15. Z2023088 PZ Report

Maricopa County — Planning & Zoning (2023-10-05)

View PDF Item 15 Meeting page

Extracted text (via pymupdf) 41067 characters
Z2023088 
Page 1 of 5 
 
 
Report to the Planning and Zoning Commission 
Prepared by the Maricopa County Planning and Development Department 
 
 
Case: 
Z2023088 - Delaney Substation Communication Tower 
 
 
 
 
Hearing Date: 
October 5, 2023 
 
Supervisor District: 
4 
 
 
 
  
 
Applicant: 
DCR Transmission LLC 
 
Owner: 
Arizona Public Service Company (APS) 
   
Request: 
Special Use Permit to allow a 260’ microwave communications tower 
 
  
 
Site Location: 
Generally located NW of Salome Hwy & Courthouse Road 
 
  
Site Size: 
Approximately 3,780 sq. ft.   
 
Density: 
N/A 
 
County Island:  
No 
 
 
County Plan: 
Tonopah / Arlington Area Plan 
 
Rural Densities (0-1) 
 
Municipal Plan: 
N/A 
 
Municipal Comments: 
None received to date  
 
Support/Opposition: 
None known 
 
Recommendation: 
Approve with conditions

Z2023088 
Page 2 of 5 
Project Summary: 
 
1. 
The applicant, DCR Transmission LLC, is requesting a special use  permit (SUP) on a Rural-43 
zoned parcel for the use of a microwave communications tower. The subject parcel 506-31-006D 
is an operating electrical power substation (known as the Delaney Substation) owned by Arizona 
Public Service Company otherwise known as APS. APS created the Delaney Substation in 
approximately 2010 to prepare for utility solar power generation facilities that are planned in the 
immediate area. The proposed 260’ microwave communications tower will allow 
communications between Delaney and other electrical substations to allow APS to better 
understand the power needs and shortcomings within its electrical grid network.   
 
2. 
The proposed microwave communications tower will be comprised of 2 microwave 
communications antennae. The tower is a triangular structure extending to 250’ with a 10’ 
lightning rod placed at the top.  
 
 
 
Existing On-Site and Adjacent Zoning / Land Use: 
 
3. 
On-site: 
 
Rural-43 / Electrical substation  
North: 
IND-1 / Vacant  
South: 
Rural-43 / Vacant (AZ State Land)  
East: 
Rural-43 / Vacant (AZ State Land)  
West: 
IND-1 / Vacant

Z2023088 
Page 3 of 5 
 
 
Utilities and Services: 
 
4. 
Water: 
 
N/A 
 
Wastewater: 
N/A 
 
Fire: 
Tonopah Valley Fire District 
Police:  
Maricopa County Sherriff  
 
Right-of-Way: 
 
5. 
The following table includes existing and proposed half-width right-of-way and the future 
classification based upon the Maricopa County Department of Transportation (MCDOT) Major 
Streets and Routes Plan.   
 
Street Name 
Half-width Existing R/W 
Half-width Proposed R/W 
Future Classification 
Thomas Rd. 
40’ 
40’ 
Minor Arterial 
 
Adopted Plan: 
 
6. 
Tonopah / Arlington Area Plan (adopted September 6, 2000): The area is established as Rural 
Density Development Area (0-1). Utility infrastructure and substations are acceptable uses with 
the rural density comprehensive plan land element.  
 
Public Participation Summary: 
 
7. 
The applicant notified the surrounding parcel owners of the proposal within 300’. The site has 
also been posted pursuant to Maricopa County requirements. The applicant met all public 
participation requirements. There has been no public comments received.  
 
 
Outstanding Concerns from Reviewing Agencies: 
 
8. 
Luke Air Force Base has reviewed the proposal noting that the tower is in the general area that it 
conducts 
its 
training 
exercises. 
The 
agency 
reviewing 
stated 
the 
tower 
will 
“not negatively impact the flying and base operations at Luke AFB”. The agency did request 
additional “Aviation Obstruction Light (AOL) or Aircraft Warning Light (ACWL)” to be installed due 
to height and location of the tower. The applicant has complied with the request adding an 
additional light to the tower per the request.  
 
