labeled in accordance with UL
2202. Electric vehicle supply equipment shall be listed and labeled in accordance with UL
2594.
Section R318.1, Means of Egress is amended by adding the following sentences:
The means of egress from dwelling units or sleeping rooms shall not lead through other
sleeping rooms, toilet rooms or bathrooms.
Section R319.4, Area Wells is amended by adding the following:
An area well shall not be located beneath an emergency escape and rescue opening. A
protective grate shall be provided over all area wells. The grate shall comply with Section
R319.4.4 and shall be designed for a minimum uniformly distributed live load of 40 pounds
per square foot.
Section R319.4.4 Bars, grilles, covers and screens is amended by adding the following sentence:
The dwelling shall be equipped with smoke alarms installed in accordance with Section
R310.
Section R325.8 Required heating is amended to read as follows:
R325.8 Required heating and cooling. Every dwelling unit shall be provided with a heating
system capable of maintaining a temperature of not less than 70oF; and a cooling system
capable of maintaining a temperature no greater than 82oF (if cooled by air conditioning) or
86oF (if cooled by evaporative cooling); at a point 3 feet (914 mm) above the floor and 2
feet (610 mm) from exterior walls in habitable rooms. The installation of one or more
portable space heaters or portable space coolers shall not be used to achieve compliance
with this code section.
Section R401.4, Soil Tests is amended by adding the following sentence:
A soils test and geotechnical evaluation report shall be required for all new buildings governed
by this code.
Section R403.1.3, Footing and Stem Wall Reinforcing is amended by adding Seismic Design
Categories B and C to all seismic design requirements listed in this section.
Section R403.1.3 is amended by adding the following subsection:
Section R403.1.3.7 Foundation Ties. When an addition is constructed, the new foundation
shall be tied to the existing foundation by installing two (2) No. 4 dowel bars, minimum 12
inches long. These shall be embedded a minimum of 6 inches into the existing footing.
Section R403.1.4 Minimum Depth is amended by revising 12 inches to 18 inches, unless otherwise
recommended by a geotechnical evaluation report.
Section R403.4.1 Crushed Stone Footings is deleted in its entirety.
14
Section R403.5 Crushed Stone Footings for Cast-In-Place Foundations is deleted in its entirety.
Section R502.9 is amended by adding the following subsection:
R502.9.1 Framing Connections. Framing details for bearing walls and posts shall be such that
all components are tied together with positive connections to transmit wind uplift forces from
the roof to the foundation. Nails loaded in withdrawal by such forces shall not be considered
as positive connections.
Approved metal framing anchors shall be provided at the top and bottom of every other stud
of a wood-frame bearing wall, except where structural panel sheathing is nailed directly to the
studs, top plate and bottom plate in accordance with Table R602.3(1).
Floor-to-floor connections shall have approved metal strap ties at a maximum of 48 inches on
center, except where justified by an engineered analysis that bears the seal of a registered
design professional.
Each truss, joist and rafter shall be connected to the top plate of the supporting wall with an
approved metal framing anchor. The framing anchor shall be of the type which connects to
both members of the double top plate. Beams shall be anchored to supporting walls and posts
with approved metal framing connectors.
Section R502.3.1 Sleeping areas and attic joists is amended to read as follows. Table R502.3.1(1)
is deleted:
Table R502.3.1(2) shall be used to determine the maximum allowable span of floor joists
that support sleeping areas and attics that are accessed by means of a fixed stairway in
accordance with Section R318.7 provided that the design live load does not exceed 40
pounds per square foot and the design dead load does not exceed 20 pounds per square foot.
The allowable span of ceiling joists that support attics used for limited storage or no storage
shall be determined in accordance with Section R802.5.
Section R602.10 Wall Bracing is amended by adding the following:
For buildings that are two or more stories in height, the empirical design provisions for wall
bracing in this section shall not be used. An engineered design shall be provided to include
both gravity and lateral load calculations. The project drawings and engineering
calculations shall bear the seal of a registered design professional.
Section R606.1.1, Professional Registration Not Required is revised to read as follows:
Masonry shall be designed in accordance with the requirements of this section and shall be
reinforced in accordance with Figure R606.11.3. Such masonry shall support only a roof
and shall be limited to 10 feet in height and shall not require an engineered design.
Masonry construction not meeting these limits shall require drawings and engineering
calculations bearing the seal of a registered design professional.
Section R606.12 Seismic requirements is revised to read as follows:
15
All new masonry elements shall meet the minimum reinforcing requirements of Sections
R606.12.2.2.3, R606.12.2.3.2 and R606.12.2.3.3. These requirements shall not apply to
glass unit masonry conforming to Section R607, anchored masonry veneer conforming to
Section R703.8 or adhered masonry veneer conforming to Section R703.12.
Section R608.1 General is amended by revising the last sentence to read:
Project drawings, details, calculations and specifications are required to bear the seal of a
registered design professional.
Section R610.1 General is amended by revising the last sentence to read:
Project drawings, details, calculations and specifications are required to bear the seal of a
registered design professional.
Section R802.8 Lateral Support is amended to read as follows:
Floor joists, rafters and ceiling joists shall be provided with lateral support at points of bearing
to prevent rotation. Where lateral support is provided by solid wood blocking, 1X nominal
lumber shall not be allowed.
Section R802.8.1 Bridging. The first sentence is revised to read as follows:
Floor joists, rafters and ceiling joists shall be supported by nominal 2 x solid blocking,
diagonal bridging (wood or metal) or a continuous 1-inch by 3-inch wood strip nailed across the
rafters or ceiling joists at intervals not exceeding 8 feet.
Section N1101.4, Above Code Programs, add the following subsection:
N1101.4.1 RESNET Testing & Inspection Protocol. The Residential Energy Services
Network (RESNET) Mortgage Industry National Home Energy Rating System Standards
(MINHERS) for third party testing and inspections shall be deemed to meet the
requirements of sections N1102.5.1, N1102.5.1.2 and N1103.3.7 and shall meet the
following conditions:
1. Third Party Testing & Inspections shall be completed by RESNET certified Raters or
Rating Field Inspectors and shall be subject to RESNET Quality Assurance Field Review
Procedures.
2. Sampling in accordance with Chapter 6 of the MINHERS Standards shall be
performed by Raters or Rating Field Inspectors Working under a RESNET Accredited
Sampling Provider.
3. Third Party Testing is required for the following items:
a. N1102.5.1– Building Envelope – Thermal Air Barrier Checklist
b. N1102.5.1.2 – Testing – Air Leakage Rate
c. N1103.3.7 – Sealing – Duct Tightness
d. Any other testing and inspections required under the code.
16
4. Alternate testing and inspection programs and protocols shall be allowed when
approved by the Building Official.
IRC Table N1102.5.1.1, Air Barrier, Air Sealing and Insulation Installation, revise the criteria for
“rim joists” as follows:
Delete the statement, “The junctions of the rim board to the sill plate and the rim board and
the subfloor shall be air sealed.”
Section N1104.2, Interior lighting controls. Delete this section in its entirety.
Section N1104.3, Exterior lighting controls. Delete this section in its entirety.
Section M1411.9, Condensate disposal, add the following:
Condensate drain piping shall not terminate over sidewalks, asphalt, concrete, walking
surfaces or similar surfaces. All condensate drain piping shall terminate in an approved
location as determined by the building official or his representative.
Section M1413 Evaporative Cooling Equipment, add the following subsection:
Section M1413.2 Water conservation. Evaporative cooling systems shall be provided with a
recirculating water system. Any bleed off rate used by the system shall be limited to that
recommended by the manufacturer. Once-through evaporative cooling systems using
potable water shall not be permitted.
Section P2903.2, delete and replace with the following text and table:
Section P2903.2 Maximum flow and water consumption. The maximum water consumption
flow rates and quantities for all plumbing fixtures and fixture fittings shall be in accordance
with Table P2903.2. Exception: Replacement of existing fixtures that do not require a
permit.
