TEMPE CONSTRUCTION CODE - EXHIBIT A.DOCX

City of Tempe — Regular City Council Meeting (2026-05-14)

View PDF Meeting page

Extracted text (via pymupdf) 162921 characters
Page 1 of 144
THE CITY OF TEMPE
CONSTRUCTION CODE

Page 2 of 144
Table of Contents
IBC
INTERNATIONAL BUILDING CODE AMENDMENTS
3
IRC
INTERNATIONAL RESIDENTIAL CODE AMENDMENTS
39
IEBC
INTERNATIONAL EXISTING BUILDING CODE AMENDMENTS
72
IECC
INTERNATIONAL ENERGY CONSERVATION CODE AMENDMENTS
88
IFGC
INTERNATIONAL FUEL GAS CODE AMENDMENTS
98
IGCC
INTERNATIONAL GREEN CONSTRUCTION CODE AMENDMENTS
102
IMC
INTERNATIONAL MECHANICAL CODE AMENDMENTS
105
IPC
INTERNATIONAL PLUMBING CODE AMENDMENTS
124
ISPSC 
INTERNATIONAL SWIMMING POOL & SPA CODE AMENDMENTS
143
NEC
NATIONAL ELECTRICAL CODE AMENDMENTS
152
IFC
INTERNATIONAL FIRE CODE AMENDMENTS
162
TAC
TEMPE ADMINISTRATIVE CODE
189

Page 3 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendments to 2024 International Building Code (IBC)
Article II, Section 8-200
Submitted by:
Building Safety Code Committee
Sec. 8-200. Adopted; where filed; amendments.
That certain document known as “The International Building Code, 2024 Edition,” which has been published as a 
code in book form by the International Code Council (ICC), chapters one through thirty-five and appendix 
chapters I, J and N inclusive, three (3) copies with amendments of which are on file in the office of the City 
Clerk, and this same code, appendices and amendments are hereby referred to, adopted and made a part hereof, as 
if fully set forth in this article.
(Ord. No. 2008.72, 12-11-08; Ord. No. O2015.12, 4-2-15)
Charter reference – Adoption by reference. §2.14.
State law reference - Adoption by reference. A.R.S. §9-801 et. seq.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 4 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 Internation Building Code (IBC)
Chapter 1
Submitted by:
Building Safety Code Committee
Chapter 1 Scope and Administration
Notes:
1.
For reserved sections herein, refer to the City of Tempe Administrative Code for these code requirements.
2.
Any conflicts between this code and the Tempe Administrative Code, the Tempe Administrative Code shall apply.
101.1 Title.  These regulations shall be known as the International Building Code Building Code of [NAME OF 
JURISDICTION], hereinafter referred to as “this code.” These regulations are one document of the overall City of Tempe 
Construction Code as defined by the adopting ordinance.
101.2 Scope. - Reserved
101.3 Purpose. – Reserved
101.4 Referenced Codes - Reserved
102 Applicability. - Reserved
Section 103 (IBC) Code Compliance Agency - Reserved
Section 104 (IBC) Duties and powers of the Building Official - Reserved
Section 105 (IBC) Permits - Reserved
Section 106 (IBC) Floor and Roof Design Loads - Reserved
Section 107 (IBC) Construction Documents - Reserved
Section 108 (IBC) Temporary Structures, Equipment, and Systems - Reserved
Section 109 (IBC) Fees - Reserved
Section 111 (IBC) Certificate of Occupancy - Reserved
Section 112 (IBC) Service Utilities - Reserved
Section 113 (IBC) Means of Appeals - Reserved
Section 114 (IBC) Violations - Reserved
Section 115 (IBC) Stop Work Order – Reserved
Section 116 (IBC) Unsafe Structures and Equipment – Reserved

Page 5 of 144
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 6 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 Internation Building Code (IBC)
Section 110.3.4.1
Submitted by:
Building Safety Code Committee
110.3.4.1 Strap and Shear.  All bracing, hardware, and holddowns are in place.  Roof sheathing is in place and 
fastened, all structural sheathing is in place and properly fastened.  Approved truss layout and calculations shall 
be onsite at time of inspection.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 7 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 Internation Building Code (IBC)
Section 110.3.6
Submitted by:
Building Safety Code Committee
110.3.6 Lath and gypsum panel product inspection.   Lath and gypsum panel product inspections shall be 
made after lathing and gypsum panel products, interior and exterior, are in place, but before any plastering is 
applied or gypsum panel product joints and fasteners are taped and finished.
Exception: Gypsum panel products that are not part of a fire-resistance-rated assembly or a shear assembly.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 8 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 Internation Building Code (IBC)
Section 312.1
Submitted by:
Building Safety Code Committee
312.1 General.
Buildings and structures of an accessory character and miscellaneous structures not classified in any specific 
occupancy shall be constructed, equipped and maintained to conform to the requirements of this code 
commensurate with the fire and life hazard incidental to their occupancy. Group U shall include, but not be 
limited to, the following:

Agricultural buildings

Aircraft hangars, accessory to a one- or two-family residence (see Section 412.4)

Barns

Carports

Communication equipment structures with a gross floor area of less than 1,500 square feet (139 m2)

Fences more than 7 feet (2134 mm) in height as measured to the highest point from the top of the footing

Grain silos, accessory to a residential occupancy

Livestock shelters

Private garages

Retaining walls

Sheds

Stables

Tanks

Towers
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 9 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 Internation Building Code (IBC)
Section 403.3
Submitted by:
Building Safety Code Committee
403.3 Automatic sprinkler system. 
Buildings and structures shall be equipped throughout with an automatic sprinkler system in accordance 
with Section 903.3.1.1 and a secondary water supply where required by Section 403.3.3.
Exception: An automatic sprinkler system shall not be required in spaces or areas of telecommunications 
equipment buildings used exclusively for telecommunications equipment, associated electrical power distribution 
equipment, batteries and standby engines, provided that those spaces or areas are equipped throughout with 
an automatic fire detection system in accordance with Section 907.2 and are separated from the remainder of 
the building by not less than 1-hour fire barriers constructed in accordance with Section 707 or not less than 2-
hour horizontal assemblies constructed in accordance with Section 711, or both.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 10 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 310.4 & 310.4.1
Submitted by: 
Building Safety Code Committee
310.4 Residential Group R-3 occupancies where the occupants are primarily permanent in nature and not 
classified as Group R-1, R-2, R-4 or I, including:
       Buildings that do not contain more than two dwelling units
Care facilities that provide accommodations for five or fewer persons receiving care
Congregate living facilities (nontransient) with 5 or fewer guest rooms and 16 10 or fewer occupants
Boarding houses (nontransient)
Convents
Dormitories
Emergency services living quarters
Fraternities and sororities
Monasteries
Congregate living facilities (transient) with 5 or fewer guestrooms and 10 or fewer occupants
Boarding houses (transient)
Lodging houses with five or fewer guestrooms and 10 or fewer occupants
Hotels (nontransient) with five or fewer guestrooms and 10 or fewer occupants
Motels (nontransient) with five or fewer guestrooms and 10 or fewer occupants
310.4.1 Care facilities within a dwelling.
Care facilities for five or fewer persons receiving care that are within a single-family dwelling are permitted to 
comply with the International Residential Code provided  Other than where preempted by Arizona State Law, 
an automatic sprinkler system is installed in accordance with Section 903.3.1.3 of this code or Section P2904 of 
the International Residential Code shall be provided.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 11 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 402.5
Submitted by: 
Building Safety Code Committee
402.5 Automatic sprinkler system.
Covered and open mall buildings and buildings connected shall be equipped throughout with an automatic 
sprinkler system in accordance with Section 903.3.1.1, which shall comply with all of the following:
1.
The automatic sprinkler system shall be complete and operative throughout occupied space in the mall 
building prior to occupancy of any of the tenant spaces. Unoccupied tenant spaces shall be similarly 
protected unless provided with approved alternative protection.
2.
Sprinkler protection for the mall of a covered mall building shall be independent from that provided for 
tenant spaces or anchor buildings.
3.
Sprinkler protection for the tenant spaces of an open mall building shall be independent from that 
provided for anchor buildings.
4.
Sprinkler protection shall be provided beneath exterior circulation balconies located adjacent to an open 
mall.
5.
Where tenant spaces are supplied by the same system, they shall be independently controlled.
Exception: An automatic sprinkler system shall not be required in spaces or areas of open parking 
garages separated from the covered or open mall building in accordance with Section 402.4.2.3 and constructed 
in accordance with Section 406.5.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 12 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 420.4
Submitted by: 
Building Safety Code Committee
420.4 Automatic sprinkler system.
Other than where preempted by the Arizona Revised Statutes, Group R occupancies shall be equipped throughout 
with an automatic sprinkler system in accordance with Section 903.2.8. Group I-1 occupancies shall be equipped 
throughout with an automatic sprinkler system in accordance with Section 903.2.6. Quick-response or 
residential automatic sprinklers shall be installed in accordance with Section 903.3.2.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 13 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 Internation Building Code (IBC)
Section 502.1
Submitted by:
Building Safety Code Committee
502.1 Address identification. New buildings shall be provided with approved address identification in 
accordance with the Tempe Zoning and Development Code, Section 4-903 A and Tempe Administrative Code, 
Section 117. Existing buildings shall be provided with approved address identification as required when 
originally constructed. Where original approvals do not exist, existing buildings shall be provided with numbers 
where each character shall be a minimum of 4 inches (102 mm) high and a minimum stroke width of 1/2 inch 
(12.7 mm). They shall be installed on a contrasting background and be plainly visible from the street or road 
fronting the property. Address numbers shall be maintained.
New and existing buildings shall be provided with approved address identification. The address identification 
shall be legible and placed in a position that is visible from the street or road fronting the property. Address 
identification characters shall contrast with their background. Address numbers shall be Arabic numbers or 
alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 4 inches (102 mm) 
high with a minimum stroke width of 1/2 inch (12.7 mm). Where required by the fire code official, address 
identification shall be provided in additional approved locations to facilitate emergency response. Where access is 
by means of a private road and the building address cannot be viewed from the public way, a monument, pole or 
other approved sign or means shall be used to identify the structure. Address identification shall be maintained.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 14 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 Internation Building Code (IBC)
Chapter 9
Submitted by:
Building Safety Code Committee
Chapter 9 Fire Protection and Life Safety Systems
Notes:
1.
For reserved sections herein, refer to the International Fire Code for these code requirements.
2.
Any conflicts between this code and the International Fire Code, the International Fire Code shall apply.
903.2 Where required. - Reserved
903.2.1.1 Group A-1. - Reserved
903.2.1.2 Group A-2. - Reserved
903.2.1.3 Group A-3. - Reserved
903.2.1.4 Group A-4. - Reserved
903.2.1.5 Group A-5. - Reserved
903.2.1.6 Assembly occupancies on roofs. - Reserved
903.2.1.7 Multiple fire areas. - Reserved
903.2.2 Group B. - Reserved
903.2.2.1 Ambulatory care facilities. - Reserved 
903.2.3 Group E. - Reserved
903.2.4 Group F-1. - Reserved
903.2.4.1 Woodworking operations. - Reserved
903.2.4.3 Group F-1 upholstered furniture or mattresses. - Reserved
903.2.5.1 General. - Reserved
903.2.5.2 Group H-5 occupancies. - Reserved
903.2.5.3 Pyroxylin plastics. - Reserved
903.2.7 Group M. - Reserved
903.2.8 Group R. - Reserved
903.2.8.1 Group R-3. - Reserved
903.2.8.2 Group R-4 Condition 1. - Reserved
903.2.9 Group S-1. - Reserved
903.2.9.1 Repair garages. - Reserved
903.2.9.2 Bulk storage of tires. - Reserved
903.2.9.4 Group S-1 upholstered furniture and mattresses. - Reserved
903.2.10 Group S-2 parking garages. - Reserved
903.2.10.1 Commercial parking garages. - Reserved
903.2.10.2 Mechanical access enclosed parking garages. - Reserved
903.2.11 Specific building areas and hazards. - Reserved
903.2.11.1 Stories without openings. - Reserved
903.2.11.1.1 Opening dimensions and access. - Reserved
903.2.11.1.2 Openings on one side only. - Reserved
903.2.11.1.3 Basements. - Reserved
903.2.11.3 Buildings 55 feet or more in height. - Reserved
903.2.11.8 Occupancies which permit smoking. - Reserved
903.2.11.9 Shell Buildings. - Reserved
903.2.11.10 Additions. - Reserved

Page 15 of 144
903.2.11.11 Change of occupancy. - Reserved
903.2.11.11 Existing building hazard Classifications - Reserved
903.3.1.1.2 Bathrooms. - Reserved
903.3.1.2 NFPA 13R sprinkler systems. - Reserved
903.3.1.2.1 Balconies and decks. - Reserved
903.3.1.2.2 Corridors and balconies in the means of egress. - Reserved
903.3.1.3 NFPA 13D sprinkler systems. - Reserved
903.3.6 Hose threads. - Reserved
905.4 Location of Class I standpipe hose connections. - Reserved
907.2.11.6.1 Alterations, repairs and additions. - Reserved
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 16 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 Internation Building Code (IBC)
Section 502.1
Submitted by:
Building Safety Code Committee
TABLE 1004.5
MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
FUNCTION OF SPACE
OCCUPANT LOAD FACTORa
Accessory storage areas, mechanical equipment room
300 gross
Agricultural building
300 gross
Aircraft hangars
500 gross
Airport terminal
Baggage claim
20 gross
Baggage handling
300 gross
Concourse
100 gross
Waiting areas
15 gross
Assembly
Gaming floors (keno, slots, etc.)
11 gross
Exhibit gallery and museum
30 net
Assembly with fixed seats
See Section 1004.6
Assembly without fixed seats
Concentrated (chairs only—not fixed)
7 net
Standing space
5 net
Unconcentrated (tables and chairs)
15 net

Page 17 of 144
Bowling centers, allow 5 persons for each lane 
including 15 feet of runway, and for additional areas
7 net
Business areas
150 gross
Concentrated business use areas
See Section 1004.8
Courtrooms—other than fixed seating areas
40 net
Day care
35 net
Dormitories
50 gross
Educational
Classroom area
20 net
Shops and other vocational room areas
50 net
Exercise rooms
50 gross
Group H-5 fabrication and manufacturing areas
200 gross
Industrial areas
100 gross
Information technology equipment facilities
300 gross
Institutional areas
Inpatient treatment areas
240 gross
Outpatient areas
100 gross
Sleeping areas
120 gross
Kitchens, commercial
200 gross
Library
Reading rooms
50 net
Stack area
100 gross
Locker rooms
50 gross
Mall buildings—covered and open
See Section 402.8.2