Staff Analysis: 
 
9. 
The immediate areas to the west and north of the subject parcel have been both rezoned and 
comprehensively planned for utility scale solar generation facilities. The request for the 
microwave communications facility will allow the owner, APS, to better manage its electrical 
loads on transmission lines which will benefit all anyone with access to the power grid. The tower 
height is requested specifically due to the technical aspects of microwave communications 
needing line of sight for transmission purposes. The vast distances between the utility 
substations justify the height proposed.

Z2023088 
Page 4 of 5 
Recommendation: 
 
10. 
Staff recommends the Commission adopt a motion recommending that the Board of Supervisors 
approve Z2023088 subject to the following conditions ‘a’ – ‘g’. 
 
a. 
Development of the site shall be in substantial conformance with the Site Plan entitled 
“Delaney Substation DCRT MW Tower“, consisting of 8 full-size sheets, dated August 21, 
2023, except as modified by the following conditions. Staff may determine slight 
refinements to remain in substantial conformance with the approved site plan.   
 
b. 
Development of the site shall be in substantial conformance with the Narrative Report 
entitled “Delaney Substation Communication Tower”, consisting of 12 pages, dated 
August 22, 2023, except as modified by the following conditions. 
 
c. 
The following engineering conditions:  
 
1. A section line , Thomas Road, coincides with the south boundary of the parcel. 
Per an approval of reduction, a 40-foot reservation will be required for Thomas 
Road. 
 
2. A mid-section alignment is located on the eastern perimeter of the proposed  
development requiring building setbacks to start from a future half street of 40-
feet per the Maricopa County Zoning and Ordinance Section 11105. 
 
3. All development and engineering design shall be in conformance with Section 
1205 of the Maricopa County Zoning Ordinance; Drainage Policies and Standards; 
Floodplain Regulations for Maricopa County; MCDOT Roadway Design Manual; 
and current engineering policies, standards and best practices at the time of 
application for construction. 
 
4. Engineering review of planning and/or zoning cases is for conceptual design 
only and does not represent final design approval nor shall it entitle applicants to 
future designs that are not in conformance with Section 1205 of the Maricopa 
County Zoning Ordinance and Drainage Policies and Standards; Floodplain 
Regulations for Maricopa County; and the MCDOT Roadway Design Manual. 
 
5. Detailed Grading and Drainage Plans showing the new site improvements must 
be submitted for the acquisition of building permits 
 
d. 
Tower lighting and marking must meet all FAA regulations. 
 
e. 
This special use permit is valid for a period of 50 years and shall expire on October 18, 
2073, or upon termination of the use for a period of 90 or more days, whichever occurs 
first. All site improvements associated with the special use permit shall be removed within 
90 days of such expiration or termination of use.   
 
f. 
The granting of this change in use of the property has been at the request of the applicant, 
with the consent of the landowner.  The granting of this approval allows the property to 
enjoy uses in excess of those permitted by the zoning existing on the date of application, 
subject to conditions.  In the event of the failure to comply with any condition, and at the 
time of expiration of the Special Use Permit, the property shall revert to the zoning that

Z2023088 
Page 5 of 5 
existed on the date of application.  It is, therefore, stipulated and agreed that either 
revocation due to the failure to comply with any conditions, or the expiration of the Special 
Use Permit, does not reduce any rights that existed on the date of application to use, 
divide, sell or possess the property and that there would be no diminution in value of the 
property from the value it held on the date of application due to such revocation or 
expiration of the Special Use Permit.  The Special Use Permit enhances the value of the 
property above its value as of the date the Special Use Permit is granted and reverting to 
the prior zoning results in the same value of the property as if the Special Use Permit had 
never been granted. 
 
g. 
Noncompliance with any Maricopa County Regulation shall be grounds for initiating a 
revocation of this Special Use Permit as set forth in the Maricopa County Zoning 
Ordinance.  
 