TABLE P2903.2 MAXIMUM FLOW RATES AND CONSUMPTION FOR PLUMBING FIXTURES AND FITTINGSb
Plumbing fixture or fixture fitting
Maximum flow rate or quantityb
Lavatory faucet
1.5 gpm at 60 psi
Shower heada,c
2.0 gpm at 80 psi
Sink faucet
1.8 gpm at 60 psi
Water closet
1.28 gallon per flushing cycled,e
For SI: 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa
17
a. A hand-held shower spray shall be considered a shower head.
b. Consumption tolerances shall be determined from referenced standards.
c. Shower heads shall comply with all requirements for high-efficiency shower heads in ASME
A112.18.1-2020/CSA B125.1
d. For a dual-flush water closet, the full-flush volume shall not exceed 1.28 gallons.
e. A 1.6 gallon per flushing cycle is permitted where a water closet is connected to an existing
building’s sanitary drainage piping.
Section P2904.1, Dwelling Unit Automatic Sprinkler Systems, General is revised to read as
follows; delete all remaining sections of P2904.
The design and installation of automatic sprinkler systems shall be in accordance with
NFPA 13D and the Glendale Municipal Code, Chapter 16, Article III. Partial automatic
sprinkler systems shall be permitted to be installed only in buildings not required to be
equipped with an automatic sprinkler system.
Section P2906.2, Lead Content is amended to read as follows: (Water Services)
The lead content in pipe and fittings used in the water supply system shall comply with
40 CFR 143.12(a) as “lead free” as follows:
1. Not contain more than 0.2 percent lead when used with respect to solder and flux;
and,
2. Not have more than a weighted average of 0.25 percent lead when used with
respect to the wetted surfaces of pipes, pipe fittings, plumbing fittings and
fixtures.
Section E3404.1 Applicability is amended by adding the following sentence:
“For electrical systems not covered by this Code, see the 2023 National Electrical Code.”
Section E3703.5, Garage branch circuits. This section is amended by adding the following
sentence:
In addition to the other branch circuits required by this section, provide a dedicated, minimum
50-ampere, 240-volt branch circuit to supply EV receptacle outlets required by Sections
R317.6 and E3901.9 in attached garages.
Section E3704, Feeder Requirements is amended by adding the following section:
E3704.7 Townhouses. Feeders supplying townhouse units shall not pass through or above
other townhouse units.
18
Sections E3901.4.2 and E3901.4.3 are amended; delete the text and replace with the following:
E3901.4.2 Island and peninsular countertops and work surfaces. At least one receptacle
shall be installed at each island and peninsular countertop space with a long dimension of
600 mm (24 in.) or greater and a short dimension of 300 mm (12 in.) or greater. A
peninsular countertop is measured from the connected perpendicular wall.
E3901.4.3 Receptacle outlet location. Receptacle outlets rendered not readily accessible by
appliances fastened in place, appliance garages, sinks, or range tops as covered in the
exception to Section E3901.4.1, or appliances occupying assigned spaces shall not be
considered as these required outlets. Required receptacle outlets shall be located in one or
more of the following:
1. On or above, but not more than 20 inches (508 mm) above, the countertop or
work surface.
2. In a countertop using receptacle outlet assemblies listed for the use in
countertops.
3. In a work surface using receptacle outlet assemblies listed for use in work
surfaces or listed for use in countertops. [210.52(C)(3)]
3901.4.2
Exception: To comply with the following conditions (1) and (2), receptacle outlets
shall be permitted to be mounted not more than 12 inches (300 mm) below the
countertop or work surface. Receptacles mounted below a countertop or work
surface in accordance with this exception shall not be located where the countertop
or work surface extends more than 6 inches (150 mm) beyond its support base.
1. Construction for the physically impaired
2. On island and peninsular countertops or work surfaces where the surface is flat
across its entire surface (no backsplashes, dividers, etc.) and there are no means to
mount a receptacle within 20 inches (500 mm) above the countertop or work
surface, such as an overhead cabinet
Section E3901.9, Basements, garages and accessory buildings. This section is amended by adding
the following sentence:
In attached garages, provide a minimum of one EV-ready receptacle outlet in accordance
with Section R317.6. All components shall be installed in compliance with the National
Electrical Code.
Section E3901.9, Basements, garages and accessory buildings is amended to read as follows:
Not less than one receptacle outlet, in addition to any provided for specific equipment, shall
be installed in each separate unfinished portion of a basement; in each vehicle bay at not less
than (18) inches (457 mm) and not more than 5.5 feet (1676 mm) above the floor in attached
garages; in each vehicle bay at not less than (18) inches (457 mm) and not more than 5.5 feet
(1676 mm) above the floor in detached garages that are provided with electric power and in
accessory buildings that are provided with electric power. [210.52(G)(1), (2), and (3)]
19
Section E3908.9, Types of equipment grounding conductors. Amend item #4 as follows:
4. Electrical metallic tubing with an additional equipment grounding conductor.
IRC Appendix BC: Accessory Dwelling Units is adopted and amended as follows:
APPENDIX BC: ACCESSORY DWELLING UNITS (ADU)
SECTION BC101
GENERAL
BC101.1 Scope.
Accessory dwelling units (ADUs) proposed for existing residential construction shall be in
accordance with this appendix and other applicable requirements in this code, and the
existing building together with the ADUs shall not exceed the scoping limitations of
Section R101.2.
BC101.1.1 Prohibited conditions.
An ADU shall not be permitted:
1. On the same lot or parcel as a two-family dwelling (duplex) or other multiple-family
dwellings.
BC101.2 Conditions.
ADUs shall be permitted without requiring a change of occupancy where in compliance
with all of the following:
1. An ADU shall be permitted within an existing single-family detached dwelling,
attached to a single-family dwelling, or in a detached structure that is within the
scope of the International Residential Code and in accordance with Arizona Statute
9-461.18.
2. No more than one attached ADU and one detached ADU shall be permitted per
single-family dwelling lot or parcel.
3. No more than one attached ADU and two detached ADUs shall be permitted if the
single-family dwelling lot is one acre or more, and only if at least one of the ADUs
is recorded as a restricted-affordable dwelling unit in accordance with the Glendale
Unified Development Code.
4. An ADU shall not have a separate address from the principal dwelling.
5. ADUs shall be ancillary or secondary to the primary dwelling and may be
constructed to equal the square footage of the primary single-family dwelling; but in
no case shall the ADU exceed 1,000 square feet.
20
6. An ADU shall be provided with a separate entrance from that serving the primary
dwelling unit from the exterior of the building.
7. The location of a detached ADU shall comply with Section R302.
8. An ADU shall be provided with adequate provisions for electricity, water supply
and sewage disposal.
SECTION BC102
DEFINITIONS
BC102.1 Definitions.
The following words and terms shall, for the purposes of this appendix, have the meanings
shown herein:
ACCESSORY DWELLING UNIT (ADU). An ancillary or secondary living unit to a
single-family detached dwelling unit. The ADU shall have a kitchenette or kitchen,
bathroom, and sleeping area, and is independently accessed from and located on the same
lot as a single-family detached unit, either within the same building as the single-family
dwelling or in a detached building.
SECTION BC103
ADU PLANNING
BC103.1 Design.
Except as modified by this section, building planning shall be in accordance with Chapter 3
and building structure shall comply with the International Residential Code.
BC103.2 Means of egress.
The path of egress travel from an ADU to a public way or to a yard or court that opens to a
public way shall be independent of, and not pass through, the primary dwelling unit.
BC103.3 Fire separation.
For ADUs adjoining the primary dwelling unit, the 1-hour fire-resistance-rated wall and
floor assembly provisions of Section R302.3 shall be required.
BC103.4 Fire sprinklers.
ADUs shall not be required to be provided with automatic fire sprinklers in accordance with
Arizona Statute 9-461.18.
SECTION BC104
UTILITIES
21
BC104.1 Heating, ventilation and air-conditioning systems.
An ADU shall be provided with:
1. A separate, dedicated heating and cooling system.
2. A separate HVAC thermostat.
BC104.2 Electrical systems.
An ADU shall be provided with:
1. A separate electric meter and a separate electric service and disconnecting means.
2. Ready access for the occupants to all overcurrent devices protecting the conductors
supplying the ADU.
BC104.3 Gas piping.
An ADU shall be provided with:
1. A separate gas meter and service.
2. Ready access for the occupants to shutoff valves serving the ADU.
BC104.4 Water service.
An ADU shall be provided with a separate city water meter and water service line.
BC104.5 Sewage disposal.
An ADU may share a sewer connection with the primary dwelling provided that the sewer
line is adequately sized. This shall be proven by calculations submitted with the
construction documents. Alternatively, an ADU may be provided with a separate building
sewer line and tap.
Sec. 9-19. – Amendments to the 2024 International Existing Building Code.