Page 18 of 144
Mercantile
60 gross
Storage, stock, shipping areas
300 gross
Parking garages
200 gross
Residential
200 gross
Skating rinks, swimming pools
Rink and pool
50 grossb
Decks
15 gross
Stages and platforms
15 net
Warehouses
500 gross
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2.
a.
Floor area in square feet per occupant.
b.
The occupant load of Public pools of Class B, C and Aquatic Recreation Facilities shall be in 
accordance with Sections 403 and 608 of the International Swimming Pool and Spa Code.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 19 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1025.1
Submitted by: 
Building Safety Code Committee
1025.1 General.
Approved luminous egress path markings delineating the exit path shall be provided in all high-rise buildings of 
Group A, B, E, I-1, M or R-1 occupancies in accordance with this section.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 20 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1101.1
Submitted by: 
Building Safety Code Committee
1101.1 Scope.
The provisions of this chapter and the Arizona Revised Statutes ARS sections 41-1492 through 
41-1492.12 shall control the design and construction of facilities for accessibility for individuals 
with disabilities.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 21 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1104.1
Submitted by: 
Building Safety Code Committee
1104.1 Site arrival points.
At least one accessible route within the site shall be provided from public transportation stops, accessible parking, 
accessible electric vehicle charging spaces, accessible passenger loading zones, and public streets or sidewalks to 
the accessible building entrance served.
Exception: Other than in buildings or facilities containing or serving Type B units, 
an accessible route shall not be required between site arrival points and 
the building or facility entrance if the only means of access between them is a vehicular way 
not providing for pedestrian access.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 22 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1203.1
Submitted by: 
Building Safety Code Committee
1203.1 Equipment and systems.
Interior spaces intended for human occupancy shall be provided with active or passive space heating and cooling 
systems capable of maintaining an indoor temperature of not less than 68° between 70oF (2021°C) and 82°F 
(28°C) (if cooled by air conditioning, and 88°F (30°C) if cooled by evaporative cooling), measured at a point 3 
feet (914mm) above the floor in the center of the room., on the design heating day. The installation of portable 
space heaters or coolers shall not be used to achieve compliance with this section.
Exception: Space heating and cooling systems are not required for:
1. Interior spaces where the primary purpose of the space is not associated with human 
comfort.
2. Group F, H, S or U occupancies.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 23 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1025.1
Submitted by: 
Building Safety Code Committee
1025.1 General.
Approved luminous egress path markings delineating the exit path shall be provided in all high-rise buildings of 
Group A, B, E, I-1, M or R-1 occupancies in accordance with this section.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 24 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1603.1.10, 1603.1.11, 1603.1.12
Submitted by: 
Building Safety Code Committee
1603.1.10 Floor design live loads posted.
Where the live loads for which each floor or portion thereof of a commercial or industrial building is or has been 
designed to exceed 50 psf (2.40 kN/m2), such design live loads shall be conspicuously posted by the owner in 
that part of each story in which they apply, using durable signs. It shall be unlawful to remove or deface such 
notices. The construction documents shall show the proposed sign location and the maximum floor loads.
1603.1.11 Issuance of certificate of occupancy.
A certificate of occupancy required by Section 107 shall not be issued until the floor load signs, required by 
Section 1603.1.10 of this code, have been installed.
1603.1.12 Restrictions on loading.
It shall be unlawful to place, or cause or permit to be placed, on any floor or roof of a building, structure or 
portion thereof, a load greater than is permitted by this code.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 25 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1607.1
Submitted by: 
Building Safety Code Committee
Table 1607.1 Minimum Uniformly Distributed Live Loads, L0, and Minimum Concentrated Live Loads
One- and two-family dwellings:
Uninhabitable attics without storage
10
Uninhabitable attics with storage
20 40
Habitable attics and sleeping areas
20 40
Canopies, including marquees
20
All other areas
40
Hotels and multifamily dwellings:
Private rooms and corridors serving them
40
Public rooms
100a
Residential
Corridors serving public rooms
100
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 26 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1104.1
Submitted by: 
Building Safety Code Committee
1612.3 Establishment of flood hazard areas. 
To establish flood hazard areas, the applicable governing authority shall adopt a flood hazard map and supporting 
data. The flood hazard map shall include, at a minimum, areas of special flood hazard as identified by the Federal 
Emergency Management Agency in an engineering report entitled “The Flood Insurance Study for [INSERT 
NAME OF JURISDICTION]Maricopa County, Arizona and Incorporated Areas” dated [insert date of 
issuance]July 19, 2001, as amended or revised with the accompanying Flood Insurance Rate Map (FIRM) and 
Flood Boundary and Floodway Map (FBFM) and related supporting data along with any revisions thereto. The 
adopted flood hazard map and supporting data are hereby adopted by reference and declared to be part of this 
section.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 27 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1704.2
Submitted by: 
Building Safety Code Committee
1704.2 Special inspections and tests.   Where application is made to the building official for construction as 
specified in Section 105 of the Tempe Administrative Code, the owner or the owner’s authorized agent, other 
than the contractor, shall employ one or more approved agencies to provide special inspections and tests during 
construction on the types of work specified in Section 1705 and identify the approved agencies to the building 
official. These special inspections and tests are in addition to the inspections by the building official that are 
identified in Section 110 of the Tempe Administrative Code.
Prior to the issuance of a permit, the registered design professional responsible for the observations shall provide 
a partially completed, parts A, B and C, Special Inspection Certificate (city form) to the building official.
The registered design professional responsible for the observations or the designated special inspector, shall 
periodically visit the site during the course of construction requiring the observations as set forth in the 
statement of special inspections.
Upon completion of the work requiring observations, a completed Special Inspection Certificate (city form) 
shall be provided to the building official under the seal and signature of the registered design professional 
responsible for the observations. A final inspection will not be approved or a Certificate of Occupancy will not 
be issued until the special inspection certificate is received by the building official.
Exceptions:
1.
Special inspections and tests are not required for construction of a minor nature or as warranted by 
conditions in the jurisdiction as approved by the building official.
2.
Unless otherwise required by the building official, special inspections and tests are not required for 
Group U occupancies that are accessory to a residential occupancy including, but not limited to, those 
listed in Section 312.1.
3.
Special inspections and tests are not required for portions of structures designed and constructed in 
accordance with the cold-formed steel light-frame construction provisions of Section 2206.1.2 or 
the conventional light-frame construction provisions of Section 2308.
4.
The contractor is permitted to employ the approved agencies where the contractor is also the owner.
1704.2.1 Special inspector qualifications.  Prior to the start of the construction, the approved agencies shall 
provide written documentation to the building official demonstrating the competence and relevant experience or 
training of the special inspectors who will perform the special inspections and tests during construction or 
provide evidence of approval in another authority having jurisdiction within Maricopa County by being listed on 
their approved published list. Experience or training shall be considered to be relevant where the documented 
experience or training is related in complexity to the same type of special inspection or testing activities for 
projects of similar complexity and material qualities. These qualifications are in addition to qualifications 
specified in other sections of this code.
The registered design professional in responsible charge and engineers of record involved in the design of the 
project are permitted to act as an approved agency and their personnel are permitted to act as special 
inspectors for the work designed by them, provided they qualify as special inspectors.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 28 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1704.5
Submitted by: 
Building Safety Code Committee
1704.5 Submittals to the building official.
In addition to the submittal of reports of special inspections and tests in accordance with Section 1704.2.4, reports 
and certificates shall be submitted by the owner or the owner’s authorized agent to the building official for each 
of the following:
1.
Certificates of compliance for the fabrication of structural, load-bearing or lateral load-resisting 
members or assemblies on the premises of an approved fabricator in accordance with Section 
1704.2.5.1.
2.
Certificates of compliance for the seismic qualification of nonstructural components, supports and 
attachments in accordance with Section 1705.14.2.
3.
Certificates of compliance for designated seismic systems in accordance with Section 1705.14.3.
4.
Reports of preconstruction tests for shotcrete in accordance with ACI 318.
5.
Certificates of compliance for open web steel joists and joist girders in accordance with Section 2207.5.
6.
Reports of material properties verifying compliance with the requirements of AWS D1.4 for weldability 
as specified in Section 26.6.4 of ACI 318 for reinforcing bars in concrete complying with a standard 
other than ASTM A706 that are to be welded.
7.
Reports of mill tests in accordance with Section 20.2.2.5 of ACI 318 for reinforcing bars complying 
with ASTM A615 and used to resist earthquake-induced flexural or axial forces in the special moment 
frames, special structural walls or coupling beams connecting special structural walls of seismic force-
resisting systems in structures assigned to Seismic Design Category B, C, D, E or F.
8.
Special Inspection Certificate for types of equipment or installations of electrical, mechanical, fuel gas or 
plumbing as required in section 1705.12.6 of this code.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 29 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1704.6.1
Submitted by: 
Building Safety Code Committee
1704.6.1 Structural observations for structures.
Structural observations shall be provided for those structures where one or more of the following conditions 
exist:
1.
The structure is classified as Risk Category III or IV.
2.
The structure is a high-rise building or the structure is 75 feet (22,860 mm) above grade plane.
3.
The structure is assigned to Seismic Design Category E, and is greater than two stories above grade 
plane.
4.
Such observation is required by the registered design professional responsible for the structural design.
5.
Such observation is specifically required by the building official.
6.
The structure is more than three stories above grade plane.
7.
Post-tension concrete.
8.
Prefabricated units and their connections when such units are utilized structurally in the lateral force-
resisting systems of a structure.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 30 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 1907.1.1
Submitted by: 
Building Safety Code Committee
1907.1.1 Identifcation of Post Tension.  
All post-tension slabs on ground shall be permanently stamped, marked or otherwise identified in a conspicuous 
location indicating the slab is a post- tension slab. Conspicuous locations include, but are not limited to, entrance 
porches, slabs at garage doors or patio slabs.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 31 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 2902.5
Submitted by: 
Building Safety Code Committee
2902.5 Drinking fountain location.
Drinking fountains shall not be required to be located in individual tenant spaces provided that public drinking 
fountains are located within a distance of travel of 500 feet (152 m) of the most remote location in the tenant 
space and not more than one story above or below the tenant space. Where the tenant space is in a covered or 
open mall, such distance shall not exceed 300 feet (91 m).
Exceptions: 
1.
In other than I-1 Residential care, I-3 Reformatories, detention centers and correctional centers, 
I- 4 Adult day care and child care, R-2 Dormitories, fraternities, sororities and boarding houses, 
R-3 Congregate living facilities with 16 or fewer persons, and R-4 Residential care/assisted 
living facilities, drinking fountains are not required for an occupant load of 30 or fewer.
2.
Drinking fountains will not be required in individual tenant spaces or single tenant buildings of 
Group B, F-1, F-2, S-1 or S-2 occupancies where an accessible break room sink is provided 
within the tenant space or building.
3.
Occupancies that provide food and/or beverage service to patrons do not need to provide 
drinking fountains.
4.
Where each tenant space has full access to a centrally located service sink on the floor it 
occupies, individual tenant service sinks will not be required.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 32 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 2902.3.3
Submitted by: 
Building Safety Code Committee
2902.3.3 Location of toilet facilities in occupancies other than malls. 
In occupancies other than covered and open mall buildings, the required public and employee toilet facilities shall 
be located not more than one story above or below the space required to be provided with toilet facilities, and the 
path of travel to such facilities shall not exceed a distance of 500 feet (152 m). The required public and employee 
toilet facilities may not be located in a building under different ownership or in a tenant space under the control of 
a different tenant.
Exceptions:
1.
The location and maximum distances of travel to required employee facilities in factory and 
industrial occupancies shall be permitted to exceed that required by this section, provided that the 
location and maximum distances of travel are approved.
2.
The location and maximum distances of travel to required public and employee facilities in Group 
S occupancies shall be permitted to exceed that required by this section, provided that the location and 
maximum distances of travel are approved.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 33 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section P2902.2
Submitted by: 
Building Safety Code Committee
[P] 2902.2 Separate facilities. 
Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Exceptions:
1.
Separate toilet facilities shall not be required for dwelling units and sleeping units.
2.
Separate toilet facilities shall not be required in structures or tenant spaces with a total occupant load, 
including both employees and customers, of 15 30 or fewer.
3.
Separate toilet facilities shall not be required in mercantile occupancies in which the maximum occupant 
load is 100 or fewer.
4.
Separate toilet facilities shall not be required in business occupancies  in which the maximum occupant 
load is 25 30 or fewer.
5.
Separate toilet facilities shall not be required to be designated by sex where single-user toilet rooms are 
provided in accordance with Section 2902.1.2.
6.
Separate toilet facilities shall not be required where rooms having both water closets and lavatory 
fixtures are designed for use by all persons regardless of sex and privacy is provided for water closets in 
accordance with Section 405.3.4 of the International Plumbing Code and for urinals in accordance 
with Section 405.3.5 of the International Plumbing Code.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 34 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Section 3103.1.3
Submitted by: 
Building Safety Code Committee
3103.1.3 Permit required. 
Temporary structures that cover an area greater than 120 square feet (11.16 m2) 400 square feet (18.58 m2), 
including connecting areas or spaces with a common means of egress or entrance that are used or intended to be 
used for the gathering together of 10 50 or more persons, shall not be erected, operated or maintained for any 
purpose without obtaining a permit from the building official.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 35 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Building Code (IBC)
Appendices Adoption
Submitted by: 
Building Safety Code Committee
Adopt the following appendices:
Appendix I - Patio Covers
Appendix J - Grading
Appendix N - Replicable Buildings
Justification:
Appendix I - Patio Covers
Justification: Previously adopted in 2018
Appendix J - Grading
Justification: Previously adopted in 2018
Appendix N - Replicable Buildings
Justification: Previously adopted in 2018
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 36 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendments to 2024 International Residential Code (IRC)
Article III, Section 8-300 
Submitted by: Building Safety Code Committee
Sec. 8-300. Adopted; where filed; amendments.
That certain document known as “The International Residential Code, 2024 Edition,” which has been published as 
a code in book form by the International Code Council (ICC), chapters one through forty-four, and appendix 
chapters BB, BF, BG, BO, CA, CB, CD, CE, CF, and NB inclusive, three (3) copies with amendments of which 
are on file in the office of the City Clerk, and this same code, appendices and amendments are hereby referred to, 
adopted and made a part hereof, as if fully set forth in this article.
(Ord. No. 2008.72, 12-11-08; Ord. No. O2015.12, 4-2-15)
Charter reference – Adoption by reference. §2.14.
State law reference - Adoption by reference. A.R.S. §9-801 et. seq.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 37 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Chapter 1
Submitted by:
Building Safety Code Committee
Chapter 1 Scope and Administration
Notes:
3.
For reserved sections herein, refer to the City of Tempe Administrative Code for these code requirements.
4.
Any conflicts between this code and the Tempe Administrative Code, the Tempe Administrative Code shall apply.
101.1 Title.  These regulations shall be known as the International Residential Code Building Code of [NAME OF 
JURISDICTION], hereinafter referred to as “this code.” These regulations are one document of the overall City of Tempe 
Construction Code as defined by the adopting ordinance.
101.2 Scope. - Reserved
101.3 Purpose. - Reserved
102 Applicability. - Reserved
Section 103 (IRC) Code Compliance Agency - Reserved.
Section 104 (IRC) Duties and powers of the Building Official - Reserved.
Section 105 (IRC) Permits - Reserved.
Section 106 (IRC) Construction documents - Reserved.
Section 107 (IRC) Temporary Structures and Uses - Reserved.
Section 108 (IRC) Fees - Reserved.
Section 110 (IRC) Certificate of Occupancy - Reserved.
Section 111 (IRC) Service Utilities - Reserved.
Section 112 (IRC) Means of Appeals - Reserved.
Section 113 (IRC) Violations - Reserved.
Section 114 (IRC) Stop Work Order - Reserved.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 38 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R109.1.1.1
Submitted by:
Building Safety Code Committee
R109.1.1.1 Stem Wall Inspection.  Shall be made after any reinforcement is in place and forms (if needed) are in 
place. Cast in place hardware shall be in place at time of inspection.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 39 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R109.1.1.2
Submitted by:
Building Safety Code Committee
R109.1.1.2 Concrete pre-slab and under-floor inspection.  Concrete slab and under-floor inspections shall be 
made after in-slab or under-floor reinforcing steel and building service equipment, conduit, piping accessories and 
other ancillary equipment items are in place, but before any concrete is placed or floor sheathing installed, 
including the subfloor.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 40 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R109.1.7.1
Submitted by:
Building Safety Code Committee
R109.1.7.1 Strap and Shear.  All bracing, hardware, and holddowns are in place.  Roof sheathing is in place and 
fastened, all structural sheathing is in place and properly fastened.  Approved truss layout and calculations shall 
be onsite at time of inspection.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 41 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R109.1.8.1
Submitted by:
Building Safety Code Committee
R109.1.8.1 Lath and gypsum panel product inspection.   Lath and gypsum panel product inspections shall be made after 
lathing and gypsum panel products, interior and exterior, are in place, but before any plastering is applied or gypsum panel 
product joints and fasteners are taped and finished.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 42 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R301.2
Submitted by: 
Building Safety Code Committee
a.
 Where weathering requires a higher strength concrete or grade of masonry than necessary to satisfy the 
structural requirements of this code, the frost line depth strength required for weathering shall govern. 
The weathering column shall be filled in with the weathering index, “negligible,” “moderate” or 
“severe” for concrete as determined from Figure R301.2(1). The grade of masonry units shall be 
determined from ASTM C34, ASTM C55, ASTM C62, ASTM C73, ASTM C90, ASTM C129, ASTM 
C145, ASTM C216 or ASTM C652.
b.
Where the frost line depth requires deeper footings than indicated in Figure R403.1(1), the frost line 
depth strength required for weathering shall govern. The jurisdiction shall fill in the frost line depth 
column with the minimum depth of footing below finish grade.
c.
The jurisdiction shall fill in this part of the table to indicate the need for protection depending on whether 
there has been a history of local subterranean termite damage.
d.
The jurisdiction shall fill in this part of the table with the wind speed from the ultimate design wind 
speeds map [Figure R301.2(2)]. Wind exposure category shall be determined on a site-specific basis in 
accordance with Section R301.2.1.4.
e.
The jurisdiction shall fill in this section of the table to establish the design criteria using “Phoenix Sky 
Harbor” in Table 10A from ACCA Manual J or established criteria determined by the jurisdiction.
f.
The jurisdiction shall fill in this part of the table with the seismic design category determined 
from Section R301.2.2.1.
TABLE R301.2
CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA
GROUND 
SNOW 
LOADo
WIND DESIGN
SEISMIC 
DESIGN 
CATEGORYf
SUBJECT TO DAMAGE FROM
ICE BARRIER 
UNDERLAYMENT 
REQUIREDh
FLOOD 
HAZARDSg
AIR 
FREEZING 
INDEXi
MEAN 
ANNUAL 
TEMPj
Speedd (mph)
Topographic 
effectsk
Special 
wind 
regionl
Windborne 
debris 
zonem
Weatheringa
Frost 
line 
depthb
Termitec
0
115
NO
NO
NO
B
Negligible
0
HEAVY
NO
SEE 
MARICOPA 
COUNTY
NA
71.2F
MANUAL J DESIGN CRITERIAn
Elevation
Altitude 
correction 
factore
Coincident 
wet bulb
Indoor 
winter 
design 
relative 
humidity
Indoor winter design dry-bulb 
temperature
Outdoor winter design dry-bulb 
temperature
Heating temperature 
difference
—
—
—
—
—
—
—
Latitude
Daily 
range
Summer 
design 
gains
Indoor 
summer 
design 
relative 
humidity
Indoor summer design dry-bulb 
temperature
Outdoor summer design dry-
bulb temperature
Cooling temperature 
difference
—
—
—
—
—
—
—
For SI: 1 pound per square foot = 0.0479 kPa, 1 mile per hour = 0.447 m/s.