 
 
Presented by: 
Andrew Lorentzen, Planner 
Reviewed by: 
Matthew Holm, AICP, Planning Supervisor 
 
Attachments: 
Case Map (1 page) 
 
Site Plan (8 pages) 
 
Narrative Report (12 pages) 
 
MCDOT comments (1 page) 
 
Luke AFB Comments (2 pages)

/
Maricopa County Planning & Development - Phoenix, AZ
4
Gross Acres: 1 approx.
Generated September 21, 2023 2:22 PM
Z2023088
Application Name:
Legal Description
Delaney Substation Communication Tower EDR
Applicant
Case Address
T02N R08W 025,
Jason Crew for DCR Transmission, L.L.C.
45550 W SALOME Hwy
Applicant Phone/Email
Parcel Primary:506-31-006D
713.569.8995
jcrew@lotuspartners.com
TONOPAH AZ 85354
Map scale 1:3,268
Supervisor District No.
DCR TRANSMISSION, L.L.C. (“DCRT”), AN AFFILIATE OF LOTUS INFRASTRUCTURE PARTNERS, SEEKS
A SPECIAL USE PERMIT FOR THE INSTALLATION OF A NEW 250-FOOT MICROWAVE COMMUNICATION

REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL 
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY 
OF ALL PEOPLE LOCATED ON THE WORK SITE, 
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL 
(OR THAT OF ITS SUB-CONTRACTOR(S)) 
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS 
DRAWING BY AN ORGANIZATION OTHER THAN 
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY 
OF SARGENT & LUNDY.
1
A
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING 
DOCUMENT WAS PREPARED BY ME OR UNDER MY 
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY 
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ENTER NAME.
ENTER NAME
ENTER DATE
IS: ENTER DATE
B
SARGENT & LUNDY  
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-1501
0C
0A
03/31/23
D-E-1501.DWG
1"=100'-0"
MICROWAVE YARD LAYOUT
FOR APS REVIEW
DELANEY SUBSTATION
DCR TRANSMISSION
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPB/XXX
FOR PERMIT APPLICATION
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL 
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY 
OF ALL PEOPLE LOCATED ON THE WORK SITE, 
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL 
(OR THAT OF ITS SUB-CONTRACTOR(S)) 
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS 
DRAWING BY AN ORGANIZATION OTHER THAN 
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY 
OF SARGENT & LUNDY.
1
A
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING 
DOCUMENT WAS PREPARED BY ME OR UNDER MY 
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY 
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ENTER NAME.
ENTER NAME
ENTER DATE
IS: ENTER DATE
B
SARGENT & LUNDY  
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-2550
0C
0A
03/31/23
D-E-2550.DWG
1"=10'-0"
LATTICE TOWER
FOR APS REVIEW
PLAN VIEW & SECTIONS
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPB/XXX
FOR PERMIT APPLICATION
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)
45°
45°
45°