The 2024 International Existing Building Code is amended in the following respects:
Section 101.1 Title. Revise to read as follows:
These regulations shall be known as the Existing Building Code of the City of Glendale,
Arizona, hereinafter referred to as “this code.”
Chapter 1 is amended by the deletion of Sections R102 through R117.
For the administration of this code, see the 2024 International Building Code and related
amendments.
22
Section 306.7.12, Toilet Rooms is amended by adding the following:
As an alternative, in existing toilet rooms and bathing rooms, one fixture (water closet or
urinal) may be removed (where two or more fixtures exist) to create the required space for an
accessible water closet.
Section 1203.3 is amended by revising the title and the text to read as follows:
1203.3 Means of Egress and Emergency Escape and Rescue. Where, in the opinion of the
building official, there is sufficient width and height for a person to pass through the opening or traverse
the means of egress, existing window openings, door openings and corridor and stairway widths are
not required to meet the widths required by the International Building Code or this code. Where
approved by the building official, the front or main exit doors need not swing in the direction of the
path of exit travel, provided that other approved means of egress having sufficient capacity to serve
the total occupant load are provided.
Section 1204.6 is amended by revising the title and the text to read as follows:
1204.6 Means of Egress and Emergency Escape and Rescue. Existing window openings, door
openings, and corridor and stairway widths less than those that would be acceptable for nonhistoric
buildings under these provisions shall be approved, provided that, in the opinion of the building
official, there is sufficient width and height for a person to pass through the opening or traverse the
exit and that the capacity of the exit system is adequate for the occupant load, or where other
operational controls to limit occupancy are approved by the building official.
Section 1201 is amended by adding the following subsection:
1201.6 Energy efficiency. Exterior alterations to a historic building shall be exempt from
the provisions of the International Energy Conservation Code.
Sec. 9-20. Amendments to the International Mechanical Code
Section 101.1 Title. Revise to read as follows:
These regulations shall be known as the Mechanical Code of the City of Glendale, Arizona,
hereinafter referred to as “this code.”
Chapter 1 is amended by the deletion of Sections R102 through R115.
For the administration of this code, see the 2024 International Building Code and related
amendments.
Section 307.2.1 Condensate disposal is amended by adding the following:
Condensate drain piping shall not terminate over sidewalks, asphalt, concrete, walking
surfaces or similar surfaces. All condensate drain piping shall terminate in an approved
location as determined by the building official or his representative.
23
Section 408, Marijuana Related Occupancies, add this section:
408 Marijuana Related Occupancies
408.1 General. Any building used to cultivate, produce, infuse or dispense marijuana shall
be designed such that there shall be no emission of dust, fumes, vapors, or odors into the
environment from the premise. A ventilation system shall be designed to prevent the
distribution of odors to other occupied parts of the building or adjacent properties. Design of
the odor control system shall be based on accepted engineering practices. All equipment and
filter media shall be listed and labeled for the application. Exhaust systems used in odor
control systems shall meet the requirements of Section 501.
408.1.1 Exhaust outlets. The termination point for exhaust outlets shall be in
accordance with Section 501.3. Exhaust from cultivation and production facilities
shall be in accordance with Section 501.3.1(2) and for dispensaries in accordance with
Section 501.3.1(3).
Section 607.2 Installation is amended to read as follows:
Fire dampers, smoke dampers, combination fire/smoke dampers and ceiling radiation
dampers located within air distribution and smoke control systems shall be installed in
accordance with the manufacturer’s instructions, the dampers’ listing and Sections 607.2.1
through 607.2.3. Dampers shall be tested by an approved testing agency or a qualified third-
party special inspector. The special Inspector/testing agency shall be an independent third-
party individual or firm and shall not be the installing contractor. Special inspections shall
be as specified in Chapter 17 of the International Building Code.
Section 928, Evaporative Cooling Equipment, add the following subsection:
Section 928.2 Water conservation. Evaporative cooling systems shall be provided with a
recirculating water system. Any bleed off rate used by the system shall be limited to that
recommended by the manufacturer. Once-through evaporative cooling systems using
potable water shall not be permitted.
Section 932, add this new section to read as follows:
Section 932 Water-cooled refrigeration/ heat removal systems.
932.1 Water conservation. A water-cooled refrigeration system or heat removal system,
(defined as refrigeration or heat removal system using water, all, or in part, for condensing
a refrigerant), shall not discharge more than three gallons of water per nominal ton per hour
into an approved sanitary disposal system. Condenser wastewater discharge shall be
accomplished by the use of an air gap, as described in the International Plumbing Code.
Each water-cooled system shall be provided with one or more of the following water-saving
devices: (a) a cooling tower: or (b) an evaporative condenser; or (c) an approved water
circulating device.
24
Sec. 9-21. Amendments to the International Plumbing Code
Section 101.1 Title is amended to read as follows:
These regulations shall be known as the Plumbing Code of the City of Glendale,
Arizona hereinafter referred to as “this code.”
Chapter 1 is amended by the deletion of Sections R102 through R115.
For the administration of this code, see the 2024 International Building Code and related
amendments.
Section 301.6 Prohibited Locations, Exception is amended to read as follows:
Exception: Floor drains, sumps and sump pumps shall be permitted at the base of the
elevator shaft, provided they are daylighted to landscape or indirectly connected to the
plumbing system and comply with Section 1003.4.
Section 305.4.1 Sewer Depth is amended as follows:
Building sewers that connect to private sewage disposal systems shall be installed not less
than 12 inches below finished grade at the point of septic tank connection. Building
sewers shall be installed not less than 12 inches below grade.
Section 410.4 Substitution is amended by revising the last sentence to read:
In other occupancies where drinking fountains are required, water dispensers shall be
permitted to be substituted for drinking fountains.
Section 412, Faucets and Fixture Fittings, add the following subsection:
412.13 Automatic faucets. New or replacement faucets serving lavatories in all buildings
other than R3 occupancies, individual units in R2 occupancies, or International Residential
Code structures shall be provided with automatic faucets in accordance with Table 604.4.
Section 604.4, delete and replace with the following:
Section 604.4 Maximum flow and water consumption. The maximum water consumption
flow rates and quantities for all plumbing fixtures and fixture fittings shall be in accordance
with Table 604.4. Exception: Replacement of existing fixtures that do not require a permit.
25
TABLE 604.4 MAXIMUM FLOW RATES AND CONSUMPTION FOR PLUMBING FIXTURES AND FITTINGS
Plumbing Fixture or Fixture Fitting
Maximum Flow Rate or Quantityb
Lavatory, private
1.5 gpm at 60 psi
Lavatory, public
0.25 gallon per metering cycle
Lavatory, public (other than metering)
0.5 gpm at 60 psi
Shower heads a,c
2.0 gpm at 80 psi
Sink faucet
1.8 gpm at 60 psi
Flushing urinals
0.5 gallons per flush
Water closet
1.28 gallons per flush d,e
For SI: 1 gallon = 3.785 L, 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa
a. A hand-held shower spray is a shower head.
b. Consumption tolerances shall be determined from referenced standards.
c. Shower heads shall comply with all requirements for high-efficiency shower heads in ASME
A112.18.1-2020/CSA B125.1
d. For a dual-flush water closet, the full-flush volume shall not exceed 1.28 gallons.
e. A 1.6 gallon per flushing cycle is permitted where a water closet is connected to a building’s
existing sanitary drainage piping.
Section 605.2, Lead Content of Water Supply Pipe and Fittings is amended to read as follows:
The lead content in pipe and fittings used in the water supply system shall comply with
40 CFR 143.12(a) as “lead free” as follows:
1. Not contain more than 0.2 percent lead when used with respect to solder and flux;
and,
2. Not have more than a weighted average of 0.25 percent lead when used with
respect to the wetted surfaces of pipes, pipe fittings, plumbing fittings and
fixtures.
Chapter 7 is amended as follows:
Any reference in this chapter that refers to the International Private Sewage Disposal Code
shall be deferred to the Maricopa County Environmental Services Department.
Section 701.5 Damage to drainage system or public sewer is amended to reference Section 1003
in its entirety and any requirements in that section shall be deferred to the City of Glendale Water
Services Department.
Section 803 Special Wastes is hereby amended to defer to the City of Glendale Water Services
Department.