Page 43 of 144
g.
The jurisdiction shall fill in this part of the table with: the date of the jurisdiction’s entry into the 
National Flood Insurance Program (date of adoption of the first code or ordinance for management of 
flood hazard areas); and the title and date of the currently effective Flood Insurance Study or other flood 
hazard study and maps adopted by the authority having jurisdiction, as amended.
h.
In accordance with Sections R905.1.2, R905.4.3.1, R905.5.3.1, R905.6.3.1, R905.7.3.1 and R905.8.3.1, 
where there has been a history of local damage from the effects of ice damming, the jurisdiction shall fill 
in this part of the table with “YES.” Otherwise, the jurisdiction shall fill in this part of the table with 
“NO.”
i.
The jurisdiction shall fill in this part of the table with the 100-year return period air freezing index (BF-
days) from Figure R403.3(2) or from the 100-year (99 percent) value on the National Climatic Data 
Center data table “Air Freezing Index-USA Method (Base 32°F).”
j.
The jurisdiction shall fill in this part of the table with the mean annual temperature from the National 
Climatic Data Center data table “Air Freezing Index-USA Method (Base 32°F).”
k.
In accordance with Section R301.2.1.5, where there is local historical data documenting structural 
damage to buildings due to topographic wind speed-up effects, the jurisdiction shall fill in this part of the 
table with “YES.” Otherwise, the jurisdiction shall indicate “NO” in this part of the table.
l.
In accordance with Figure R301.2(2), where there is local historical data documenting unusual wind 
conditions, the jurisdiction shall fill in this part of the table with “YES” and identify any specific 
requirements. Otherwise, the jurisdiction shall indicate “NO” in this part of the table.
m. In accordance with Section R301.2.1.2 the jurisdiction shall indicate the wind-borne debris wind zone(s). 
Otherwise, the jurisdiction shall indicate “NO” in this part of the table.
n.
The jurisdiction shall fill in these sections of the table to establish the design criteria using Table 1a or 
1b from ACCA Manual J or established criteria determined by the jurisdiction.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 44 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section 301.2.4
Submitted by: 
Building Safety Code Committee
R301.2.4 Floodplain construction.
Buildings and structures constructed in whole or in part in flood hazard areas (including A or V zones) as 
established in Table R301.2, and substantial improvement and repair of substantial damage of buildings and 
structures located in whole or in part in flood hazard areas, shall be designed and constructed in accordance 
with Section R306. Buildings and structures that are located in more than one flood hazard area, including A 
Zones, Coastal A Zones and V Zones, shall comply with the provisions associated with the most restrictive flood 
hazard area. Buildings and structures located in whole or in part in identified floodways shall be designed and 
constructed in accordance with ASCE 24.the Tempe City Code, Chapter 12.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 45 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section 301.5
Submitted by: 
Building Safety Code Committee
TABLE R301.5
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS (in pounds per square foot)
USE
UNIFORM LOAD 
(psf)
CONCENTRATED LOAD 
(lb)
Uninhabitable attics without storageb
10
—
Uninhabitable attics with limited storageb, g
20
—
Habitable attics and attics served with fixed 
stairs
3040
—
Balconies (exterior) and deckse
40
—
Fire escapes
40
—
Guards
—
200h, i
Guard in-fill componentsf
—
50h
Handraild
—
200h
Passenger vehicle garages
50
2,000a
Areas other than sleeping areas
40
—
Sleeping areas
3040
—
Stairs
40c
300c
For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm2, 1 pound = 4.45 N.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 46 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section 302.1(1) & 302.1 (2)
Submitted by: 
Building Safety Code Committee
R302.1.  TABLE R302.1(1)
EXTERIOR WALLS
EXTERIOR WALL 
ELEMENT
MINIMUM FIRE-RESISTANCE RATING
MINIMUM FIRE 
SEPARATION 
DISTANCE
Fire-resistance 
rated
1 hour—tested in accordance with ASTM 
E119, UL 263 or Section 703.2.2 of 
the International Building Code with exposure 
from both sides
0 feet
Walls
Not fire-
resistance 
rated
0 hours
≥ 5 feet
Not allowed
NA
< 2 feet
Fire-resistance 
rated
1 hour on the underside, or heavy timber, or 
fire-retardant-treated wooda, b
≥ 2 feet to < 5 feet
Projections
Not fire-
resistance 
rated
0 hours
≥ 5 feet
Not allowed
NA
< 3 feet
25% 
maximum of 
wall area
0 hours
3 feet
Openings in 
walls
Unlimited
0 hours
5 feet
Penetrations
All
Comply with Section R302.4
< 3 feet

Page 47 of 144
None required
3 feet
For SI: 1 foot = 304.8 mm.
NA = Not Applicable.
a.
 The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the eave 
overhang if fireblocking is provided from the wall top plate to the underside of the roof sheathing.
b.
The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the rake 
overhang where vent openings that communicate with the attic are not installed in the overhang or 
gable wall.
c.
Patios and carports fire separation distance shall be taken from walls and projections, no consideration 
shall be given for openings in walls.
d.
The fire-resistance rating of columns and projections, shall be permitted to be reduced to 0 for patios 
and carports constructed of noncombustible materials where the fire separation distance is 3 feet or 
more.
TABLE R302.1(2)
EXTERIOR WALLS—DWELLINGS AND TOWNHOUSES WITH AN AUTOMATIC SPRINKLER 
SYSTEM
EXTERIOR WALL 
ELEMENT
MINIMUM FIRE-RESISTANCE RATING
MINIMUM FIRE 
SEPARATION 
DISTANCE
Fire-
resistance 
rated
1 hour—tested in accordance with ASTM 
E119, UL 263 or Section 703.2.2 of 
the International Building Code with exposure 
from the outside
0 feet
Walls
Not fire-
resistance 
rated
0 hours
3 feeta
Not allowed
NA
< 2 feet
Fire-
resistance 
rated
1 hour on the underside, or heavy timber, or 
fire-retardant-treated woodb, c
2 feeta
Projections
Not fire-
resistance 
rated
0 hours
3 feet
Not allowed
NA
< 3 feet
Openings in 
walls
Unlimited
0 hours
3 feeta
Penetrations
All
Comply with Section R302.4
< 3 feet

Page 48 of 144
None required
3 feeta
For SI: 1 foot = 304.8 mm.
NA = Not Applicable.
a.
The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the eave 
overhang if fireblocking is provided from the wall top plate to the underside of the roof sheathing.
b.
The fire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the rake 
overhang where vent openings that communicate with the attic are not installed in the overhang or 
gable wall.
c.
Patios and carports fire separation distance shall be taken from walls and projections, no consideration 
shall be given for openings in walls.
d.
The fire-resistance rating of columns and projections, shall be permitted to be reduced to 0 for patios 
and carports constructed of noncombustible materials where the fire separation distance is 3 feet or 
more.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 49 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R306.1
Submitted by: 
Building Safety Code Committee
R306.1 General.
Buildings and structures constructed in whole or in part in flood hazard areas (including A or V zones) established 
in Table R301.2, and substantial improvement and repair of substantial damage of buildings and 
structures located in whole or in part in flood hazard areas, shall be designed and constructed in accordance with 
the provisions contained in this section and Tempe City Code, Chapter 12. Buildings and structures that are 
located in more than one flood hazard area, including A Zones, Coastal A Zones and V Zones, shall comply with 
the provisions associated with the most restrictive flood hazard area. Buildings and structures located in whole or 
in part in identified floodways shall be designed and constructed in accordance with ASCE 24.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 50 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R309
Submitted by: 
Building Safety Code Committee
R309.1 Townhouse automatic sprinkler systems.
Other than where preempted by the Arizona Revised Statutes in townhouses and attached accessory uses thereto, 
an automatic fire sprinkler system shall be installed as required by Section P2904 An automatic sprinkler system 
shall be installed in townhouses.
Exception:An automatic sprinkler system shall not be required where additions or alterations are made to 
existing townhouses that do not have an automatic sprinkler system installed.
R309.1.1 Design and installation.
Automatic sprinkler systems for townhouses shall be designed and installed in accordance with Section 
P2904 or NFPA 13D.
R309.2 One- and two-family dwellings automatic sprinkler systems.
An automatic sprinkler system shall be installed in one- and two-family dwellings.
Exception:  An automatic sprinkler system shall not be required for additions or alterations to existing 
buildings that are not already provided with a sprinkler system. Other than where preempted by the Arizona 
Revised Statutes in one and two-family dwellings, and attached accessory uses thereto, an automatic fire sprinkler 
system shall be installed as required by Section P2904.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 51 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R325.8
Submitted by: 
Building Safety Code Committee
R325.8 Required heating and cooling.
Where the winter design temperature in Table R301.2 is below 60°F (16°C), every dwelling unit shall be provided with heating 
facilities capable of maintaining a room temperature of not less than 68°F (20°C) at a point 3 feet (914 mm) above the floor and 2 
feet (610 mm) from exterior walls in habitable rooms at the design temperature. The installation of one or more portable space 
heaters shall not be used to achieve compliance with this section.
Interior spaces intended for human occupancy shall be provided with active or passive space-heating and cooling systems capable 
of maintaining an indoor temperature of not less than 68°F (20°C) between 70°F (21°C) and 82°F (28°C) (if cooled by air 
conditioning, and 88°F (30°C) if cooled by evaporative cooling), measured at a point 3 feet (914mm) above the floor in the center 
of the room. on the design heating day. The installation of portable space heaters or coolers shall not be used to achieve 
compliance with this section.
Exceptions:
1.
Space heating and cooling systems are not required for interior spaces where the primary purpose is not associated
with human comfort.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 52 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R310.6 & R311.6
Submitted by: 
Building Safety Code Committee
R310.6 Power source.
Smoke alarms shall receive their primary power from the building wiring where such wiring is served from a 
commercial source and, where primary power is interrupted, shall receive power from a battery. Wiring shall be 
permanent and without a disconnecting switch other than those required for overcurrent protection.
Exceptions:
1.    Smoke alarms shall be permitted to be battery operated where installed in buildings without 
commercial power.
2.    Smoke alarms installed in accordance with Section R310.2.2 shall be permitted to be battery 
powered where alteration or repairs do not result in the removal of interior wall or ceiling finishes 
unless there is an attic or crawl space or basement available which could provide access for hardwiring 
of smoke alarms.
R311.6 Power source.
Carbon monoxide alarms shall receive their primary power from the building wiring where such wiring is served from a 
commercial source and, where primary power is interrupted, shall receive power from a battery. Wiring shall be permanent and 
without a disconnecting switch other than those required for overcurrent protection.
Exceptions:
1.
Carbon monoxide alarms shall be permitted to be battery operated where installed in buildings without commercial 
power.
2.
Carbon monoxide alarms installed in accordance with Section R311.2.2 shall be permitted to be battery 
powered where alteration or repairs do not result in the removal of interior wall or ceiling finishes unless there is an 
attic or crawl space or basement available which could provide access for hardwiring of smoke alarms.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 53 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R401.3
Submitted by: 
Building Safety Code Committee
R401.3 Drainage.
Surface drainage shall be diverted to a storm sewer conveyance or other approved point of collection that does 
not create a hazard in accordance of the provisions of the Tempe City Code, Chapter 12. Lots shall be graded to 
drain surface water away from foundation walls. The grade shall fall not fewer than 6 inches (152 mm) within the 
first 10 feet (3048 mm).
Exception: Where lot lines, walls, slopes or other physical barriers prohibit 6 inches (152 mm) of fall within 10 feet (3048 mm), 
drains or swales shall be constructed in accordance with the provisions of the Tempe City Code, Chapter 12, to ensure drainage 
away from the structure. Impervious surfaces within 10 feet (3048 mm) of the building foundation shall be sloped not less than 2 
percent away from the building
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 54 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R502.3.1
Submitted by: 
Building Safety Code Committee
R502.3.1 Sleeping areas and attic joists.
Table R502.3.1(1) shall be used to determine the maximum allowable span of floor joists that support sleeping 
areas and attics that are accessed by means of a fixed stairway in accordance with Section R318.7 provided that 
the design live load does not exceed 30 40 pounds per square foot (1.44 92 kPa) and the design dead load does 
not exceed 20 pounds per square foot (0.96 kPa). The allowable span of ceiling joists that support attics used for 
limited storage or no storage shall be determined in accordance with Section R802.5.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 55 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section R1007.1
Submitted by: 
Building Safety Code Committee
R1007.1 Clean Burning Fireplaces.
The purpose of this standard is to regulate fireplaces, woodstoves, or other solid-fuel burning devices to reduce the 
amount of air pollution caused by particulate matter and carbon monoxide.
The effective date of the regulations and prohibitions set forth in this standard took effect on December 31, 1998.
  Definitions: For purposes of this standard, the following words and terms shall be defined as follows:
    FIREPLACE means a built-in place masonry hearth and fire chamber or a factory-built appliance, designed to 
burn solid fuel or to accommodate gas or electric log insert or similar device, and which is intended for occasional 
recreational or aesthetic use, not for cooking, heating, or industrial processes.
    SOLID FUEL includes but is not limited to wood, coal, or other nongaseous or non-liquid fuels, including 
those fuels defined by the Maricopa County Air Pollution Control Officer as inappropriate fuel to burn in 
residential wood-burning devices.
    WOODSTOVE means a solid-fuel burning heating appliance including a pellet stove, which is either 
freestanding or designed to be inserted into a fireplace.
R1007.2 Installation restrictions.
On or after the effective date, no person, firm or corporation shall construct or install a fireplace or a woodstove, 
and the building official shall not approve or issue a permit to construct or install a fireplace or a woodstove, 
unless the fireplace or woodstove complied with one of the following:
1.
A fireplace which has a permanently installed gas or electric log insert.
2.
A fireplace, woodstove, or other solid-fuel burning appliance which has been certified by the United 
States Environmental Protection Agency as conforming to 40 Code of Federal Regulations Part 60, 
Subpart AAA as in effect on July 1, 1990.
3.
A fireplace, woodstove or other solid-fuel burning appliance which has been tested and listed by a 
nationally recognized testing agency to meet performance standards equivalent to those adopted by 40 
Code of Federal Regulations Part 60, Subpart AAA as in effect on July 1, 1990.
4.
A fireplace, woodstove or other solid-fuel burning appliance which has been determined by the Maricopa 
County Air Pollution Control Officer to meet performance standards equivalent to those adopted by 40 
Code of Federal Regulations Part 60, Subpart AAA as in effect on July 1, 1990.
5.
A fireplace which has a permanently installed woodstove insert which complies with subparagraphs 2, 3, 
or 4 above.
R1007.3
The following installations are not regulated by this standard and are not prohibited by this standard:
1.
Furnace, boilers, incinerators, kilns, and other similar space heating or industrial process equipment.
2.
Cook-stoves, barbecue grills, and similar appliances designed primarily for cooking.
3.
Fire pits, barbecue grills, and other outdoor fireplaces.
R1007.4 Fireplace or Woodstove Alterations Prohibited.
R1007.4.1