8'-6"
19'-0"
LEGEND:
NOTES:
CONSTRUCTION NOTES:
SCALE
1.
ONLY ONE (1) MAIN GROUND BAR (MGB) TO BE INSTALLED IN ORDER TO ENSURE
SINGLE-POINT GROUNDING. LOCATE MGB AT POINT OF FEEDLINE ENTRY THAT IS
MOST PRACTICAL BASED ON SITE LAYOUT. SEPARATION IN INTERIOR PERIMETER
GROUND BUS (IPGB) TO BE LOCATED ON OPPOSITE WALL OF MGB.
2.
MAIN GROUND GRID TO BE BURIED 30" BELOW FINISHED GRADE.
3.
RACK #1 IS 23" WIDTH, RACKS #2-5 ARE 19" WIDTH
COMPRESSION CONNECTION
5/8" x 20'-0" DIA. COPPERWELD GROUND ROD
300 KCM BARE COPPER, STRANDED, HARD DRAWN
GROUNDING CABLE
REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL 
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY 
OF ALL PEOPLE LOCATED ON THE WORK SITE, 
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL 
(OR THAT OF ITS SUB-CONTRACTOR(S)) 
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS 
DRAWING BY AN ORGANIZATION OTHER THAN 
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY 
OF SARGENT & LUNDY.
1
A
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING 
DOCUMENT WAS PREPARED BY ME OR UNDER MY 
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY 
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ENTER NAME.
ENTER NAME
ENTER DATE
IS: ENTER DATE
B
SARGENT & LUNDY  
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-2551
0C
0A
03/31/23
D-E-2551.dwg
1/2"=1'-0"
COMMUNICATION SHELTER
FOR APS REVIEW
 PLAN & ELEVATION VIEWS
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPB/XXX
FOR PERMIT APPLICATION
C5551
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)
REFERENCE DRAWINGS:
LATTICE TOWER PLAN & SECTIONS
D-E-2550
WAVE GUIDE BRIDGE PLAN & SECTIONS
D-E-2552
EXTERNAL GROUNDING
D-E-3501
INTERNAL GROUNDING
D-E-3502
HANDHOLE DETAIL
D-E-4501
GENSET DETAIL
D-E-4502
CONDUIT LAYOUT
D-E-2501
FOUNDATION LAYOUT
D-E-2502
GROUNDING LAYOUT
D-E-2503
MICROWAVE YARD LAYOUT
D-E-1501
CABLE TRAY
1.
CONTRACTOR/INSTALLER SHALL TAKE ALL APPROPRIATE PRECAUTIONS WITHIN OR
ADJACENT TO THE AREA IN WHICH EXCAVATION, DEMOLITION, FOUNDATION OR
MODIFICATION WORK IS TO BE PERFORMED.
2.
THE CONTRACTOR/INSTALLER SHALL EXERCISE DUE CAUTION DURING ALL
EXCAVATION/FOUNDATION/DEMOLITION WORK.
3.
CONTRACTOR/INSTALLER SHALL TAKE ALL APPROPRIATE   PRECAUTIONS TO ENSURE
THE SAFETY OF ALL PEOPLE LOCATED   ON THE WORK SITE, INCLUDING
CONTRACTOR'S/INSTALLER'S   PERSONNEL (OR THAT OF ITS SUBCONTRACTOR(S))
PERFORMING   THE WORK.
4.
FOR GENERAL NOTES SEE DWG. D-E-1501.

·
·
·
·
·
REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL 
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY 
OF ALL PEOPLE LOCATED ON THE WORK SITE, 
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL 
(OR THAT OF ITS SUB-CONTRACTOR(S)) 
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS 
DRAWING BY AN ORGANIZATION OTHER THAN 
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY 
OF SARGENT & LUNDY.
1
$DATE$
$FILEABBREV$
A
B
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING 
DOCUMENT WAS PREPARED BY ME OR UNDER MY 
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY 
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ARIZONA.
ENTER NAME
ENTER DATE
IS: ENTER DATE
$TIME$
$PINFO1$
Form GDG-0401-01-08, ANSI (Imperial) MicroStation Border - Size E - 34 x 44
Revision 11A, Revision Date: 04-30-2010
SARGENT & LUNDY  
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-2552
0C
0A
1
1
03/31/23
D-E-2552.dwg
NTS
WAVEGUIDE BRIDGE
FOR APS REVIEW
PLAN VIEW & ELEVATION VIEW
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPBXXX
FOR PERMIT APPLICATION
C5551
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)

REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL 
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY 
OF ALL PEOPLE LOCATED ON THE WORK SITE, 
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL 
(OR THAT OF ITS SUB-CONTRACTOR(S)) 
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS 
DRAWING BY AN ORGANIZATION OTHER THAN 
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY 
OF SARGENT & LUNDY.
1
$DATE$
$FILEABBREV$
A
B
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING 
DOCUMENT WAS PREPARED BY ME OR UNDER MY 
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY 
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ARIZONA.
ENTER NAME
ENTER DATE
IS: ENTER DATE
$TIME$
$PINFO1$
Form GDG-0401-01-08, ANSI (Imperial) MicroStation Border - Size E - 34 x 44
Revision 11A, Revision Date: 04-30-2010
SARGENT & LUNDY  
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-4503
0C
0A
03/31/23
D-E-4503.dwg
1"=1'-0"
RF SAFETY EXPOSURE
FOR APS REVIEW
WARNING SIGNS, LABELS PLACARDS
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPB/XXX
FOR PERMIT APPLICATION
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)

REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL 
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY 
OF ALL PEOPLE LOCATED ON THE WORK SITE, 
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL 
(OR THAT OF ITS SUB-CONTRACTOR(S)) 
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS 
DRAWING BY AN ORGANIZATION OTHER THAN 
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY 
OF SARGENT & LUNDY.
1
$DATE$
$FILEABBREV$
A
B
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING 
DOCUMENT WAS PREPARED BY ME OR UNDER MY 
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY 
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ARIZONA.
ENTER NAME
ENTER DATE
IS: ENTER DATE
$TIME$
$PINFO1$
Form GDG-0401-01-08, ANSI (Imperial) MicroStation Border - Size E - 34 x 44
Revision 11A, Revision Date: 04-30-2010
SARGENT & LUNDY  
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-4504
0C
0A
05/11/23
D-E-4504.dwg
NTS
LATTICE TOWER
FOR APS REVIEW
OBSTRUCTION LIGHTING DETAILS
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPB/XXX
FOR PERMIT APPLICATION
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)

REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL 
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY 
OF ALL PEOPLE LOCATED ON THE WORK SITE, 
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL 
(OR THAT OF ITS SUB-CONTRACTOR(S)) 
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS 
DRAWING BY AN ORGANIZATION OTHER THAN 
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY 
OF SARGENT & LUNDY.
1
A
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING 
DOCUMENT WAS PREPARED BY ME OR UNDER MY 
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY 
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ENTER NAME.
ENTER NAME
ENTER DATE
IS: ENTER DATE
B
SARGENT & LUNDY  
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-1502
0A
0A
08/21/23
D-E-1501.DWG
1"=10'-0"
MICROWAVE YARD LAYOUT
FOR PERMIT APPLICATION
DELANEY SUBSTATION
DCR TRANSMISSION
A13498.001
DELANEY SUBSTATION
DCRT MW TOWER
MDL/XXX
MPB/XXX
FOR PERMIT APPLICATION
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)

Delaney Colorado River Transmission, L.L.C.
Rev1
August 22, 2023
Project No.: 13498.001
55 East Monroe Street 
Chicago, IL 60603-5780 USA 
312-269-2000 
www.sargentlundy.com 
 
Maricopa County Special Use Permit  
Project Narrative  
 
Delaney Substation Communication Tower  
45550 W Salome Hwy 
Tonopah, AZ 85354 
Tracking # PA2023070

DCR Transmission L.L.C.  
Delaney Communication Tower 
A13498.001 
Rev1 
August 22, 2023 
 
 
Maricopa County Special Use Permit  
Pre-Application Package 
 
P. 1 
 
L E G A L N O T I C E 
This deliverable was prepared by Sargent & Lundy, L.L.C. (“S&L”) expressly for the sole use of DCR 
Transmission, L.L.C. (“Client”) in accordance with the contract agreement between S&L and Client. This 
deliverable was prepared using the degree of skill and care ordinarily exercised by engineers practicing 
under similar circumstances. Client acknowledges: (1) S&L prepared this deliverable subject to the particular 
scope limitations, budgetary and time constraints, and business objectives of Client; (2) information and data 
provided by others, including Client, may not have been independently verified by S&L; and (3) the 
information and data contained in this deliverable are time-sensitive and changes in the data, applicable 
codes, standards, and acceptable engineering practices may invalidate the findings of this deliverable. Any 
use or reliance upon this deliverable by third parties shall be at their sole risk.

DCR Transmission L.L.C.  
Delaney Communication Tower 
A13498.001 
Rev1 
August 22, 2023 
 
 
Maricopa County Special Use Permit  
Pre-Application Package 
 
P. 2 
 
V I C I N I T Y M A P

DCR Transmission L.L.C.  
Delaney Communication Tower 
A13498.001 
Rev1 
August 22, 2023 
 
 
Maricopa County Special Use Permit  
Pre-Application Package 
 
P. 3

DCR Transmission L.L.C.  
Delaney Communication Tower 
A13498.001 
Rev1 
August 22, 2023 
 
 
Maricopa County Special Use Permit  
Pre-Application Package 
 
P. 4 
 
P R O J E C T N A R R A T I V E

DCR Transmission L.L.C.  
Delaney Communication Tower 
A13498.001 
Rev1 
August 22, 2023 
 