26
Section 903.1.1 Roof Extension is amended as follows:
This section allows the Authority Having Jurisdiction to determine the minimum height
above a roof that a vent must terminate. The City of Glendale shall require that all vents
terminate a minimum of 6 inches above the roof and not less than 12 inches from any
vertical surface.
Section 1003 Interceptors and Separators is amended by deferring to the requirements of the
City of Glendale Water Services Department where applicable.
Chapter 13 Non-Potable Water Systems is amended by deleting this chapter in its entirety.
These systems shall be designed and constructed in accordance with applicable Maricopa
County and State of Arizona regulations and requirements.
Sec. 9-22. Amendments to the 2023 National Electrical Code.
Article 90- Introduction
Section 90.1 (A) is amended to read as follows:
90.1 (a) Practical safeguarding. The purpose of this code is the practical safeguarding of
persons and property from hazards arising from the use of electricity. Any and all electrical
work for light, heat, power, or any other purposes shall be installed in conformity with the
rules and regulations as set forth in this code and that document titled, National Electrical
Code, 2023 edition, also known as NFPA 70, and in conformity with the rules, policies,
regulations and amendments as set forth by the building official. This Code is not intended
as a design specification or an instruction manual for untrained persons.
Section 90.2(C)(7) is added to read as follows:
Special Inspection. The City of Glendale requires Special Electrical Inspections for the
types of work specified below as amended by adding sections 90.2(C)(7) and 90.2(C)(8)
Special Electrical Inspections include, but are not limited to, testing or observation of the
work assigned for conformance with the approved design drawings and specifications,
and submission of appropriate inspection reports or certificates to the City of Glendale
Electrical Inspector.
The Special Electrical Inspector shall be a qualified person who demonstrates
competence to the satisfaction of the Building Official for the type of work requiring
Special Inspection. These individual(s) or firm(s) shall be responsible for performing the
Special Inspection tasks and reports required by the City of Glendale. The Special
Electrical Inspector(s) shall be an independent, third-party individual, firm or testing
agency and shall not be the installing contractor or any other person responsible for the
work.
Electrical Special Inspection:
27
1. Ground-fault protection performance tests for equipment provided or
required to have ground-fault protection.
2. Switchboard, panelboards, motor control center, and all other equipment
rated 1,000 amps or more; or over 600 volts. (over-potential test, also
known as a dielectric withstand test, and commonly referred to as a hi-pot
test.)
3. Emergency and standby power systems including: switchboards,
panelboards, distribution boards, transfer equipment, power source,
conductors, fire pumps, exhaust and ventilation fans.
4. Other special inspections as required by the building official.
Section 90.2(C)(8) is added to read as follows:
Electrical observation. Electrical observation by the ‘Registrant of Record’ shall be
provided for the following installations:
1. Installation or alteration of that portion of a health care facility electrical
system which fall within the scope of article 517, Part 3- “Essential
Electrical System” of the 2023 National Electrical Code.
2. Installations or alterations of high voltage electrical systems, which exceed
600 volts.
3. Installations or alterations of electrical systems within locations classified
as hazardous by the provisions of the 2023 National Electrical Code, or the
currently adopted International Fire Code, except for gasoline dispensing
installations and systems located within storage garages, repair garages or
lubritoriums.
The owner shall employ the Engineer responsible for the electrical design, or another
Engineer designated by the Engineer responsible for the electrical design to perform
visual observation of complex electrical equipment and systems for general conformance
to the approved plans and specifications, including but not limited to, placement and
interconnection of equipment. Electrical observation shall be performed at intermediate
significant stages of the construction progression and when installation is complete and
ready to be inspected by the Building Official. Certificates of Electrical Observation
shall be completed and sealed by the Engineer of Record for all life safety items as one of
the requirements prior to release of a temporary certificate of occupancy. All certificates
of Electrical Observation shall be completed and sealed prior to the project’s final
approval and the electrical portion of the certificate of occupancy is completed.
Article 100 Definitions
Article 100 is amended by revising the definition of the following items to read as follows:
Kitchens. Commercial and Institutional Kitchens and Bars. For the purposes of this
section, a kitchen or bar is defined as any area where food or beverage is prepared, served
28
or dispensed.
Article 210- Branch Circuits
Section 210.8(B)(2) is amended to read as follows:
(2) Kitchens: Commercial and Institutional Kitchens and bars. For the purposes of this
section, a kitchen or bar is defined as any area where food or beverage is prepared, served
or dispensed.
Sections 210.52(C)(2) and 210.53(C)(3) are amended; delete the text and replace with the
following:
210.52(C)(2) Island and peninsular countertops and work surfaces. At least one receptacle
shall be installed at each island and peninsular countertop space with a long dimension of
600 mm (24 in.) or greater and a short dimension of 300 mm (12 in.) or greater. A
peninsular countertop is measured from the connected perpendicular wall.
210.52(C)(3) Receptacle outlet location. Receptacle outlets shall be located in one or more
of the following:
1. On or above, but not more than 20 inches (508 mm) above, the countertop or
work surface.
2. In a countertop using receptacle outlet assemblies listed for the use in
countertops.
3. In a work surface using receptacle outlet assemblies listed for use in work
surfaces or listed for use in countertops.
Receptacle outlets rendered not readily accessible by appliances fastened in place,
appliance garages, sinks or range tops as covered in 210.52(C)(1), Exception No.1,
or appliances occupying assigned apces shall not be considered as these required
outlets.
Exception: To comply with the following conditions (1) and (2), receptacle outlets
shall be permitted to be mounted not more than 12 inches (300 mm) below the
countertop or work surface. Receptacles mounted below a countertop or work
surface in accordance with this exception shall not be located where the countertop
or work surface extends more than 6 inches (150 mm) beyond its support base.
1. Construction for the physically impaired
2. On island and peninsular countertops or work surfaces where the surface is flat
across its entire surface (no backsplashes, dividers, etc.) and there are no means to
mount a receptacle within 20 inches (500 mm) above the countertop or work
surface, such as an overhead cabinet
Informational Note No. 1: See 406.5(E) for installation of receptacles in countertops
and 406.5(F) for installation of receptacles in work surfaces. See 380.10 for
29
installation of multioutlet assemblies.
Informational Note No. 2: See Informative Annex J and ANSI/ICC A117.1-2009,
Standard on Accessible and Usable Buildings and Facilities, for additional
information.
Article 230 Services
Section 230.2 is amended by adding the following sentence to the end of the first paragraph:
No electrical service on one property shall supply power to another separate and distinct
property unless these properties are legally combined and under the same ownership.
Section 230.43 is amended to read as follows:
Section 230.43. Wiring methods for 600 volts, nominal, or less. Service-entrance conductors
shall be installed in accordance with the applicable requirements of this code covering the type
of wiring method used and shall be limited to the following methods:
1. Rigid metal conduit
2. Intermediate metal conduit
3. Wire ways
4. Bus ways
5. Auxiliary gutters
6. Rigid non-metallic conduit may be used underground
7. Schedule 80 rigid non- metallic conduit may extend above ground to the
service equipment.
(Informational note): Refer to the serving utility company’s requirements for additional
information on installing service-entrance conductors on or within buildings and underground
laterals serving the premises.
Article 250 Grounding and Bonding
Section 250.118, Types of equipment grounding conductors. Amend item #4 as follows:
4. Electrical metallic tubing with an additional equipment grounding conductor.
Article 300 Wiring Methods
Section 300.4(D) Exception 1 is amended to read as follows:
Exception 1: Steel plates, sleeves, or the equivalent shall not be required to
protect rigid metal conduit, intermediate metal conduit, or electrical metallic
tubing. Rigid nonmetallic conduit (PVC conduit) is required to be protected.
Section 310.12 is amended to read as follows:
30
310.12: 120/240-Volt, Single-Phase Dwelling Services and Feeders. For one-family
dwellings and the individual dwelling units of two-family and multifamily dwellings,
service and feeder conductors supplied by a single-phase, 120/240-volt system shall be
permitted to be sized in accordance with 310.12(A) through (D).
(A)
Services. For a service rated 100 amperes through 400 amperes, the service
conductors supplying the entire load associated with a one-family dwelling, or the service
conductors supplying the entire load associated with an individual dwelling unit in a two-
family or multifamily dwelling, shall be permitted to have an ampacity not less than 83
percent of the service rating. If no adjustment or correction factors are required, Table
310.12(A) shall be permitted to be applied.