Page 56 of 144
On or after the effective date, no person, firm or corporation shall alter or remove a gas or electric log insert or a 
woodstove insert from a fireplace for purposes of converting the fireplace to directly burn wood or other solid fuel.
R1007.4.2
On or after the effective date, no person, firm or corporation shall alter a fireplace, woodstove or other solid fuel 
burning appliance in any manner that would void its certification or operational compliance with the provisions of 
this standard.
R1007.5 Permits Required.
In addition to the provisions and restrictions of this standard, construction, installation or alteration of all 
fireplaces, woodstoves and other gas, electric or solid-fuel burning appliances and equipment shall be done in 
compliance with provisions of this Code and shall be subject to the permits and inspections.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 57 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section N1103.10.3
Submitted by: 
Building Safety Code Committee
N1103.10.3 (R403.10.3) Covers.
Outdoor heated pools and outdoor permanent spas shall be provided with a vapor-retardant cover or 
other approved vapor-retardant means.
Exception: 
1.
Where more than 75 percent of the energy for heating, computed over an operation season of not fewer 
than 3 calendar months, is from a heat pump or an on-site renewable energy system, covers or other 
vapor-retardant means shall not be required.
2.
Where pools are equipped with variable speed pump motors.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 58 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section N1111.1.2
Submitted by: 
Building Safety Code Committee
N1111.1.2 (R503.1.2) Heating and cooling systems.
New heating and cooling systems and duct work that are part of an alteration shall comply with Section 
N1103 and this section. Alterations to existing heating and cooling systems and duct work shall comply with this 
section.
Exception: 
1.
Where ductwork from an existing heating and cooling system is extended.
2.
Where additions are 250 square feet or less and do not exceed the capacities of the existing system.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 59 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section P2603.5.1
Submitted by: 
Building Safety Code Committee
P2603.5.1 Sewer depth.
Building sewers that connect to private sewage disposal systems shall be not less than [number]12 inches 
(305mm) below finished grade at the point of septic tank connection. Building sewers shall be not less 
than [number]12 inches (305mm) below grade.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 60 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section E3901.4.2 & E3901.4.3
Submitted by: 
Building Safety Code Committee
E3901.4.2 Island and peninsular countertops and work surfaces.
Receptacle outlets, if installed to serve an island or peninsular countertop or work surface, shall be installed in 
accordance with Section E3901.4.3. If a receptacle outlet is not provided to serve an island or peninsular 
countertop or work surface, provisions shall be provided at the island or peninsula for future addition of a 
receptacle outlet to serve the island or peninsular countertop or work surface.
At least one receptacle outlet shall be installed at each island countertop space with a long dimension of 24 inches 
(610 mm) or greater and a short dimension of 12 inches (305 mm) or greater.
Not less than one receptacle outlet shall be installed at each peninsular countertop long dimension space having a 
long dimension of 24 inches (610 mm) or greater and a short dimension of 12 inches (305 mm) or greater. A 
peninsular countertop is measured from the connected perpendicular wall. 
E3901.4.3 Receptacle outlet location.
Receptacle outlets rendered not readily accessible by appliances fastened in place, appliance garages, sinks, or 
rangetops as covered in the exception to Section E3901.4.1, or appliances occupying assigned spaces shall not be 
considered as these required outlets. Required receptacle outlets shall be located in one or more of the following:
1.
On or above, but not more than 20 inches (508 mm) above, the countertop or work surface.
2.
In a countertop using receptacle outlet assemblies listed for the use in countertops.
3.
In a work surface using receptacle outlet assemblies listed for use in work surfaces or listed for use in 
countertops. [210.52(C)(3)]
4.
Receptacle outlets shall be permitted to be mounted not more than 12 inches (305 mm) below the 
countertop or work surface in construction designed for the physically impaired and for island and 
peninsular countertops or work surface where the surface is flat across its entire surface and there are no 
means to mount a receptacle within 20 inches (508 mm) above the countertop, such as in an overhead 
cabinet. Receptacles mounted below the countertop or work surface in accordance with this exception 
shall not be located where the countertop or work surface extends more than 6 inches (152 mm) beyond 
its support base.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 61 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Section P2904.1.1
Submitted by: 
Building Safety Code Committee
P2904.1.1 Required sprinkler locations.
Sprinklers shall be installed to protect all areas of a dwelling unit of livable, including garages and carport areas, 
greater than 5000 square feet.
Exceptions:
1.
Attics, crawl spaces and normally unoccupied concealed spaces that do not contain fuel-
fired appliances do not require sprinklers. In attics, crawl spaces and normally unoccupied concealed 
spaces that contain fuel-fired equipment, a sprinkler shall be installed above the equipment; however, 
sprinklers shall not be required in the remainder of the space.
2.
Clothes closets, linen closets and pantries not exceeding 24 square feet (2.2 m2) in area, with the smallest 
dimension not greater than 3 feet (915 mm) and having wall and ceiling surfaces of gypsum board.
3.
Bathrooms not more than 55 square feet (5.1 m2) in area.
4.
Garages; carports; exterior porches; unheated entry areas, such as mud rooms, that are adjacent to an 
exterior door; and similar areas.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 62 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Appendix BB
Submitted by: 
Building Safety Code Committee
Appendix BB, Section BB102-Definitions
TINY HOUSE. A dwelling that is not less than 120 square feet (18.58 m2) and not more than 400 square feet (37 
m2) in floor area excluding lofts, that is not under the authority of the Arizona Department of Housing, 
Manufactured Housing Division, or constructed as a recreational vehicle as determined by the building official. or 
less in floor area excluding lofts. A dwelling that is 400 square feet (37 m2) or less in floor area excluding lofts.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 63 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Residential Code (IRC)
Appendices Adoption
Submitted by: 
Building Safety Code Committee
Adopt the following appendices:
Appendix BB - Tiny Houses
Appendix BF - Patio Covers
Appendix BG - Sound Transmission
Appendix BO - Existing Buildings and Structures
Appendix CA - Sizing and Capacities of Gas Piping
Appendix CB - Sizing of Venting Systems Serving Appliances Equipped with
Draft Hoods, Category 1 Appliances and Appliances Listed for Use with Type B Vents.
Appendix CD - Piping Standards for Various Appliances
Appendix CE - Venting Methods
Appendix CF - Sizing of Water Piping System
Appendix NB - (Rb) Solar-Ready Provisions - Detached One- and Two-Family Dwellings and Townhouses
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 64 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Article IV, Section 8-400
Submitted by:
Building Safety Code Committee
Sec. 8-400 Adopted; where filed; amendments.
That certain document known as “The International Existing Building Code, 2024 Edition,” which has been 
published as a code in book form by the International Code Council (ICC), chapters one through sixteen and 
appendix chapters A, A1 through A5 and B, three (3) copies with amendments of which are on file in the office of 
the City Clerk, and this same code, appendices and amendments are hereby referred to, adopted and made a part 
hereof, as if fully set forth in this article.
(Ord. No. 2008.72, 12-11-08; Ord. No. O2015.12, 4-2-15)
Charter reference – Adoption by reference. §2.14.
State law reference - Adoption by reference. A.R.S. §9-801 et. seq.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 65 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Chapter 1
Submitted by:
Building Safety Code Committee
Chapter 1 Scope and Administration
Notes:
1.
For reserved sections herein, refer to the City of Tempe Administrative Code for these code requirements.
2.
Any conflicts between this code and the Tempe Administrative Code, the Tempe Administrative Code shall apply.
101.1 Title.  These regulations shall be known as the International Existing Building Code as amended by the City of Tempe 
Building Code of [NAME OF JURISDICTION], hereinafter referred to as “this code.” These regulations are one document of 
the overall City of Tempe Construction Code as defined by the adopting ordinance.
101.2.2 Application of fire code. - Where work regulated by this code is also regulated by the construction requirements for 
existing buildings in Chapter 11 of the International Fire Code, such work shall comply with applicable requirements in both 
codes.
101.5 Safeguards during construction. – Reserved
Section 102 Applicability – Reserved
Section 103 Code compliance agency – Reserved
Section 104 Duties and powers of code official – Reserved
Section 105 Permits – Reserved
Section 106 Construction documents – Reserved
Section 107 Temporary uses, equipment and systems – Reserved
Section 108 Fees – Reserved
Section 110 Certificate of occupancy – Reserved
Section 111 Service utilities – Reserved
Section 112 Means of appeals – Reserved
Section 113 Violations – Reserved
Section 114 Stop work order – Reserved
Section 115 Unsafe structures and equipment – Reserved

Page 66 of 144
Section 116 Emergency measures – Reserved
Section 117 Demolition – Reserved
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 67 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 109.3.1.1
Submitted by:
Building Safety Code Committee
109.3.1.1 Stem Wall Inspection.  Shall be made after any reinforcement is in place and forms (if needed) are in 
place. Cast in place hardware shall be in place at time of inspection.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 68 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 109.3.1.2
Submitted by:
Building Safety Code Committee
109.3.1.2 Concrete pre-slab and under-floor inspection.  Concrete slab and under-floor inspections shall be 
made after in-slab or under-floor reinforcing steel and building service equipment, conduit, piping accessories and 
other ancillary equipment items are in place, but before any concrete is placed or floor sheathing installed, 
including the subfloor.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 69 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 109.3.4.1
Submitted by:
Building Safety Code Committee
109.3.4.1 Strap and Shear.  All bracing, hardware, and holddowns are in place.  Roof sheathing is in place and 
fastened, all structural sheathing is in place and properly fastened.  Approved truss layout and calculations shall 
be onsite at time of inspection.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 70 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 109.3.5
Submitted by:
Building Safety Code Committee
109.3.5 Lath and gypsum panel product inspection.   Lath and gypsum panel inspections shall be made after 
lathing and gypsum panel products, interior and exterior, are in place but before any plastering is applied or 
before gypsum panel product joints and fasteners are taped and finished.
Exception: Gypsum panels that are not part of a fire-resistance-rated assembly or a shear assembly.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 71 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 306.7.12
Submitted by:
Building Safety Code Committee
306.7.12 Toilet rooms.
Where it is technically infeasible to alter existing toilet rooms to be accessible, one accessible single-user toilet room or one 
accessible family or assisted-use toilet room constructed in accordance with Section 1110.2.1 of the International Building Code 
is permitted. This toilet room shall be located on the same floor and in the same area as the existing toilet rooms. At the 
inaccessible toilet rooms, directional signs indicating the location of the nearest such toilet room shall be provided. These 
directional signs shall include the International Symbol of Accessibility, and sign characters shall meet the visual character 
requirements in accordance with ICC A 117.1. One of two or more fixtures (water closets and/or urinals) may be removed to 
create space for one wheelchair accessible toilet compartment in each existing toilet room. The resulting reduction in water closets 
is permitted to create a conforming wheelchair accessible toilet compartment in each existing toilet room. Alterations under this 
section shall not reduce other accessibility requirements including, but not limited to, required clear floor spaces and 
clearances.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 72 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 502.3
Submitted by:
Building Safety Code Committee
[BS] 502.3 Existing structural elements carrying gravity load
Any existing gravity load-carrying structural element for which an addition and its related alterations cause an increase in design 
gravity loads dead, live or snow load, including snow drift effects, of more than 5 percent shall be replaced or altered as needed to 
carry the gravity loads required by the International Building Code for new structures. Any existing gravity load-carrying 
structural element whose vertical load-carrying capacity is decreased as part of the addition and its related alterations shall be 
considered to be an altered element subject to the requirements of Section 503.3. Any existing element that will form part of the 
lateral load path for any part of the addition shall be considered to be an existing lateral load-carrying structural element subject to 
the requirements of Section 502.3. 
Exceptions: 
1.
Buildings of Group R occupancy with not more than five dwelling or sleeping units used solely for residential purposes 
where the existing building and the addition together comply with the conventional light-frame construction methods of 
the International Building Code or the provisions of the International Residential Code.
2.
Structural elements whose design gravity load combination is increased by not more than 5 percent and whose gravity 
load-carrying capacity has not been decreased. Determination of the percent increase shall account for the cumulative 
effects of additions or alterations since original construction.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 73 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 503.3
Submitted by:
Building Safety Code Committee
[BS] 503.3 Existing structural elements carrying gravity load.
Any existing gravity load-carrying structural element for which an alteration causes an increase in design gravity loads dead, live 
or snow load, including snow drift effects, of more than 5 percent shall be replaced or altered as needed to carry the gravity loads 
required by the International Building Code for new structures. Any existing gravity load-carrying structural element whose 
gravity load-carrying capacity is decreased as part of the alteration shall be shown to have the capacity to resist the applicable 
design gravity loads dead, live and snow loads including snow drift effects required by the International Building Code for new 
structures.
Exceptions: 
1.
Buildings of Group R occupancy with not more than five dwelling or sleeping units used solely for residential purposes 
where the altered building complies with the conventional light-frame construction methods of the International 
Building Code or the provisions of the International Residential Code.
2.
Buildings in which the increased dead load is due entirely to the addition of a second layer of roof covering weighing 3 
pounds per square foot (0.1437 kN/m2) or less over an existing single layer of roof covering.
3.
Structural elements whose design gravity load combination is increased by not more than 5 percent and whose gravity 
load-carrying capacity has not been decreased. Determination of the percent increase shall account for the cumulative 
effects of additions or alterations since original construction.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 74 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 706.2
Submitted by:
Building Safety Code Committee
[BS] 706.2 Addition or replacement of roofing or replacement of equipment.
Any existing gravity load-carrying structural element for which an alteration causes an increase in design gravity loads dead, live 
or snow load, including snow drift effects, of more than 5 percent shall be replaced or altered as needed to carry the gravity loads 
required by the International Building Code for new structures. 
Exceptions: 
1.
Buildings of Group R occupancy with not more than five dwelling or sleeping units used solely for residential purposes 
where the altered building complies with the conventional light-frame construction methods of the International 
Building Code or the provisions of the International Residential Code.
2.
Buildings in which the increased dead load is due entirely to the addition of a second layer of roof covering weighing 3 
pounds per square foot (0.1437 kN/m2) or less over an existing single layer of roof covering.
3.
Structural elements whose design gravity load combination is increased by not more than 5 percent and whose gravity 
load-carrying capacity has not been decreased. Determination of the percent increase shall account for the cumulative 
effects of additions or alterations since original construction.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 75 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 805.2
Submitted by:
Building Safety Code Committee
[BS] 805.2 Addition or replacement of roofing or replacement of equipment.
Any existing gravity load-carrying structural element for which an alteration causes an increase in design gravity loads dead, live 
or snow load, including snow drift effects, of more than 5 percent shall be replaced or altered as needed to carry the gravity loads 
required by the International Building Code for new structures. Any existing gravity load-carrying structural element whose 
gravity load-carrying capacity is decreased as part of the alteration shall be shown to have the capacity to resist the applicable 
design gravity loads dead, live and snow loads, including snow drift effects, required by the International Building Code for new 
structures. 
Exceptions: 
1.
Buildings of Group R occupancy with not more than five dwelling or sleeping units used solely for residential purposes 
where the altered building complies with the conventional light-frame construction methods of the International 
Building Code or the provisions of the International Residential Code.
2.
Buildings in which the increased dead load is attributable to the addition of a second layer of roof covering weighing 3 
pounds per square foot (0.1437 kN/m2) or less over an existing single layer of roof covering.
3.
Structural elements whose design gravity load combination is increased by not more than 5 percent and whose gravity 
load-carrying capacity has not been decreased. Determination of the percent increase shall account for the cumulative 
effects of additions or alterations since original construction.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 76 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 1103.1
Submitted by:
Building Safety Code Committee
[BS] 1103.1 Additional Gravity Loads
Any existing gravity load-carrying structural element for which an addition and its related alterations cause an increase in design 
gravity loads dead, live or snow load, including snow drift effects, of more than 5 percent shall be replaced or altered as needed to 
carry the gravity loads required by the International Building Code for new structures. Any existing gravity load-carrying 
structural element whose gravity load-carrying capacity is decreased as part of the addition and its related alterations shall be 
considered to be an altered element subject to the requirements of Section 805.2. Any existing element that will form part of the 
lateral load path for any part of the addition shall be considered to be an existing lateral load-carrying structural element subject to 
the requirements of Section 1103.2. 
Exceptions: 
1.
Buildings of Group R occupancy with not more than five dwelling units or sleeping units used solely for residential 
purposes where the existing building and the addition together comply with the conventional light-frame construction 
methods of the International Building Code or the provisions of the International Residential Code.
2.
Structural elements whose design gravity load combination is increased by not more than 5 percent and whose gravity 
load-carrying capacity has not been decreased.
Determination of the percent increase shall account for the cumulative effects of additions or alterations since original 
construction.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 77 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 1202.2
Submitted by:
Building Safety Code Committee
[BS] 1202.2 Repair and Replacement.
Repair and replacement of existing or missing features using original materials shall be permitted. Partial replacement for repairs 
that match the original in configuration, height, and size shall be permitted. Glazing is subject to the requirements of Section 
1203.8. Replacement glazing in hazardous locations shall comply with the safety glazing requirements of Chapter 24 of 
the International Building Code. 
Exception: Glass block walls, louvered windows, and jalousies repaired with like materials.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 78 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 1203.3
Submitted by:
Building Safety Code Committee
1203.3 Means of egress and emergency escape and rescue.
Where, in the opinion of the code official, there is sufficient width and height for a person to pass through the opening or traverse 
the means of egress, existing window and door openings, and corridor and stairway widths are not required to meet the widths 
required by the International Building Code or this code. Where approved by the code official, the front or main exit doors 
need not swing in the direction of the path of exit travel, provided that other approved means of egress having sufficient capacity 
to serve the total occupant load are provided. 
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 79 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Existing Building Code (IEBC)
Section 1204.6
Submitted by:
Building Safety Code Committee
1204.6 Means of egress and emergency escape and rescue.
Existing window and door openings, and corridor and stairway widths less than those that would be acceptable for non-historic 
buildings under these provisions shall be approved, provided that, in the opinion of the code official, there is sufficient width and 
height for a person to pass through the opening or traverse the exit and that the capacity of the exit system is adequate for the 
occupant load, or where other operational controls to limit occupancy are approved by the code official. 
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 80 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Energy Conservation Code (IECC)
Article IX, Section 8-900
Submitted by:
Building Safety Code Committee
Sec. 8-900. Adopted; where filed; amendments.
That certain document known as the “International Energy Conservation Code, 2024 Edition,” which has been 
published as a code in book form by the International Code Council (ICC), chapters one through six and appendix 
chapter CB for commercial provisions, and chapters one through six and appendix chapter RB for residential 
provisions, three (3) copies with amendments of which are on file in the office of the City Clerk, and this same 
code, and amendments are hereby referred to, adopted and made a part hereof, as if fully set forth in this article.
(Ord. No. 2008.72, 12-11-08; Ord. No. O2015.12, 4-2-15)
Charter reference – Adoption by reference. §2.14.
State law reference - Adoption by reference. A.R.S. §9-801 et. seq.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 81 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Energy Conservation Code (IECC)
Chapter 1 [CE]
Submitted by:
Building Safety Code Committee
Chapter 1 Scope and Administration
Notes:
1.
For reserved sections herein, refer to the City of Tempe Administrative Code for these code requirements.
2.
Any conflicts between this code and the Tempe Administrative Code, the Tempe Administrative Code shall apply.
C101.1 Title. This code shall be known as the International Energy Conservation Code as amended by the City of  Tempe [name 
of jurisdiction] and shall be cited as such. It is referred to herein as “this code or the Energy Code”. These regulations are one 
document of the overall Tempe Construction Code as defined by the adopting ordinance.
C101.2 Scope. This code applies to the design and construction of buildings not covered by the scope of the IECC-Residential 
Provisions. Group R-2 when defined as a Commercial Building by section C202, shall have the option of complying under the 
Residential Provisions of the code, regardless of height. Once defined as such on the submittal documents, all components of the 
Residential Provisions shall be followed.
C101.4 Compliance. Residential buildings shall meet the provisions of IECC - Residential Provisions. Commercial 
buildings shall meet the provisions of IECC - Commercial Provisions. Group R-2 when defined as a Commercial Building by 
section C202, shall have the option of complying under the Residential Provisions of the code, regardless of height. Once defined 
as such on the submittal documents, all components of the Residential Provisions shall be followed.
Section C102 Applicability.  - Reserved
Section C103 Code Compliance Agency.  - Reserved
Section C104 Alternative Materials, Design and Methods of Construction and Equipment.  - Reserved
Section C105 Construction Documents.  - Reserved
Section C106 Fees.  - Reserved
Section C108 Notice of Approval.  - Reserved
Section C109 Means of Appeals - Reserved
Section C110 Stop Work Order - Reserved
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 82 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Energy Conservation Code (IECC)
Chapter 4 [CE], Section C401.2.1
Submitted by:
Building Safety Code Committee
C401.2.1 International Energy Conservation Code.
Commercial buildings shall comply with one of the following:
1.
Prescriptive Compliance. The Prescriptive Compliance option requires compliance with Sections C402 through C406 
and Sections C408. Dwelling units and sleeping units in Group R-2 buildings shall be deemed to be in compliance with 
this chapter, provided that they comply with Section R406.
2.
Simulated Building Performance. The Simulated Building Performance option requires compliance with Section C407.
Exceptions:
1.
Additions, alterations, repairs, and changes of occupancy to existing buildings complying with Chapter 5.
2.
Compliance with the provisions of Section C408 is optional.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 83 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Energy Conservation Code (IECC)
Chapter 4 [CE], Section C405.12, C405.13, C405.14, and C405.15
Submitted by:
Building Safety Code Committee
C405.12 Automatic Receptacle Control
This section shall be deleted in its entirety.
Note: The corresponding requirements in ASHRAE 90.1 8.4.2 Automatic Receptacle Control is also deleted in its entirety.
C405.13 Energy Monitoring
This section is deleted in its entirety.
Note: The corresponding requirements in ASHRAE 90.1 8.4.3 Electrical Energy Monitoring is also deleted in its entirety.
C405.14 Reserved
C405.15 Renewable Energy Systems 
This section is deleted in its entirety.
Note: The corresponding requirements in ASHRAE 90.1 10.5.1 Renewable Energy Systems is also deleted in its entirety.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 84 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Energy Conservation Code (IECC)
Chapter 1 [RE]
Submitted by:
Building Safety Code Committee
R101.1 Title. This code shall be known as the International Energy Conservation Code as amended by the City of  Tempe [name 
of jurisdiction] and shall be cited as such. It is referred to herein as “this code or the Energy Code”. These regulations are one 
document of the overall Tempe Construction Code as defined by the adopting ordinance.
R101.2 Scope. This code applies to the design and construction of buildings not covered by the scope of the IECC-Residential 
Provisions. Group R-2 when defined as a Residential Building by section R202, shall have the option of complying under the 
Commercial Provisions of the code, regardless of height. Once defined as such on the submittal documents, all components of the 
Commercial Provisions shall be followed.
R101.4 Compliance. Residential buildings shall meet the provisions of IECC—Residential Provisions. Commercial 
buildings shall meet the provisions of IECC—Commercial Provisions. Group R-2 when defined 
as a Residential Building by section R202, shall have the option of complying under the 
Commercial Provisions of the code, regardless of height. Once defined as such on the submittal 
documents, all components of the Commercial Provisions shall be followed.
Section R102 Applicability.  - Reserved
Section R103 Code Compliance Agency.  - Reserved
Section R104 Alternative Materials, Design and Methods of Construction and Equipment.  - Reserved
Section R105 Construction Documents.  - Reserved
Section R106 Fees.  - Reserved
Section R108 Notice of Approval.  - Reserved
Section R109 Means of Appeals - Reserved
Section R110 Stop Work Order - Reserved
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 85 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Energy Conservation Code (IECC)
Chapter 4 [RE], Section 401.1
Submitted by:
Building Safety Code Committee
R401.1 Scope.
This chapter applies to residential buildings.
Exceptions:
Exterior lighting requirements for footcandles levels that are required by the City of Tempe, Zoning and 
Development Code, are not regulated by this code.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 86 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Energy Conservation Code (IECC)
Chapter 4 [RE], Section 404.1.5
Submitted by:
Building Safety Code Committee
R404.1.5 Gas lighting.
Gas-fired lighting appliances shall not be equipped with a continuous pilot and shall be equipped 
with an on-demand pilot, intermittent ignition or interrupted ignition as defined by ANSI Z21.20.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 87 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Energy Conservation Code (IECC)
Chapter 4 [RE], Section 503.1.2
Submitted by:
Building Safety Code Committee
R503.1.2 Heating and cooling systems.
New heating and cooling systems and ductwork that are part of the alteration shall comply with Section R403 and 
this section. Alterations to existing heating and cooling systems and ductwork shall comply with this section.
Exception: 
1.
Where ductwork from an existing heating and cooling system is extended.
2.
Where additions do not exceed 250 square feet and do not exceed the capacities of the existing system.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 88 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendments to 2024 International Fuel Gas Code (IFGC)
Article VII, Section 8-700
Submitted by:
Building Safety Code Committee
Sec. 8-700.  Adopted; where filed; amendments.
That certain document known as “The International Fuel Gas Code, 2024 Edition,” which has been published as a 
code in book form by the International Code Council (ICC), chapters one through eight and appendix chapters A, 
B, and C inclusive, three (3) copies with amendments of which are on file in the office of the City Clerk, and this 
same code, appendices and amendments are hereby referred to, adopted and made a part hereof, as if fully set 
forth in this article.
(Ord. No. 2008.72, 12-11-08; Ord. No. O2015.12, 4-2-15)
Charter reference – Adoption by reference. §2.14.
State law reference - Adoption by reference. A.R.S. §9-801 et. seq.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 89 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Fuel Gas Code (IFGC)
Chapter 1
Submitted by:
Building Safety Code Committee
Chapter 1 Scope and Administration
Notes:
1.
For reserved sections herein, refer to the City of Tempe Administrative Code for these code requirements.
2.
Any conflicts between this code and the Tempe Administrative Code, the Tempe Administrative Code shall apply.
101.1 Title.  These regulations shall be known as the International Fuel Gas Code as amended by the City of Tempe Building 
Code of [NAME OF JURISDICTION], hereinafter referred to as “this code.” These regulations are one document of the overall 
City of Tempe Construction Code as defined by the adopting ordinance.
101.2 Scope. - Reserved
101.2.1 Appendices.  Provisions in the appendices shall not apply unless specifically adopted.  Appendix chapters A, B and C are 
adopted as part of this code.
102.5 Change in occupancy. - Reserved
102.8 Referenced codes and standards. - Reserved
Exception: Where enforcement of a code provision would violate the conditions of the listing of the equipment or appliance, the 
conditions of the listing and the manufacturer’s installation instructions shall apply.
102.8.1 Conflicts. - Reserved.
102.8.2 Provisions in referenced codes and standards. - Reserved.
102.10 Other laws. - Reserved.
Section 103 (IFGC) Code compliance agency - Reserved.
Section 104 (IFGC) Duties and powers of the code official - Reserved.
Section 105 (IFGC) Permits - Reserved.
Section 106 (IFGC) Construction documents - Reserved.
Section 107 (IFGC) Notice of approval - Reserved.
Section 108 (IFGC) Fees - Reserved.
Section 109 (IFGC) Service utilities - Reserved.
Section 110 (IFGC) Temporary uses, equipment and systems - Reserved.