(B)
Feeders. For a feeder rated 100 amperes through 400 amperes, the feeder
conductors supplying the entire load associated with a one-family dwelling, or the feeder
conductors supplying the entire load associated with an individual dwelling unit in a two-
family or multifamily dwelling, shall be permitted to have an ampacity not less than 83
percent of the feeder rating. If no adjustment or correction factors are required, Table
310.12(A) shall be permitted to be applied.
(C)
Feeder Ampacities. In no case shall a feeder for an individual dwelling unit be
required to have an ampacity greater than that specified in 310.12(A) or (B).
(D)
Grounded Conductors. Grounded conductors shall be permitted to be sized smaller
than the ungrounded conductors, if the requirements of 220.61 and 230.42 for service
conductors or the requirements of 215.2 and 220.61 for feeder conductors are met.
Where correction or adjustment factors are required by 310.15(B) or (C), they shall be
permitted to be applied to the ampacity associated with the temperature rating of the
conductor.
Informational Note No. 1: See 240.6(A) for standard ampere ratings for fuses and inverse
time circuit breakers.
Informational Note No. 2: See Informative Annex D, Example D7.
Section 334.10 is amended to read as follows:
334.10 Uses Permitted. Type NM and Type NMC cables shall be permitted to be used in
the following, except as prohibited in 334.12:
1. One- and two-family dwellings and their attached or detached garages, and their
storage buildings.
2. Multi-family dwelling units and their detached garages – permitted to be of Types III,
IV and V construction.
3. Cable trays in dwellings in accordance with 334.10(1) or in dwelling units, in
31
accordance with 334.10(2) where the cables are identified for the use.
Article 410 Luminaires, Lampholders, and Lamps
Section 410.36(B) is amended by adding a second paragraph to read as follows:
Intermediate or heavy-duty ceiling systems shall be used for the support of luminaires
(lighting fixtures). All light fixtures shall be positively attached to the suspended ceiling
system. The attachment device shall have a capacity of 100 percent of the lighting fixture
weight acting in any direction. Luminaires (fixtures) weighing less than 56 pounds and
track lighting shall have two 12 gauge wires attached at opposing corners of the
luminaire(s) (fixture) or track lighting strip to the structure above. These wires may be
slack, and shall contain, at a minimum, at least 3 tight twists within a 3-inch length of the
wire at each end. Recessed luminaire housings, exit signage, all single bulb fixtures and
emergency unit equipment that are installed within or on a suspended ceiling shall have a
minimum of at least one 12-gauge wire attached to the structure above and this wire may
be slack and shall contain, at a minimum, at least 3 tight twists of the wire within a 3-inch
length at each end. Luminaires weighing more than 50 pounds shall comply with NEC
314.27 (a)(2).
Sec. 9-23. Amendments to the 2024 International Property Maintenance Code
Section 101.1, Title is amended to read as follows:
These regulations shall be known as the Property Maintenance Code of Glendale, Arizona,
hereinafter referred to as “this code.”
Section 102.3, Application of other codes is amended by replacing International Zoning Code with
Glendale Unified Development Code in the last sentence.
Section 103.1, Creation of agency is amended to read as follows:
The Building Safety Division is hereby created and the official in charge thereof shall be
known as the building official. The Code Compliance Division is hereby created and the
official in charge thereof shall be known as the code compliance official. The function of
these agencies shall be the implementation, administration and enforcement of the
provisions of this code. When this code refers to the code official, it has the same meaning
as the building official and the code compliance official.
Section 105.2.2, Alternative materials, design and methods of construction and equipment is
amended by deleting the Exception.
Section 105.6 Official records is amended to read as follows:
The code official shall keep official records as required by Sections 105.6.1 through 105.6.5.
Such official records shall be retained in accordance with the regulations of the State of
32
Arizona and City Clerk’s Office.
Section 105.7, Liability is amended by replacing “member of the board of appeals” with “hearing
officer” in the first sentence.
Section 106 is deleted and replaced by the following:
106 - APPEALS RELATED TO UNSAFE BUILDINGS, STRUCTURES AND EQUIPMENT
106.1 Appeals. Decisions, orders and notices of violations relating to unsafe buildings,
structures or building service equipment may be appealed to the building official. The appeal
shall be filed within 30 calendar days from the date of the order or action of the building
official; provided however, that if the building or structure or building service equipment is
in such condition as to make it immediately dangerous to the life, limb, property, or safety of
the public or adjacent property and is ordered vacated and is posted in accordance with this
code, such appeal shall be filed within 20 calendar days from the date of service from the
building official in accordance with this code.
106.1.1 Processing, Scheduling and Noticing of Appeal. Upon receipt of any appeal filed
pursuant to this section, the building official shall schedule a hearing with a hearing
officer appointed by the city manager's office. As soon as practicable, the hearing officer
shall fix a date, time and place for the hearing of the appeal. Such date shall not be less
than 10 calendar days nor more than 60 calendar days from the date the appeal was filed
with the building official, unless the parties agree to another date. Written notice of the
time and place of the hearing shall be given at least 10 calendar days prior to the date of
the hearing to each appellant by either causing a copy of such notice to be delivered to
the appellant personally or by mailing a copy thereof, postage prepaid, addressed to the
appellant at the address shown on the appeal.
106.1.2 Failure to Appeal. Failure of any person to file an appeal in accordance with the
provisions of this code shall constitute a waiver of the right to an administrative hearing
and adjudication of the notice of violation or any portion thereof.
106.1.3 Scope of Hearing on Appeal. Only those matters or issues specifically raised by
the appellant shall be considered in the hearing of the appeal.
106.1.4 Staying of Notice of Violation. Except for vacation orders made pursuant to this
section, enforcement of any notice of violation issued under this code shall be stayed
during the pendency of an appeal therefrom which is properly and timely filed.
106.1.5 Failure to Abate.
(a)
If the unsafe building, structure or building service equipment is not repaired or
demolished as required by the notice provided for in Section 109, the building
official shall give written notice to the owner of the unsafe building, structure or
service equipment and other parties in interest, by certified mail or personal
service, to appear before a hearing officer at a designated time and place to show
cause why the unsafe conditions have not been repaired or demolished in
accordance with the statement of particulars set forth in the notice provided for
in Section 109. The city manager shall appoint a hearing officer who shall
33
conduct the hearing in accordance with this section.
(b) The hearing officer shall hear such testimony as the building official, owner and
other parties in interest may offer relevant to the condition of the unsafe building,
structure or building service equipment and the failure to repair or demolish the
same.
(c) The hearing officer shall make written findings of fact from the testimony
offered as to whether or not the building, structure or building service equipment
in question is an unsafe condition as defined in this section and whether good
cause exists for the failure to repair or demolish the unsafe condition.
(d) If the hearing officer finds the building, structure, or building service equipment
to be unsafe and if the owner of the unsafe building, structure or building service
equipment or other parties in interest fail to show good cause why the unsafe
building, structure or building service equipment should not be demolished
forthwith, the hearing officer shall authorize the building official to cause the
damaged building to be demolished. The costs of such demolition shall be
charged against the real property on which the unsafe building, structure or
building service equipment existed as an assessment. Such assessment shall be
recorded in the office of the county recorder and shall be a lien on such real
property from the date of its recording until paid. Such lien shall be subject and
inferior to a lien for general taxes and to all prior encumbrances of record.
(e) If the hearing officer finds the building, structure or building service equipment
to be unsafe and that good cause exists to grant the owner or other parties in
interest additional time to complete the repair or demolition of the damaged
building, structure, or building service equipment, the hearing officer shall order
that such repairs or demolition be completed with diligence and before a date
certain, provided that no extension of time longer than 270 calendar days shall be
granted to complete the repairs or demolition. If an extension of time to complete
repairs or demolition of the unsafe building, structure or building service
equipment is granted but the owner and other parties in interest do not complete
the repair or demolition of the unsafe conditions within the extension of time
granted, the building official, upon the expiration of the extension granted, shall
cause the unsafe building, structure or service equipment to be demolished
forthwith, no further extensions shall be allowed or granted. The costs of such
demolition are the responsibility of the property owner and are due 30 calendar
days after the final invoice is submitted. Where costs are not paid within 30
calendar days of issuance of the final invoice, the city shall place a lien upon the
property and charge interest at the annual rate of 10% until such time as the lien
is satisfied. Such assessment shall be recorded in the office of the county
recorder and shall be a lien on such real property from the date of its recording
until paid. Such lien shall be subject and inferior to a lien for general taxes.