Page 90 of 144
Section 112 (IFGC) Means of Appeals - Reserved.
Section 113 (IFGC) Violations - Reserved.
Section 114 (IFGC) Stop Work Order - Reserved.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 91 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Fuel Gas Code (IFGC)
Chapter 4, Section 403.11
Submitted by:
Building Safety Code Committee
403.11 Flanges.  Flanges and flange gaskets shall comply with Sections 403.11.1 through 403.11.7.
403.11.1 Cast iron.
Cast-iron flanges shall be in accordance with ASME B16.1
403.11.2 Steel.
Steel flanges shall be in accordance with ASME B16.5 or ASME B16.47.
403.11.3 Nonferrous.
Nonferrous flanges shall be in accordance with ASME B16.24 except listed components 
using aluminum flange connections constructed in accordance with dimensional 
specifications of ANSI/ASME B16.5.
403.11.4 Ductile iron.
Ductile-iron flanges shall be in accordance with ASME B16.42.
403.11.5 Raised face.
Raised face flanges shall not be joined to flat faced cast-iron, ductile-iron or nonferrous 
material flanges.
403.11.6 Flange facings.
Standard facings shall be permitted for use under this code. Where 150-pound (1034 kPa) 
pressure-rated steel flanges are bolted to Class 125 cast-iron flanges, the raised face on the 
steel flange shall be removed.
403.11.7 Lapped flanges.
Lapped flanges shall be used only above ground or in exposed locations accessible for 
inspection.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 92 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendments to 2024 International Green Construction Code (IgCC)
Article III, Section 8-300
Submitted by:
Building Safety Code Committee
Sec. 8-800. Adopted; where filed; amendments.
That certain document known as “the International Green Construction Code, 2024 edition,” which has been 
published as a code in book form by the International Code Council (ICC), chapters 1 through 11, appendix 
chapters A through N, and annex 1 inclusive, and this same code, appendices, annex,  and amendments are hereby 
referred to, adopted, and made a part hereof, as if fully set forth in this article and amended as follows:  
(Ord. No. 2008.72, 12-11-08; Ord. No. O2015.12, 4-2-15)
Charter reference – Adoption by reference. §2.14.
State law reference - Adoption by reference. A.R.S. §9-801 et. seq.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 93 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 Internation Green Construction Code (IgCC)
Chapter 1
Submitted by:
Building Safety Code Committee
Chapter 1 Scope and Administration
Notes:
3.
For reserved sections herein, refer to the City of Tempe Administrative Code for these code requirements.
4.
Any conflicts between this code and the Tempe Administrative Code, the Tempe Administrative Code shall apply.
101.1 Title.  These regulations shall be known as the International Green Construction Code Building Code of [NAME OF 
JURISDICTION], hereinafter referred to as “this code.” These regulations are one document of the overall City of Tempe 
Construction Code as defined by the adopting ordinance.
101.2 (2.3) General. - The use of this code is optional, unless specifically required through ordinance by the City of Tempe. This 
code is an overlay document to be used in conjunction with the other codes and standards adopted by the jurisdiction. This code is 
not intended to be used as a standalone construction regulation document and permits are not to be issued under this code. This 
code is not intended to abridge or supersede safety, health or environmental requirements under other applicable codes or 
ordinances. 
This code is intended to provide minimum requirements to be used in conjunction with the other codes and standards adopted by 
the jurisdiction. The requirements in this code shall not be used to circumvent any applicable safety, health or environmental 
requirements.
101.5.1 Jurisdictional options. - Reserved.
101.5.4 (4.3.4) Referenced standard reproduction annexes. - Reserved.
102 Applicability - Reserved.
Section 103 (IgCC) Code Compliance Agency - Reserved.
Section 104 (IgCC) Duties and powers of the Authority Having Jurisdiction - Reserved.
Section 105 (IgCC) Permits - Reserved.
Section 106 (IgCC) Construction Documents - Reserved.
Section 107 (IgCC) Fees - Reserved.
Section 109 (IgCC) Certificate of Occupancy - Reserved.
Section 110 (IgCC) Means of Appeals - Reserved.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 94 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Article V, Section 8-500 
Submitted by:
Building Safety Code Committee
Sec 8-500 Adopted; where filed; amendments.
That Certain document known as “The International Mechanical Code, 2024 Edition,” which has been published 
as a code in book form by the International Code Council (ICC), chapters one through nine and chapters eleven, 
twelve, fourteen, fifteen and appendix chapter A inclusive, three (3) copies with amendments of which are on file 
in the office of the City Clerk, and this same code, appendix and amendments are hereby referred to, adopted and 
made a part hereof, as if fully set forth in this article.
(Ord. No. 2008.72, 12-11-08; Ord. No. O2015.12, 4-2-15)
Charter reference – Adoption by reference. §2.14.
State law reference - Adoption by reference. A.R.S. §9-801 et. seq.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 95 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Chapter 1
Submitted by:
Building Safety Code Committee
Chapter 1 Scope and Administration
Notes:
5.
For reserved sections herein, refer to the City of Tempe Administrative Code for these code requirements.
6.
Any conflicts between this code and the Tempe Administrative Code, the Tempe Administrative Code shall apply.
101.1 Title.  These regulations shall be known as the International Mechanical Code as amended by the City of Tempe Building 
Code of [NAME OF JURISDICTION], hereinafter referred to as “this code or IMC”. These regulations are one document of the 
overall City of Tempe Construction Code as defined by the adopting ordinance.
101.2 Appendices. Provisions in the appendices shall not apply unless specifically adopted. Appendix A is 
adopted.
101.4 Severability. - Reserved.
102.1 General. - Reserved.
102.8 Referenced codes and standards. - Reserved
Exception: Where enforcement of a code provision would violate the conditions of the listing 
of the equipment or appliance, the conditions of the listing and the manufacturer’s installation 
instructions shall apply.
102.8.1 Conflicts. - Reserved.
102.8.2 Provisions in referenced codes and standards. - Reserved.
102.10 Other laws. - Reserved.
102.11 Application of references. - Reserved.
Section 103 Code compliance agency - Reserved.
Section 104 Duties and powers of the code official - Reserved.
Section 105 Permits - Reserved.
Section 106 Construction documents - Reserved.
Section 107 Notice of approval - Reserved.
Section 108 Fees - Reserved.
Section 109 Service utilities - Reserved.

Page 96 of 144
Section 110 Temporary uses, equipment and systems - Reserved.
Section 112 Means of appeals - Reserved.
Section 113 Board of appeals - Reserved.
Section 114 Violations - Reserved.
Section 115 Stop work order - Reserved.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 97 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 309.1
Submitted by:
Building Safety Code Committee
[BG] 309.1 Space-heating systems. Heating and cooling systems.  Interior spaces intended for human occupancy shall be 
provided with active or passive space-heating and cooling systems capable of maintaining an indoor temperature of not less than 
68°F (20°C) between 70°F (21°C) and 82°F (28°C) (if cooled by air conditioning, and 88°F (31°C) if cooled by evaporative 
cooling), measured at a point 3 feet (914mm) above the floor in the center of the room. on the design heating day. The installation 
of portable space heaters or coolers shall not be used to achieve compliance with this section.
Exceptions:
2.
Space heating and cooling systems are not required for interior spaces where the primary purpose is not associated
with human comfort.
2.      Group F, H, S, and U occupancies.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 98 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 313.1
Submitted by:
Building Safety Code Committee
313.1 Mechanical special inspections and observations. The owner or the owner’s authorized agent, other than 
the contractor, shall employ the registered design professional responsible for the mechanical design or one or 
more approved agencies designated by the registered design professional responsible for the mechanical design to 
perform visual observations of complex mechanical equipment and systems for general conformance to the 
approved plans and specification, including but not limited to, placement and interconnection of equipment and 
shall identify the approved agencies to the building official in accordance with Section 1704.2 of the International 
Building Code as amended. Mechanical observations shall be performed at significant stages of the construction 
when the installation is complete and ready for inspection. Mechanical observations are in addition to and not in 
lieu of inspections required by the Tempe Administrative Code, Section 110, and by Section 1705.12.6 of the 
International Building Code, and shall be provided when one of the following conditions exist: 
1.  Duct smoke detectors for air distribution systems as install in accordance with Section 606 of this code.
2.  Fire, fire/smoke, radiation and smoke damper operation for dampers install in accordance with Section 
607 of this code.
3.  Installation of alternative grease duct enclosure systems including but not limited to grease duct-wrap 
or double wall grease duct systems, install in accordance with Sections 506.3.11.2and 506.3.11.3 of this 
code.
4.  The welding of grease duct joints, seams penetrations, and duct-to-hood joints required by Section 
506.3.2 and 506.3.2.2 of this code.
5.  The required grease duct leakage test required by Section 506.3.2.5 of this code.
6.  Type I hood performance test and the capture and containment test required by Section 507.6 and 
507.6.1 of this code.
7.  Test and Balance report for air balance of ventilation systems installed in ambulatory care and I-2 
occupancies designed and installed in accordance with ASHRAE 170 as required by Section 407.1 of this 
code.
8.  Hazardous exhaust systems install in accordance with Section 510 of this code.
9.  Smoke control systems in accordance with Section 513 of this code.
10.  Special cases – Work which, in the opinion of the building official, involves unusual hazards or 
conditions.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 99 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 407.1
Submitted by:
Building Safety Code Committee
407.1 General. Mechanical ventilation for ambulatory care facilities and Group I-2 occupancies shall be designed and installed in 
accordance with this code and ASHRAE 170.
407.1.1 Special Inspection. Mechanical systems designed and installed in accordance with IMC 407.1 and ASHRAE 
170 shall be verified by a qualified third party Special Inspector. The Special Inspector/testing agency shall be an 
independent third party individual or firm and shall not be the installing contractor. A report shall be generated by the 
third party individual or firm showing compliance. Special inspections shall be as specified in Chapter 17 of the 
International Building Code as amended.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 100 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 408.1
Submitted by:
Building Safety Code Committee
408.1 General. Any building or portion thereof used to cultivate, produce, process, infuse or dispense marijuana 
shall be designed such that no emissions of dust, fumes, vapors or odors are introduced into the environment from 
the building or portion thereof. A ventilation system shall be designed to prevent the distribution of odors to other 
occupied spaces in the building or adjacent properties. Design of the odor control system shall be based on 
acceptable engineering practices. All equipment and filter media shall be listed and labeled for the application. 
Exhaust systems used in odor control systems shall meet the requirements of Section 501 of this code.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 101 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 408.1.1
Submitted by:
Building Safety Code Committee
408.1.1 Exhaust outlets. The termination point of exhaust outlets shall be in accordance with Section 501.3 of 
this code. Exhaust from cultivation and production facilities shall be in accordance with Section 501.3.1(2) of this 
code and for dispensaries in accordance with Section 501.3.1(3) of this code. 
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 102 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 502.14
Submitted by:
Building Safety Code Committee
502.14 Motor vehicle operation. In areas where motor vehicles operate, mechanical ventilation shall be provided in accordance 
with Section 403 Additionally, areas in which stationary motor vehicles are operated shall be provided with a source capture 
system that connects directly to the motor vehicle exhaust systems. Makeup air for the required exhaust systems in areas where 
motor vehicles operate shall be provided through permanent unobstructed openings to the outdoors, such as louvers and grills. 
Mechanical equipment and louvers used for makeup air purposes shall be electrically interlocked with the exhaust system. Such 
system shall be engineered by a registered design professional or shall be factory-built equipment designed and sized for the 
purpose.
Exceptions:
1.  This section shall not apply where the motor vehicles being operated or repaired are electrically powered.
2.  This section shall not apply to one- and two-family dwellings.
3.  This section shall not apply to motor vehicle service areas where engines are operated inside the building only for the
     duration necessary to move the motor vehicles in and out of the building.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 103 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 606.2.1
Submitted by:
Building Safety Code Committee
606.2 Where required. Smoke detectors shall be installed where indicated in Sections 606.2.1 through 606.2.3.
Exception: Smoke detectors shall not be required where air distribution systems are incapable of spreading smoke 
beyond the enclosing walls, floors and ceilings of the room or space in which the smoke is generated.
606.2.1 Return air systems. Air distribution systems. Smoke detectors shall be installed in return air systems with air 
distribution systems downstream of the filters and ahead of any branch connections in systems having a design capacity 
greater than 2,000 cfm (0.9 m3/s). in-the return air duct or plenum upstream of any filters, exhaust air connections, 
outdoor air connections, or decontamination equipment and appliances.
Exception: Smoke detectors are not required in the return air system where all portions of the building served 
by the air distribution system are protected by area smoke detectors connected to a fire alarm system in 
accordance with the International Fire Code. The area smoke detection system shall comply with Section 
606.4.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 104 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 608.1
Submitted by:
Building Safety Code Committee
608.1 Balancing. Air distribution, ventilation and exhaust systems shall be provided with means to adjust the 
system to achieve the design airflow rates and shall be balanced by an approved method. Ventilation 
air distribution shall be balanced by an approved method and such balancing shall verify that the air distribution 
system is capable of supplying and exhausting the airflow rates required by Chapter 4. 
The ventilation air distribution system shall be provided with means to adjust the system to achieve not less than 
the minimum ventilation airflow rate as required by sections 403.3 and 403.3.1.2. Ventilation systems shall be 
balanced using a nationally accepted air balancing test method. Such balancing shall verify that the ventilation 
system is capable of supplying and exhausting the airflow rates required by Sections 403.3 and 403.3.1.2. A final 
report shall be provided to the engineer of record and the Tempe Building Inspector.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 105 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section  928.1
Submitted by:
Building Safety Code Committee
928.1 General. Evaporative cooling equipment shall:
1.
Be installed in accordance with the manufacturer’s instructions.
2.
Be installed on level platforms in accordance with Section 304.10.
3.
Have openings in exterior walls or roofs flashed in accordance with the International Building Code.
4.
Be provided with an approved water supply, sized for peak demand. The quality of water shall be provided in 
accordance with the equipment manufacturer’s recommendations. The piping system and protection of the potable 
water supply system shall be installed as required by the International Plumbing Code.
5.
Have air intake opening locations in accordance with Section 401.4.
6.
A permanent relief opening or other engineered design sufficient to assure positive airflow shall balance intake air.
7.
Outside air shall be provided as specified in Section 403.2.
8.
Air ducts and dampers, which are a portion of an evaporative cooling system, shall comply with Chapter 6.
9.
Overflow drains shall be provided that discharge to an approved disposal location.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 106 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 932.1
Submitted by:
Building Safety Code Committee
932.1 General. On or after December 31, 1998, no person, firm, or corporation shall construct or install a 
fireplace or a woodstove, and the city shall not approve or issue a permit to construct or install a fireplace or a 
woodstove, unless the fireplace or woodstove complies with one of the following:
1.
A fireplace which has permanently installed gas or electric log insert;
2.
A fireplace, woodstove, or other solid-fuel-burning appliance which has been certified by the United 
States Environmental Protection Agency as conforming to 40 Code of Federal Regulations Part 60, 
Subpart AAA;
3.
A fireplace, woodstove, or other solid-fuel-burning appliance that has been tested and listed by a 
nationally recognized testing agency to meet performance standards equivalent to those adopted by 40 
Code of Federal Regulations Part 60, Subpart AAA;
4.
A fireplace, woodstove, or other solid-fuel-burning appliance that has been determined by the Maricopa 
County Air Pollution Control Officer to meet performance standards equivalent to those adopted by 40 
Code of Federal Regulations Part 60, Subpart AAA; or
5.
A fireplace that has a permanently installed woodstove insert that complies with paragraphs 2, 3, or 4 
above.
Exception: The following installations are not regulated and are not prohibited by this section:
1.
Furnaces, boilers, incinerators, kilns, and other similar space heating or industrial process 
equipment;
2.
Cook stoves, barbecue grills, and similar appliances designed primarily for cooking; and
3.
Fire pits, barbecue grills, and other outdoor fireplaces. 
Fireplaces constructed or installed on or after December 31, 1998, that contain a gas or electric log insert or a 
woodstove insert, shall not be altered to directly burn wood or any other solid fuel. On or after December 31, 
1998, no person, firm, or corporation shall alter a fireplace, woodstove, or other solid-fuel-burning appliance in 
any manner that would void its certification or operational compliance with the provisions of this section.  
Fireplaces constructed or installed on or after December 31, 1998, shall not be altered without first obtaining a 
permit from the city to ensure compliance with this section.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 107 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 1001.1
Submitted by:
Building Safety Code Committee
1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and 
pressure vessels, except where regulated by the Industrial Commission of Arizona.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 108 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 1105.10
Submitted by:
Building Safety Code Committee
1105.10 Dimensions. Refrigeration machinery rooms shall be of such dimensions that all system parts are readily accessible with 
adequate space for service, maintenance, and operations. A minimum unobstructed walking space at least three (3) feet (914 mm) 
in width and six (6) feet eight (8) inches (2032 mm) in height or approved manufacturer’s installation or required clearances shall 
be maintained throughout, allowing free access to at least two sides of all moving machinery and approaching each stop valve. 
Access to refrigeration machinery rooms shall be restricted to authorized personnel and posted with permanent signage.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 109 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Mechanical Code (IMC)
Section 1109.2.5
Submitted by:
Building Safety Code Committee
1109.2.5 Refrigerant pipe shafts. Refrigerant piping that penetrates two or more floor/ceiling assemblies shall 
be enclosed in a fire-resistance-rated shaft enclosure. The fire-resistance-rated shaft enclosure shall comply with 
Section 713 of the International Building Code.
Exceptions:
1.  Refrigeration systems using R-718 refrigerant (water).
2.  Piping in a direct refrigeration system using Group A1 refrigerant where the
     refrigerant quantity does not exceed the limits of Table 1103.1 for the smallest
     occupied space through which the piping passes.
3.  Piping located on the exterior of the building where vented to the outdoors
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 110 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment the 2024 International Plumbing Code
Article VI, Section 8-600
Submitted by:
Building Safety Code Committee
Sec. 8-600 Adopted; where filed; amendments.
That certain document known as “The International Plumbing Code, 2024 Edition,” which has been published as 
a code in book form by the International Code Council (ICC), chapters one through fifteen and, appendix chapters 
B, C, and E inclusive, three (3) copies with amendments of which are on file in the office of the City Clerk, and 
this same code, appendix and amendments are hereby referred to, adopted and made a part hereof, as if fully set 
forth in this article.
(Ord. No. 2008.72, 12-11-08; Ord. No. O2015.12, 4-2-15)
Charter reference – Adoption by reference. §2.14.
State law reference - Adoption by reference. A.R.S. §9-801 et. seq.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 111 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Chapter 1
Submitted by:
Building Safety Code Committee
Chapter 1 Scope and Administration
Notes:
7.
For reserved sections herein, refer to the City of Tempe Administrative Code for these code requirements.
8.
Any conflicts between this code and the Tempe Administrative Code, the Tempe Administrative Code shall apply.
101.1 Title.  These regulations shall be known as the International Plumbing Code as amended by the City of Tempe Building 
Code of [NAME OF JURISDICTION], hereinafter referred to as “this code or IPC”. These regulations are one document of the 
overall City of Tempe Construction Code as defined by the adopting ordinance.
101.2.1 Appendices. Provisions in the appendices shall not apply unless specifically adopted. Appendices B, C, 
& E are adopted in this code.
101.4 Severability. - Reserved.
102.1 General. - Reserved.
102.8 Referenced codes and standards. - Reserved
102.8.1 Conflicts. - Reserved.
102.8.2 Provisions in referenced codes and standards. - Reserved.
102.10 Other laws. - Reserved.
102.11 Application of references. - Reserved.
Section 103 Code compliance agency - Reserved.
Section 104 Duties and powers of the code official - Reserved.
Section 105 Permits - Reserved.
Section 106 Construction documents - Reserved.
Section 107 Notice of approval - Reserved.
Section 108 Fees - Reserved.
Section 109 Service utilities - Reserved.
Section 110 Temporary uses, equipment and systems - Reserved.