(f)
Any determination by the hearing officer, including any additional extension in
time beyond that initially granted by the hearing officer may only be appealed to
Maricopa County Superior Court.
106.1.6 Notice by Publication.
34
If the whereabouts of any person entitled to notice under this section cannot be ascertained
by the city in the exercise of reasonable diligence, service of such notice may be made by
publishing the notice in a newspaper printed and published in the city for two (2)
consecutive weeks.
Section 109.1, Unsafe conditions is amended by replacing “condemned” with “unsafe to occupy.”
Section 109.1.5, item #5 is amended by deleting the words “or immoral persons.”
Section 109.2, Closing of vacant structures is amended by revising “placard of condemnation” to
“placard stating unsafe to occupy.”
Section 109.4.2, Method of service is amended by revising the first paragraph to read as follows:
Such notice shall be deemed to be properly served where a copy thereof is served in
accordance with one of the following methods. Service shall be deemed complete upon
delivery.
Section 109.7, Placarding is amended by revising placard bearing the word “Condemned” to
placard bearing the words:
DO NOT ENTER
UNSAFE TO OCCUPY
IT IS A CLASS I MISDEMEANOR TO OCCUPY THESE PREMISES
OR TO REMOVE OR DEFACE THIS NOTICE
In the last sentence, revise “condemned equipment” to “unsafe equipment.”
Section 109.7.1, Placard removal is amended by removing the word “condemnation” throughout
this subsection.
Section 109.8, Prohibited occupancy, revise the first sentence to read:
Any occupied structure declared unsafe to occupy and placarded by the code official shall
be vacated as ordered by the code official.
Section 110.5 shall be amended to read as follows:
Section 110.5 Costs of emergency repairs and securing the property. All costs incurred in
the performance of emergency work; securing a home, business and/or property shall be
paid by the legal property owner. The legal counsel of the jurisdiction shall institute
appropriate action against the owner of the premises or owner’s authorized agent where the
unsafe structure or equipment is or was located for the recovery of any costs imposed on the
jurisdiction.
Section 110.6, Hearing is amended by revising “appeals board” to “building official.”
Section 111.1, Demolition, General, item #1, revise “2 years” to “1 year.”
35
Section 202, General definitions; delete the definition of “Condemn.”
Section 303.2, Swimming Pools, Enclosures is amended by deferring these requirements to the
adopted 2024 International Swimming Pool and Spa Code and related amendments.
Section 304.3, Premises Identification is amended by revising the last sentence to read as follows:
The size of the address numbers shall comply with the city’s adopted fire code and its
amendments.
Section 602.3, Heating and Cooling Supply is amended to read as follows:
Every owner and operator of any building who rents, leases or lets one or more dwelling
units or sleeping units or indoor occupiable work spaces shall supply heating and cooling to
the occupants thereof. These dwelling units, sleeping units and indoor occupiable work
spaces shall be provided with a heating system capable of maintaining a temperature of not
less than 70oF; and a cooling system capable of maintaining a temperature no greater than
82oF (if cooled by air conditioning) or 86oF (if cooled by evaporative cooling); at a point 3
feet (914 mm) above the floor and 2 feet (610 mm) from exterior walls in habitable rooms.
The installation of one or more portable space heaters or portable space coolers shall not be
used to achieve compliance with this code section.
Section 602.4 is deleted in its entirety.
Sec. 9-24. Amendments to the 2024 International Energy Conservation Code.
Section C101.1 Title is amended to read as follows:
This code shall be known as the Energy Conservation Code of the City of Glendale,
Arizona, hereinafter referred to as “this code.”
Section C202, General Definitions, RESIDENTIAL BUILDING is amended to allow the
residential provisions of this energy code to apply to residential occupancies R-2, R-3 and R-4
of four or more stories in height. In accordance with A.R.S. 9-462, triplexes and fourplexes
are allowed to comply with the residential provisions of this energy code. As an option, these
R-2, R-3 and R-4 occupancies may be constructed to comply with the commercial provisions
of this energy code.
Section C408.2.1 is amended by adding the following sentence:
The provision of a commissioning plan shall be optional.
Section C404.5.1, Maximum allowable pipe length method, revise item 1 to read as follows:
1. For a public lavatory faucet, the maximum allowable piping length from the nearest
source of heated water supply pipe to the termination of the fixture supply pipe shall be
10 feet.
36
Section C405.15, Renewable energy systems. This section is deleted in its entirety. The
corresponding requirements in ASHRAE 90.1, Section 10.5.1 are deleted.
Section R101.1 Title is amended to read as follows:
This code shall be known as the Energy Conservation Code of the City of Glendale,
Arizona, hereinafter referred to as “this code.”
Section R104.1.1, Above Code Programs, add the following subsection:
R104.1.1.1 RESNET Testing & Inspection Protocol. The Residential Energy Services
Network (RESNET) Mortgage Industry National Home Energy Rating System Standards
(MINHERS) for third party testing and inspections shall be deemed to meet the
requirements of sections R402.5.1, R402.5.1.2 and R403.3.7 and shall meet the following
conditions:
1. Third Party Testing & Inspections shall be completed by RESNET certified Raters or
Rating Field Inspectors and shall be subject to RESNET Quality Assurance Field Review
Procedures.
2. Sampling in accordance with Chapter 6 of the MINHERS Standards shall be
performed by Raters or Rating Field Inspectors Working under a RESNET Accredited
Sampling Provider.
3. Third Party Testing is required for the following items:
a. R402.5.1– Building Envelope – Thermal Air Barrier Checklist
b. R402.5.1.2 – Testing – Air Leakage Rate
c. R403.3.7 – Sealing – Duct Tightness
d. Any other testing and inspections required under the code.
4. Alternate testing and inspection programs and protocols shall be allowed when
approved by the Building Official.
Section R202, General Definitions, RESIDENTIAL BUILDING is amended to allow the
residential provisions of this energy code to apply to residential occupancies R-2, R-3 and R-4
of four or more stories in height. In accordance with A.R.S. 9-462, triplexes and fourplexes are
allowed to comply with the residential provisions of this energy code. Also, as an option, these
R-2, R-3 and R-4 occupancies may be constructed to comply with the commercial provisions of
this energy code.
Section R404.2, Interior lighting controls. Delete this section in its entirety.
Section R404.3, Exterior lighting controls. Delete this section in its entirety.
Sec. 9-25. Amendments to the 2024 International Swimming Pool and Spa Code
37
The International Swimming Pool and Spa Code, 2024 Edition, is amended in the following
respects:
Section 101.1 is amended to read as follows:
101.1 Title. These regulations shall be known as the Swimming Pool and Spa Code of
Glendale, Arizona, hereinafter referred to as “this code.”
Chapter 1, Scope and Administration is amended by the deletion of Sections 102 through 114. For
administration of this code, see the 2024 International Building Code and related amendments.
ISPSC Section 202, Definitions: RESIDENTIAL SWIMMING POOL (Residential Pool). Revise
this definition as follows:
A pool intended for use that is accessory to a residential dwelling and available only to the
household and its guest including any structure intended for swimming, dipping or
immersion purposes with a minimum water depth of 18 inches (457.2 mm). This includes
in-ground, above-ground and on-ground swimming pools, hot tubs, spas and fixed-in-place
wading pools. All other pools shall be considered public pools for purposes of this code.
ISPSC Section 305.1, Barrier requirements, General. Add the following text:
It is the responsibility of the property owner and any other person in responsible charge of a
swimming pool to ensure that the required swimming pool barrier, including all gates,
doors, locks, latches, and other portions of the barrier are maintained safe and in good
working order at all times. No person shall alter or remove any portion of a swimming pool
barrier except to repair, reconstruct, or replace the barrier in compliance with provisions of
this section. All barriers shall be installed, inspected and approved prior to plastering or
filling with water.
ISPSC Section 305.2.1, Barrier height and clearances. Revise item #1 to read as follows:
1. The top of the barrier shall be not less than 60 inches (1524 mm) above grade where
measured in the side of the barrier that faces away from the pool or spa. Such height
shall exist around the entire perimeter of the barrier and for a distance of 3 feet (914
mm) measured horizontally from the outside of the required barrier. A dwelling or
accessory building may be used as part of such barrier.
ISPSC Section 305.2.1, Barrier height and clearances. Add the following item:
5. The barrier shall be at least 20 inches from the water’s edge.
ISPSC Section 305.2.5, Mesh fence as a barrier. Delete the text and replace with the following:
Mesh fences, other than chain link fences in accordance with Section 305.2.8, shall be
installed in accordance with the manufacturer’s instructions and shall comply with ASTM
38
F2286 and with all of the following:
1. The bottom of the mesh fence shall be not more than 1 inch above the deck or
installed surface or grade.
2. The maximum vertical clearance from the bottom of the mesh fence and
the solid surface shall not permit the fence to be lifted more than 4 inches
from grade or decking.
3. The fence shall be designed and constructed so that it does not allow
passage of a 4-inch sphere under any mesh panel. The maximum vertical
clearance from the bottom of the mesh fence and the solid surface shall
be not greater than 4 inches from grade or decking.
4. An attachment device shall attach each barrier section at a height not lower
than 45 inches above grade. Common attachment devices include, but are
not limited to, devices that provide the security equal to or greater than
that of a hook-and-eye-type latch incorporating a spring-actuated
retaining lever such as a safety gate hook.
5. Where a hinged gate is used with a mesh fence, the gate shall be equipped
to accommodate a locking device. Pedestrian access gates shall open
outward away from the pool or spa, shall be self-closing and shall have a
self- latching device.
6. Patio deck sleeves such as vertical post receptacles that are placed inside
the patio surface shall be of a nonconductive material.
ISPSC Section 305.2.8, Chain link dimensions. Revise to read as follows:
The maximum opening formed by a chain link fence shall be not more than 1 ¾ inches (44
mm). Where the fence is provided with slats fastened at the top and bottom that reduce the
openings, such openings shall be not greater than 1 ¾ inches (44 mm). The chain link mesh
shall be minimum 11 wire gauge.
ISPSC Section 305.3.2, Double or multiple gates. Revise to read as follows:
If a set of double gates or multiple gates is the only access to the yard area where the
swimming pool is located, they shall have not fewer than one leaf secured in place and the
adjacent leaf shall be self-closing and be secured with a self-latching device. The gate and
barrier shall not have openings larger than 1/2 inch (12.7 mm) within 18 inches (457 mm)
of the latch release mechanism. The self-latching mechanism shall comply with the
requirements of Section 305.3.3.
If a pedestrian gate is present in conjunction with the double or multiple gates, the double or
multiple gates need not be self-closing or self-latching and shall be equipped with a padlock
or similar locking device. Where the release mechanism of the latching device is located
less than 54 inches (1372 mm) from the bottom of the gate, the release mechanism shall
comply with the following:
1. The release mechanism shall be located on the pool side of the gate at least 3 inches
(76 mm) below the top of the gate, and
39
2. The gate and barrier shall have no opening greater than 1/2 inch (12.7 mm) within
18 inches (457 mm) of the release mechanism.
ISPSC Section 305.4, delete this section and replace with the following:
305.4 Secondary protection.
1. Application. The provisions of this section shall apply to swimming pools, spas,
hot tubs or other contained bodies of water (above or below ground) when a
residence, living area, accessory dwelling unit or accessory building, in which a
child younger than six (6) years of age will or does reside, constitutes part of the
barrier or enclosure required by Section 305.2:
a. Such swimming pool, spa, hot tub or other contained body of
water is constructed or installed on or after the effective date of
this ordinance at a single family residence; or
b. An existing swimming pool or other body of water lawfully
constructed prior to the effective date of this ordinance, but which
does not conform to these regulations, shall become subject to these
regulations as a result of any alteration, addition, or expansion of a
dwelling unit, accessory dwelling unit or guest room having access
to such pool, that increases the livable area; or
c. The existing single family residence is sold.
2. Requirements for secondary protection. When an event described in paragraph (1)
above occurs, one of the following methods of secondary protection shall be
provided:
a. Between the swimming pool or other contained body of water and
the residence or living area, a minimum five (5) foot high wall,
fence or barrier to the pool area which meets all of the
requirements of Sections 305.2 and 305.3; or
b. The pool shall be protected by a motorized safety pool cover in
compliance with ASTM F1346 which requires the operation of a
key switch and which does not require manual operation other than
the use of the key switch. The key switch shall be located not less
than 54 inches (1372 mm) above the floor or adjacent ground level
and where the entire pool cover can be visually inspected; or
c. All ground level doors or other doors with direct access to the area
containing a swimming pool or other contained body of water shall
be equipped with either: (1) a self-closing and self-latching device
with the latch located at least 54 inches above the finished floor; or
(2) an alarm placed not less than 54 inches above the finished floor
which activates automatically whenever the door is opened. The
alarm shall sound continuously for a minimum of 30 seconds
beginning within the first 7 seconds after the door and its screen, if
present, are opened and be capable of providing a sound pressure
40
level of not less than 85 dBA when measured at 10 feet in any
direction. The sound of the alarm shall be distinctive from other
household sounds such as smoke detectors, telephones, and
doorbells. The alarm system may be equipped with a manual
means to temporarily deactivate the alarm for a single opening.
Such deactivation shall last no longer than 15 seconds. An “off”
switch is not acceptable. The deactivation switch shall be located
at least 54 inches above the finished floor.
Sliding doors shall not form any part of a required barrier
unless equipped with a self-closing and self-latching mechanism.
Multi-panel sliding doors or walls shall meet the requirements of
this section, or shall be secured in place by a permanent fastening
method that requires a tool to remove.
Emergency escape or rescue windows from sleeping rooms
with access to the swimming pool or other contained body of water
shall be equipped with a latching device not less than 54 inches
above the floor. All other openable dwelling unit or guest room
windows with similar access shall be equipped with a screwed-in-
place wire mesh screen or a latching device located not less than
54 inches above the floor; or
d. An alarm maintained in or on the swimming pool or other body of
water. The alarm shall be installed so as to activate automatically
whenever a person enters the swimming pool or body of water and
remain activated until manually turned off. The alarm shall sound
continuously within the first 7 seconds after a person enters the
swimming pool or body of water and be capable of providing a
sound pressure level of not less than 85 dBA when measured at 10
feet in any direction. The sound of the alarm shall be distinctive
from other household sounds such as smoke detectors, telephones,
and doorbells; or
e. The swimming pool shall be an above-ground swimming pool
which has non-climbable exterior sides which are a minimum
height of 4 feet. Any access ladder or steps shall be removable
without tools and secured in an inaccessible position with a
latching device not less than 54 inches above the ground when the
pool is not in use; or
f. Latching or locking hard safety cover which may be latched or
locked shall be deemed to meet all barrier requirements of this
section for any spa or hot tub which is not more than 8 feet in
width, length or diameter; or
g. Alternative protection not specified herein and providing
protection meeting the intent of these requirements is allowed
when approved by the building official.
3. Compliance.
a. All plans submitted to the city for swimming pools to be
constructed or installed after the effective date of this section shall
41
specify the manner in which compliance with secondary protection
shall be accomplished. Submission of plans shall constitute
verification by the contractor and owner of compliance with this
section and the manner of compliance.
b. If an existing single family residence containing a swimming pool
or other body of water is sold after the effective date of this
ordinance, and secondary protection is required by this section, the
buyer shall comply with the provisions of this section no later than
30 days after the date the buyer takes occupancy of the residence.
4. Maintenance. Secondary protection required by this section shall be maintained in
proper operating order by the owner or occupant.
ISPSC Section 305. Add the following section:
305.9 Exemptions. The requirements of Section 305 do not apply to the
following:
a. A system of sumps, irrigation canals, irrigation flood control or drainage
works constructed or operated for the purpose of storing, delivering,
distributing or conveying water.
b. Stock ponds, storage tanks, livestock operations, livestock watering troughs
or other structures used in normal agricultural practices.
c. Lakes or decorative ponds.
ISPSC Section 307.2.2 Materials and Structural Design, Exception is revised to read as
follows:
Exception: Pools and spas constructed with reinforced concrete or reinforced
shotcrete with a minimum compressive strength of 2,500 pounds per square
inch when designed by a registered design professional and approved by the
building official shall be permitted.
ISPSC Section 411.1.4, Public Swimming Pools, Entry and Exit. Revise to read as follows:
Swimming pools greater than 20 feet wide in width shall be provided with entries and exits
on each side of the deep area of the pool. The entries and exits on the sides of the deep area
of a pool shall be located not more than 82 feet apart.