Page 112 of 144
Section 112 Means of appeals - Reserved.
Section 113 Board of appeals - Reserved.
Section 114 Violations - Reserved.
Section 115 Stop work order - Reserved.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 113 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 111.3 and 111.3.2
Submitted by:
Building Safety Code Committee
Section 111 Inspections and Testing
111.3 Special inspections. Special inspections of alternative engineered design plumbing systems shall be 
conducted in accordance with Sections 111.3.1 and 111.3.2 and chapter 17 of the International Building Code as 
adopted.
111.3.2 Written report.  The registered design professional shall submit a final report and the completed special 
inspection certificate in writing to the code official upon completion of the installation, certifying that 
the alternative engineered design conforms to the approved construction documents and that all special 
inspections have been conducted. A notice of approval for the plumbing system shall not be issued until a written 
certification has been submitted.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 114 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 312.1.1
Submitted by:
Building Safety Code Committee
312.1.1 Test gauges. Gauges used for testing shall be as follows: 
1.
Tests requiring a pressure of 10 psi (69 kPa) or less shall utilize a testing gauge having increments of 
0.10 psi (0.69 kPa) or less. 
2.
Tests requiring a pressure of greater than 10 psi (69 kPa) but less than or equal to 100 psi (689 kPa) shall 
utilize a testing gauge having increments of 1 psi (6.9 kPa) or less. 
3.
Tests requiring a pressure of greater than 100 psi (689 kPa) shall utilize a testing gauge having 
increments of 2 psi (14 kPa) or less. 
4.
Pressure tests required by this code, which are performed utilizing dial gauges, shall be limited to a 
gauge having a maximum gauge rating not exceeding twice the applied test pressure.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 115 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 317.1
Submitted by:
Building Safety Code Committee
317.1 Plumbing special inspections and observations. The owner or the owner’s authorized agent, other than 
the contractor, shall employ the registered design professional responsible for the plumbing design or one or more 
approved agencies designated by the registered design professional responsible for the plumbing design to 
perform visual observations of complex plumbing equipment and systems for general conformance to the 
approved plans and specification, including but not limited to, placement and interconnection of equipment and 
shall identify the approved agencies to the building official in accordance with Section 1704.2 of the International 
Building Code as amended. Plumbing observations shall be performed at significant stages of the construction 
and when the installation is complete and ready for inspection. Plumbing observations are in addition to and not 
in lieu of inspections required by the Tempe Administrative Code, Section 110, and Section 1705.12.6 of the 
International Building Code, and shall be provided when one of the following conditions exist:
1.
Alternative engineered design plumbing systems as allowed by Section 316 of this code. 
2.
Computer designed drainage and vacuum drainage systems as allowed Sections 713 and 715 of this 
code.
3.
Medical gas and vacuum systems as allowed by Section 1202 of this code.
4.
Non-medical oxygen systems as allowed by the Section 1203 of this code.
5.
Non-potable water systems as allowed Chapters 13 and 14 of this code.
6.
Special cases – Work which, in the opinion of the building official, involves unusual hazards or 
conditions.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 116 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 403.2
Submitted by:
Building Safety Code Committee
403.2 Separate facilities.  Where plumbing fixtures are required, separate toilet facilities shall be provided for each sex.
Exceptions:
1.
Separate toilet facilities shall not be required for dwelling units and sleeping units.
2.
Separate toilet facilities shall not be required in structures or tenant spaces with a total occupant load, 
including both employees and customers, of 1530 or fewer.
3.
Separate toilet facilities shall not be required in mercantile occupancies in which the maximum occupant load 
is 100 30 or fewer.
4.
Separate toilet facilities shall not be required in business occupancies in which the maximum occupant load is 
25 30 or fewer.
5.
Separate toilet facilities shall not be required to be designated by sex where single- user toilet rooms are 
provided in accordance with Section 403.1.2.
6.
Separate toilet facilities shall not be required where rooms having both water closets and lavatory fixtures are 
designed for use by all persons regardless of sex and privacy is provided for water closets in accordance with 
Section 405.3.4 and for urinals in accordance with Section 405.3.5.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 117 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 410.2
Submitted by:
Building Safety Code Committee
410.2 Small occupancies.  Drinking fountains shall not be required for an occupant load of 15 30 or fewer.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 118 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 410.4, 416.3
Submitted by:
Building Safety Code Committee
410.4 Substitution.  Occupancies that provide food and/or beverage service to patrons do not need to provide drinking fountains. 
In other occupancies, where drinking fountains are required, water dispensers, bottled water dispensers or bottled water, where 
free of charge, shall be permitted to be substituted for not more than 50 percent of the required number of drinking 
fountains. Where restaurants provide drinking water in a container free of charge, drinking fountains shall not be required in those 
restaurants. In other occupancies where three or more drinking fountains are required, water dispensers shall be permitted to be 
substituted for not more than 50 percent of the required number of drinking fountains.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 119 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 416.3
Submitted by:
Building Safety Code Committee
416.3 Commercial food waste disposer. Commercial food waste disposers are not allowed per the Public Works 
Director.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 120 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 605.25
Submitted by:
Building Safety Code Committee
605.25 Non-Metallic Potable Water Pipe, Fittings, and Valves.  Non-Metallic potable water pipe, fittings, and valves shall not 
be exposed in exterior outdoor locations. Components of the exterior exposed potable water system shall be metallic only and 
approved metallic materials, fittings, and valves are listed in IPC Table 605.3, IPC Table 605.4, IPC Table 605.5, and IPC Table 
605.6.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 121 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Chapter 1
Submitted by:
Building Safety Code Committee
608.7.2 Secondary backflow protection.
The following activities or facilities shall have a Secondary Reduced Pressure Principle Backflow Prevention assembly installed 
as close as practicable to each point of service delivery: Hospitals, surgical clinics, medical buildings, laboratories, morgues, 
mortuaries, veterinary hospitals, animal grooming shops, industrial occupancies, packing plants, slaughter houses, chemical 
plants, municipal waste treatment facilities, auxiliary water systems, construction water services or as otherwise required by the 
City of Tempe Building Official.
Note: Multiple water services which are interconnected onsite shall be provided with not less than a Double Check Valve 
Assembly at each service connection.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 122 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 608.8
Submitted by:
Building Safety Code Committee
608.8 Valves and outlets prohibited below grade.  Potable water outlets and combination stop-and-waste valves shall not be 
installed underground or below grade. A freezeproof yard hydrant that drains the riser into the ground shall be considered as 
having a stop-and-waste valve below grade. 
Exception: Freezeproof yard hydrants that drain the riser into the ground shall be permitted to be installed, provided 
that the potable water supply to such hydrants is protected in accordance with Section 608.14.2 or 608.14.5 ASSE 1057 
Freeze Resistant Sanitary Yard Hydrant with Backflow Protection, and the hydrants and the piping from the backflow
preventer to the hydrant are identified in accordance with Section 608.9. 
608.8.1 Prohibited Locations.  Backflow prevention devices shall not be installed in pits, underground vaults, or 
submerged locations.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 123 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 903.1.1
Submitted by:
Building Safety Code Committee
903.1.1 Roof extension unprotected.  Open vent pipes that extend through a roof shall be terminated not less than 
6 [NUMBER] inches (152 mm) above the roof.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 124 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 1003.1, 1003.3
Submitted by:
Building Safety Code Committee
1003.1 Where required.  Interceptors and separators shall be provided to prevent the discharge of oil, grease, 
sand and other substances harmful or hazardous to the public sewer, the private sewage system or the sewage 
treatment plant or processes. The Public Works Director may require additional conditions when interceptors and 
separators are required.
1003.3 Grease interceptors. Grease interceptors shall comply with the requirements of Sections 1003.3.1 
through 1003.3.8.  The Public Works Director may provide additional requirements.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 125 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 1106.1
Submitted by:
Building Safety Code Committee
1106.1 General. The size of the vertical conductors and leaders, scuppers, building storm drains, building storm 
sewers and any horizontal branches of such drains or sewers shall be based on the 100-year hourly rainfall rate of 
three (3) inches (76 mm) per hour. indicated in Figures 1106.1(1) through 1106.1(5) or on other rainfall rates 
determined from approved local weather data.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 126 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Section 1109.1
Submitted by:
Building Safety Code Committee
1109.1 General.  All storm water related installations and alterations shall follow the currently adopted City of 
Tempe Storm Water Management Plan.  Where the public sewer is a combined system for both sanitary and 
storm water, the storm sewer shall be connected independently to the public sewer. 
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 127 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Plumbing Code (IPC)
Appendices B, C, and E
Submitted by:
Building Safety Code Committee
Adopt Appendices B, C, & E.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 128 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Swimming Pool and Spa Code (ISPSC)
Article X, Section 8-1000
Submitted by:
Building Safety Code Committee
Sec. 8-1000. Adopted; where filed; amendments.
That certain document known as “The International Swimming Pool and Spa Code, 2024 Edition,” which has 
been published as a code in book form by the International Code Council (ICC), chapters one through eleven, 
three (3) copies with amendments of which are on file in the office of the City Clerk, and this same code, and 
amendments are hereby referred to, adopted and made a part hereof, as if fully set forth in this article.
(Ord. No. 2008.72, 12-11-08; Ord. No. O2015.12, 4-2-15)
Charter reference – Adoption by reference. §2.14.
State law reference - Adoption by reference. A.R.S. §9-801 et. seq.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 129 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Swimming Pool and Spa Code (ISPSC)
Chapter 1
Submitted by:
Building Safety Code Committee
Chapter 1 Scope and Administration
Notes:
1.
For reserved sections herein, refer to the City of Tempe Administrative Code for these code requirements.
2.
Any conflicts between this code and the Tempe Administrative Code, the Tempe Administrative Code shall apply.
101.1 Title.  These regulations shall be known as the International Swimming Pool and Spa Code (ISPSC) as amended by the 
City of Tempe Building Code of [NAME OF JURISDICTION], hereinafter referred to as “this code.” These regulations are one 
document of the overall City of Tempe Construction Code as defined by the adopting ordinance.
101.4 Severability. – Reserved
Section 102 Applicability
102.1 General. – Reserved
102.7 Referenced codes and standards. - Reserved.
102.9 Other laws. - Reserved.
102.10 Application of references. - Reserved.
Section 103 Code compliance agency – Reserved
Section 104 Duties and powers of the code official – Reserved
Section 105 Permits – Reserved
Section 106 Temporary structures, equipment and systems – Reserved
Section 107 Construction documents – Reserved
Section 108 Notice of approval – Reserved
Section 109 Fees – Reserved
Section 110 Service utilities – Reserved
Section 112 Means of appeals – Reserved
Section 113 Violations – Reserved
Section 114 Stop work order – Reserved

Page 130 of 144
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 131 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Swimming Pool and Spa Code (ISPSC)
Chapter 2
Submitted by:
Building Safety Code Committee
Residential Swimming Pool (residential pool). A pool intended for use, that is accessory to a residential setting and available 
only to the household and its guests including any structure intended for swimming or recreational bathing that contains water 
over 18 inches (457.2mm) deep. This includes in-ground, above ground and on ground swimming pools, hot tubs, spas, and fixed 
in place wading pools. All Oother pools shall be considered to be public pools for the purpose of this code.
Public Swimming Pool (Public Pool). A pool, other than a residential pool, that is intended to be used for 
swimming or bathing and is operated by an owner, lessee, operator, licensee or concessionaire, regardless of 
whether a fee is charged for use. Public pools shall be further classified and defined as follows:
Class A competition pool. A pool intended for use for accredited competitive aquatic events such as 
Federation International De Natation (FINA), USA Swimming, USA Diving, USA Synchronized 
Swimming, USA Water Polo, National Collegiate Athletic Association (NCAA), or the National 
Federation of State High School Associations (NFHS).
Class B public pool. A pool intended for public recreational use that is not identified in the other 
classifications of public pools.
Class C semi-public pool. A pool operated solely for and in conjunction with lodgings such as hotels, 
motels, apartments or condominiums, townhouse complexes, trailer courts, mobile home parks, or 
similar establishments. A semipublic pool includes a pool that is operated by a neighborhood or 
community association for the residents of the community and their guests and a swimming pool at a 
country club, camp or similar establishment where the primary business of the establishment is not the 
operation of a swimming pool and where the use of the swimming pool is included in the fee for the 
primary use of the establishment. This includes in-ground, aboveground, and on-ground pools; spas and 
fixed in-place wading pools.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 132 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Swimming Pool and Spa Code (ISPSC)
Section 301.1.2, 301.1.3, 301.1.4
Submitted by:
Building Safety Code Committee
301.1.2 Unenclosed pools. It is hereby declared to be a violation of this code and a public nuisance and 
dangerous to the public health, safety, and welfare to maintain an outdoor swimming pool or spa in the city unless 
enclosed by a barrier in accordance with Section 305.2 of this code. It shall be the responsibility of both the 
property owner and the occupant of the premises to install and maintain the fences, locks, latches, alarms, and 
gates that make up the barrier in good condition and proper working order when water is in the pool, either or 
both may be deemed in violation of this code for failure to do so.
301.1.3 Prerequisites to issuance of building permit. A building permit shall not be issued for any swimming 
pool, spa or hot tub unless the plans for such pool provide for barrier requirements as required by this code.
301.1.4 Final inspection and approval. No swimming pool, spa or hot tub shall be filled in whole or in part with 
water unless the pool barrier requirements have been installed in accordance with this code and approved by the 
building official or authorized representative.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 133 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Swimming Pool and Spa Code (ISPSC)
Chapter 305.1
Submitted by:
Building Safety Code Committee
305.1 General.  The provisions of this section shall apply to the design of barriers for restricting entry into areas having pools and 
spas. Where spas or hot tubs are equipped with a lockable safety cover complying with ASTM F1346 and swimming pools are 
equipped with a powered safety cover that complies with ASTM F1346, the areas where those spas, hot tubs or pools are located 
shall not be required to comply with Sections 305.2 through 305.7. 
It is the responsibility of the property owner and any other person in responsible charge of a swimming pool to ensure that the 
required swimming pool barrier, including all gates, doors, locks, latches, and other portions of the barrier are maintained safe and 
in good working order at all times. No person shall alter or remove any portion of a swimming pool barrier except to repair, 
reconstruct, or replace the barrier in compliance with the provisions of this section. All barriers shall be installed, inspected, and 
approved prior to plastering or filling with water.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 134 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Swimming Pool and Spa Code (ISPSC)
Section 305.2.1
Submitted by:
Building Safety Code Committee
305.2.1 Barrier height and clearances.
Barrier heights and clearances shall be in accordance with all of the following:
1.
The top of the barrier shall be not less than 48 60 inches (1219 1525 mm) above grade where measured 
on the side of the barrier that faces away from the pool or spa. Such height shall exist around the entire 
perimeter of the barrier and for a distance of 3 feet (914 mm) measured horizontally from the outside of 
the required barrier.
2.
The vertical clearance between grade and the bottom of the barrier shall not exceed 2 inches (51 mm) for 
grade surfaces that are not solid, such as grass or gravel, where measured on the side of the barrier that 
faces away from the pool or spa.
3.
The vertical clearance between a surface below the barrier to a solid surface, such as concrete, and the 
bottom of the required barrier shall not exceed 4 inches (102 mm) where measured on the side of the 
required barrier that faces away from the pool or spa.
4.
Where the top of the pool or spa structure is above grade, the barrier shall be installed on grade or shall 
be mounted on top of the pool or spa structure. Where the barrier is mounted on the top of the pool or 
spa, the vertical clearance between the top of the pool or spa and the bottom of the barrier shall not 
exceed 4 inches (102 mm).
5.
The inside of a barrier shall be not closer than 24 inches (610 mm) to the nearest edge of the water of a 
pool or spa measured perpendicular from the fence to the water’s edge.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 135 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2024 International Swimming Pool and Spa Code (ISPSC)
Section 305.2.5
Submitted by:
Building Safety Code Committee
305.2.5 Mesh fence as a barrier.
Mesh fences, other than chain link fences in accordance with Section 305.2.8, shall be installed in accordance 
with the manufacturer’s instructions and shall comply with ASTM F2286 and with both all of the following:
1.
Where a hinged gate is used with a mesh fence, the gate shall comply with Section 305.3.
2.
 Mesh fences shall not be installed on top of onground residential pools.
3.
 Mesh fences shall be installed with a positive attachment of all parts are made with hardware that is 
appropriate to the performance test requirements and requires a tool to remove.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 136 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2023 National Electrical Code (NEC)
Article VIII, Section 8-800
Submitted by: 
Building Safety Code Committee
Sec. 8-800. Adopted; where filed; amendments.
That certain document known as “The National Electrical Code, 2023 Edition,” that which has been published as 
a code in book form by the National Fire Protection Association entitled National Electrical Code, N.F.P.A. No. 
70-2023 edition, article ninety and chapters one through nine, three (3) copies with amendments of which are on 
file in the office of the City Clerk, and this same code, and amendments are hereby referred to, adopted and made 
a part of, as if fully set out in this article.
(Ord. No. 2008.72, 12-11-08; Ord. No. O2015.12, 4-2-15)
Charter reference – Adoption by reference. §2.14.
State law reference - Adoption by reference. A.R.S. §9-801 et. seq.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 137 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2023 National Electrical Code (NEC)
Article 90
Submitted by:
Building Safety Code Committee
Article 90 Introduction
Notes:
1.
For reserved sections herein, refer to the City of Tempe Administrative Code for these code requirements.
2.
Any conflicts between this code and the Tempe Administrative Code, the Tempe Administrative Code shall apply.
90.1 Scope. This article covers use and application, arrangement, and enforcement of this Code. It also covers the expression of 
mandatory, permissive, and nonmandatory text, provides guidance on the examination of equipment and on wiring planning, and 
specifies the use and expression of measurements.
90.1.1 Title.  These regulations shall be known as the National Electrical Code as amended by the City of Tempe hereinafter 
referred to as “this code or NEC”. These regulations are one document of the overall City of Tempe Construction Code as defined 
by the adopting ordinance.
90.1.2 Authority.  Where used in this article, the term authority having jurisdiction shall include the building official or other 
individuals designated by the building official. This Code shall be administered and enforced by the authority having jurisdiction 
designated by the governing authority as follows:
1.  The authority having jurisdiction shall be permitted to render interpretations of this Code in order to provide 
clarification to its requirements, as permitted by 90.4.
2.  When the use of any electrical equipment or its installations is found to be dangerous to human life or property, the 
authority having jurisdiction shall be empowered to have the premises disconnected from its source of electric supply. 
When such equipment or installation has been so condemned or disconnected, a notice shall be placed thereon listing 
the causes for the condemnation, the disconnection, or both, and the penalty established by 80.23 for the unlawful use 
thereof. Written notice of such condemnation or disconnection and the causes therefore shall be given within 24 hours 
to the owners, the occupant, or both, of such building, structure, or premises. It shall be unlawful for any person to 
remove said notice, to reconnect the electrical equipment to its source of electric supply, or to use or permit to be used 
electric power in any such electrical equipment until such causes for the condemnation or disconnection have been 
remedied to the satisfaction of the inspection authorities.
3.  The authority having jurisdiction shall be authorized to inspect, at all reasonable times, any building or premises for 
dangerous or hazardous conditions or equipment as set forth in this Code. The authority having jurisdiction shall be 
permitted to order any person(s) to remove or remedy such dangerous or hazardous condition or equipment. Any 
person(s) failing to comply with such order shall be in violation of this Code.
4.  Where the authority having jurisdiction deems that conditions hazardous to life and property exist, he or she shall be 
permitted to require that such hazardous conditions in violation of this Code be corrected.
5.  The authority having jurisdiction shall be permitted to investigate the cause, origin, and circumstances of any fire, 
explosion, or other hazardous condition.
6.  The authority having jurisdiction shall be permitted to require plans and specifications to ensure compliance with this 
Code.
7.  Whenever any installation subject to inspection prior to use is covered or concealed without having first been 
inspected, the authority having jurisdiction shall be permitted to require that such work be exposed for inspection. The 
authority having jurisdiction shall be notified when the installation is ready for inspection and shall conduct the 
inspection.

Page 138 of 144
90.1.3 Inspections and Approvals.  Inspections shall be made throughout the installation process and shall be requested by the 
permit holder.  Work shall not be continued until required inspections has been passed.
1.  Upon the completion of any installation of electrical equipment that has been made under a permit other than an 
annual permit, it shall be the duty of the person, firm, or corporation making the installation to notify the building 
official, who shall cause the work to be inspected.
2.  Underground electrical work shall be inspected and made prior to the concealing any of the work or conduits
3.  Rough Electrical work shall be inspected prior to being covered by other materials and prior to the installation of 
fixtures
4.  Electrical Equipment Inspection. Prior to energizing all wiring within the panel shall be secured and landed.
5.  Other electrical inspections, special inspections, observation and reports as required by the building official.
6.  Final Electrical Inspection.  Electrical shall be energized and all over current protection devices are to be in place and 
all required arc fault, ground fault interruption, fuses, surge protection devices and all other protection devices installed 
in their permanent location.
90.1.4 Connection to Electricity Supply.  Connections to the electric supply shall conform to 80.25(A) through 
(C).
(A) Authorization.  Except where work is done under an annual permit and except as otherwise provided in 
80.25, it shall be unlawful for any person, firm, or corporation to make connection to a supply of electricity 
or to supply electricity to any electrical equipment installation for which a permit is required or that has been 
disconnected or ordered to be disconnected.
(B) Special Consideration.  By special permission of the authority having jurisdiction, temporary power 
shall be permitted to be supplied to the premises for specific needs of the construction project. 
(C) Disconnection.  Where a connection is made to an installation that has not been inspected, as outlined in 
the preceding paragraphs of this section, the supplier of electricity shall immediately report such connection 
to the Building Official.  If, upon subsequent inspection, it is found that the installation is not in conformity 
with the provisions of Article 80, building official shall notify the person, firm, or corporation making the 
installation to rectify the defects immediately without delay or a longer period of time as determined by the 
building official.  If such work is not completed within the period as may be specified, the building official 
shall have the authority to cause the disconnection of that portion of the installation that is not in conformity.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 139 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2023 National Electrical Code (NEC)
Article 110.2
Submitted by:
Building Safety Code Committee
110.2 Approval. The conductors and equipment required or permitted by this Code shall be acceptable only if 
approved.
110.2.1 Electrical special inspections and observation. The owner or the owner’s authorized agent, other than 
the contractor, shall employ the registered design professional responsible for the electrical design or one or more 
approved agencies designated by the registered design professional responsible for the electrical design to 
perform visual observations of complex electrical equipment and systems for general conformance to the 
approved plans and specification, including but not limited to, placement and interconnection of equipment and 
shall identify the approved agencies to the building official in accordance with Section 1704.2 of the International 
Building Code as amended. Electrical observations shall be performed at significant stages of the construction 
when the installation is complete and ready for inspection. Electrical observations are in addition to and not in 
lieu of inspections required by Section 110 of the Tempe Administrative Code and Section 1705.12.6 of the 
International Building Code, and shall be provided when one of the following conditions exist:
1.
Ground-fault protection performance tests for equipment with ground-fault protect.
2.
Switch boards, panelboards, motor control centers and other equipment rated at 1,000 amperes or more or 
over 600 volts.
3.
The installation or alteration of electrical systems over 600V.
4.
Transformers rated 100 kVA or more, single phase or 300 kVA or more three-phase.
5.
Insulation integrity of conductors that supply equipment rated at 1,000 amperes or more, or over 600 volts.
6.
Emergency and standby power systems, including switchboards, panelboards, distribution boards, transfer 
equipment, power source, conductors, fire pumps, exhaust and ventilation fans.
7.
Selective Coordination – This includes verification of the installation in accordance with the required 
selective coordination study. 
8.
The installation or alteration of that portion of a health care facility’s electrical system which fall under the 
scope of Article 517 of this code, including such systems installed in facilities where outpatient surgical 
procedures are performed.
9.
The installation or alteration of electrical systems within locations classified as hazardous by provisions of 
this code, except for gasoline dispensing installations and systems located within storage garages, repair garages 
or lubritorium’s.
10. Special cases – Work which, in the opinion of the building official, involves unusual hazards or conditions.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 140 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2023 National Electrical Code (NEC)
Article 110.7
Submitted by:
Building Safety Code Committee
110.7 Wiring Integrity. Completed wiring installations shall be free from short circuits, ground faults, or any 
connections to ground other than as required or permitted elsewhere in this code. All equipment rated at 1,000 
amperes or more shall be tested for insulation breakdown prior to its being energized. This test shall be performed 
by an independent testing facility or agency approved by the authority having jurisdiction and in accordance with 
this code.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 141 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2023 National Electrical Code (NEC)
Article 210.52
Submitted by:
Building Safety Code Committee
210.52 (G)(1) Garages. In each attached garage and in each detached garage that is provided with electric power, 
at least one GFCI receptacle outlet shall be installed in each vehicle bay at not less than 457 mm (18 in.) and not 
more than 1.7 m (5½ ft.) above the floor. 
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 142 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2023 National Electrical Code (NEC)
Article 215.25
Submitted by:
Building Safety Code Committee
215.25 Feeder Circuits in Attached Single-Family Dwellings (Townhouses).  Dwelling Unit Feeders. Feeder 
circuits in each dwelling unit of attached one-family dwellings (townhouses) shall supply only loads within that 
dwelling unit or loads associated with that dwelling unit. Feeders serving adjoining townhouse dwelling units 
shall not pass through, above, below, or be attached to other townhouse dwelling units. This applies regardless of 
ownership of the individual townhouse units.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 143 of 144
CITY OF TEMPE CONSTRUCTION CODE AMENDMENTS
Amendment to 2023 National Electrical Code (NEC)
Article 250.118
Submitted by:
Building Safety Code Committee
250.118 Types of Equipment Grounding Conductors. The equipment grounding conductor run with or 
enclosing the circuit conductors shall be one or more or a combination of the following:
(4) Electrical metallic tubing with an additional equipment grounding conductor.
Adopted by City of Tempe Ord. No. 2011.33, 9-22-11; Ord. No. 02015.12, 4-2-15
Effective TBD

Page 144 of 144