Sec. 9-26. Amendments to the International Green Construction Code
IgCC Section 101.1 Title. Amend the text as follows:
These regulations shall be known as the Green Construction Code of Glendale, Arizona,
hereinafter referred to as “this code.”
IgCC Table 101.5.1 Requirements Determined by the Jurisdiction, is amended as follows:
42
All of the code sections listed in the Table are adopted as “optional” requirements.
Compliance with the 2024 International Green Construction Code is voluntary as
determined by the design professional.
IgCC Chapter 1, Administration is amended by the deletion of Sections 102 through 110. For
administration of this code, see the 2024 International Building Code and related amendments.
Secs. 9-27 – 9-30. Reserved.
SECTION 2. That the Glendale City Code Chapter 9, Article III is deleted in its entirety and a new
Article III is adopted and shall read as follows:
ARTICLE III. WATER CONSERVATION PLUMBING REQUIREMENTS
Sec. 9-31. Purpose.
This article establishes maximum rates of water flow or discharge for plumbing fixtures and
devices in order to promote water conservation.
Sec. 9-32. Certification.
The plumbing fixtures and devices required to be installed pursuant to this article shall be
certified by the International Association of Plumbing and Mechanical Officials and comply with
all applicable American-National Standards Institute standards.
Sec. 9-33. Definitions.
In this article, unless the context otherwise requires:
Commercial, industrial and public construction: Buildings used for commercial, industrial or
public purposes, including restaurants, bars, nightclubs, public buildings, comfort stations, schools,
gymnasia, factories, offices, athletic clubs, hotels and motels.
Director: The building safety director or his designee.
Person: An individual, public or private corporation, company, partnership, firm, association,
society, estate or trust, any other private organization or enterprise, the United States, any state,
territory or country or a governmental entity, political subdivision or municipal corporation
organized under or subject to the constitution and laws of this state.
Plumbing fixture: A lavatory faucet, lavatory faucet replacement aerator, kitchen faucet,
kitchen faucet replacement aerator, shower head, urinal, water closet, evaporative cooler or
decorative fountain. "Plumbing fixture" does not include parts necessary for routine maintenance.
PSI: Pounds per square inch of water pressure.
43
Residential construction or residential dwelling: Buildings used for temporary or permanent
human habitation, including single-family residences and accessory guest houses, multifamily
dwellings, townhouses, condominiums, apartments, the sleeping quarters of hotels and motels,
dormitories and group housing units.
Urinal: A fixture that consists of a water flushed bowl, and any associated flush valve, and
that is used for the disposal of human urine.
Water closet: A fixture that consists of a water flushed bowl, and any associated flush valve,
and that is used for the disposal of all wastes from the human body.
Sec. 9-34. Prohibited plumbing fixtures; residential construction.
Except as provided in Arizona Revised Statutes Sections 45-315 and 45-319, on the effective
date of this ordinance, no person may install any plumbing fixture for use in this city in any new
residential construction or for replacing plumbing fixtures in existing residential construction,
unless the fixtures meet the following water-saving performance standards:
(1) Lavatory faucets and replacement aerators shall be designed to deliver no more than one
and one-half (1.5) gallons of water per minute at a pressure of sixty (60) psi or shall be
equipped with permanent flow control devices that allow delivery of no more than one
and one-half (1.5) gallons of water per minute at a pressure of sixty (60) psi.
(2) Kitchen faucets and replacement aerators shall be designated to deliver no more than one
and eight tenths (1-8/10) gallons of water per minute at a pressure of sixty (60) psi or
shall be equipped with permanent flow control devices that allow delivery of no more
than average of one and eight tenths (1-8/10) gallons of water per minute at a pressure of
sixty (60) psi.
(3) Shower heads shall be designed to deliver no more than two (2) gallons of water per
minute at a pressure of eighty (80) psi.
(4) Water closets shall be designed to use no more than one and twenty-eight hundredths
(1.28) gallons of water per flush.
(5) Urinals shall be designed to use no more than one-half (0.5) gallon of water per flush. No
urinals may be installed that use a timing device to flush periodically regardless of
demand.
(6) Evaporative cooling systems and decorative fountains shall be equipped with water
recycling or reuse systems.
Sec. 9-35. Prohibited plumbing fixtures; commercial, industrial and public construction.
Except as provided in Arizona Revised Statutes Sections 45-315 and 45-319, beginning on the
effective date of this ordinance, no person may install any plumbing fixtures for use in this city in
any new commercial, industrial or public construction or for replacing plumbing fixtures in
existing commercial, industrial or public construction, unless the fixtures meet the following water-
saving performance standards:
(1) Lavatory faucets shall be equipped with a mechanism that causes the faucet to close
automatically after delivering no more than one (1) quart of water.
44
(2) Shower heads shall be designed to deliver no more than two (2) gallons of water per
minute at a pressure of eighty (80) psi.
(3) Water closets shall be designed to use no more than one and twenty-eight hundredths
(1.28) gallons of water per flush.
(4) Urinals shall be designed to use no more than one-half (0.5) gallon of water per flush. No
urinals may be installed that use a timing device to flush periodically regardless of
demand.
(5) Evaporative cooling systems and decorative fountains shall be equipped with water
recycling or reuse systems.
Sec. 9-36. Violation; civil penalties.
(a)
A person who knowingly violates any provision of this article is subject to a civil
penalty of not more than one hundred dollars ($100.00) for the first violation. A person
who has previously been found in violation of any provision of this article is subject to a
civil penalty of not more than two hundred fifty-dollars ($250.00) for a second or any
subsequent violation. The installation in this city of each plumbing fixture that fails to
comply with the standards prescribed by this article constitutes a separate violation.
Tampering with a fixture that was originally designed to comply with the standards
prescribed by this article constitutes a violation. If a violation involves installing a
fixture that does not comply with the standards prescribed by this article, the person
who acquired the building or plumbing permit or the person who installed the fixture, or
both, are subject to the penalties specified in this section.
(b)
The city may bring an action to recover penalties under this section in superior court in
the county in which the violation occurred, after a hearing conducted pursuant to Sec. 9-
37.
(c)
This section does not apply to the owner or occupant of a residential dwelling who
violates this article in connection with the installation of a plumbing fixture in a
residential dwelling occupied by the owner or occupant.
Sec. 9-37. Inspections.
The director or the director's authorized representative shall, during normal business hours,
have access to unoccupied new residential construction for the purpose of making periodic
inspections to determine compliance with this article. New residential construction shall only be
inspected prior to issuance of the certificate of occupancy or upon final electrical inspection.
Inspections pursuant to this section shall be on reasonable notice to the owner or occupant of the
premises to be inspected unless reasonable grounds exist to believe that such notice would frustrate
the enforcement of this article. The director may, and if required by law shall, apply for and obtain
warrants for entry and inspection to carry out the administration and enforcement purposes of this
article.
Sec. 9-38. Cease and desist order; hearing; injunctive relief.
(a) If the director has reason to believe that a person is violating or has violated this article, the
director may give the person written notice by certified mail that the person may appear and
show cause at a hearing to be held at least thirty (30) days from the date of mailing the notice
why the person should not be ordered to cease and desist from the violation. The notice shall
45
inform the person of the date, time and place of the hearing and the consequences of failure to
appear.
(b) After a hearing pursuant to subsection (a) of this section, or after the expiration of the time to
appear, the director shall issue a decision and order. The decision and order may take such
form as the director determines to be reasonable and appropriate and may include a
determination of violation, a cease and desist order, a recommendation of a civil penalty and
an order directing that positive steps be taken to abate or ameliorate any harm or damage
arising from the violation. The person affected may appeal the decision to superior court in the
county in which the violation is alleged to have occurred.
(c) If the person continues the violation after the director or local official has issued a final
decision and order pursuant to subsection (b) of this section, the city may apply for a
temporary restraining order or preliminary or permanent injunction from the superior court
according to the Arizona Rules of Civil Procedure. A decision to seek injunctive relief does
not preclude other forms of relief or enforcement against the violator.
SECTION 3. That the provisions of this ordinance shall become effective thirty (30) days after
passage by the Glendale City Council.
PASSED, ADOPTED AND APPROVED by the Mayor and Council of the City of
Glendale, Maricopa County, Arizona this
day of
, 2025.
MAYOR
ATTEST:
City Clerk
(SEAL)
APPROVED AS TO FORM:
City Attorney
REVIEWED BY:
City Manager