 
Maricopa County Special Use Permit  
Pre-Application Package 
 
P. 5 
 
Introduction 
DCR Transmission, L.L.C. (“DCRT”), an affiliate of Lotus Infrastructure Partners, is a transmission utility in 
the state of California and will be a Participating Transmission Owner under the jurisdiction of the Federal 
Energy Regulatory Commission.  
DCRT seeks a Special Use Permit (“SUP”) from Maricopa County for the installation of a new microwave 
communication tower and associated infrastructure (“Project”) in Maricopa County, Arizona, on land leased 
from Arizona Public Service Company (“APS”). This project narrative was prepared by Sargent and Lundy to 
support DCRT’s SUP Application.  
The tower would be built immediately adjacent to APS’s existing Delaney Substation, which is located at 
45550 W Salome Highway, Tonopah, AZ, 85354. Lease negotiations are currently underway with APS, who 
is aware of and supportive of DCRT’s Special Use Permit application.  
Purpose of Request 
The purpose of the Project is to establish the required communication between the existing Southern 
California Edison (“SCE”) Colorado River Substation (“CRS”), the series compensation station (“SCS”) 
associated with Ten West Link 500 kV transmission line (“Ten West Link”), the new 500 kV Cielo Azul 
switchyard (“Cielo Azul” or “Switchyard”) located in La Paz County, Arizona, the Atlas Solar Project (a 
renewable energy project proposing to connect to Cielo Azul) and Delaney Substation (Figure 1). 
Establishing this telecommunications system will assist in satisfying the communication requirements 
associated with the interconnection of the Atlas Solar Project and the new renewable energy facilities 
proposing to connect to the Switchyard to the bulk transmission grid via Ten West Link. This new 
communication path is required to support the System Protection and is an essential element to maintain the 
reliability of the bulk transmission network serving California and Arizona. 
Figure 1. Microwave Communication Path

DCR Transmission L.L.C.  
Delaney Communication Tower 
A13498.001 
Rev1 
August 22, 2023 
 
 
Maricopa County Special Use Permit  
Pre-Application Package 
 
P. 6 
 
Description of Proposal 
The proposed Project would be located on the southwest corner of Delaney Substation, outside of the 
existing substation fence line, as shown on the preliminary Site Plan included in this package. The parcel is 
zoned Rural-43 with a land use of “Other Employment”( Maricopa County Planning and Development 
Department, 2023; Maricopa Association of Governments, 2023). On Maricopa County planning documents, 
the land use is listed as “Vacant/APS Substation” (Maricopa County Planning and Development Department, 
2019). The proposed Project footprint has previously been disturbed and is covered with aggregate stone. 
The proposed Project consists of the following: 
• 
A single 250-foot self-support microwave communication tower with a 10-foot lightning rod (total 
height 260 feet above ground level (“agl”)).  
o 
The proposed microwave communication tower will have two antennas: one located at 245 
feet agl and one located at 215 feet agl. Additional antennas may be added to the tower in 
the future.  
o 
The tower will be constructed of galvanized steel, which will be grey in color and will 
naturally dull over the course of a year or less as the galvanizing is exposed to natural 
weathering conditions.  
o 
The tower will be marked/lighted in accordance with FAA Advisory circular 70/7460-1 M, 
Obstruction Marking and Lighting, a med-dual system-Chapters 4, 8 (M-Dual), & 15. This 
will include infrared as well as signal lighting.  
• 
9-foot by 19-foot communication enclosure. Shelter height will be approximately 14 feet agl. The 
below details are from the Communication Shelter Specification for the Project: 
o 
The equipment supplied shall be of metal construction and shall be self-supporting and free 
standing. All metal work shall be free from burrs and sharp edges. Elements may be 
connected by bolts, thread forming screws, or welds. 
o 
The Communication Shelter shall be fabricated as heavy duty, fire resistant and non-
combustible construction. The shelter walls shall provide a two-hour fire rating. 
• 
An approximately 30 kW diesel-powered emergency generator set.  
• 
APS will provide station power.  
• 
Sign and fence details are included in the Site Plan and design drawings included in this 
application.  
• 
There will be no landscaping – disturbed areas will be restored to be consistent with the current 
land cover (gravel).  
• 
Access to the SUP area will be via the existing Delaney Substation driveway. APS holds an existing 
right-of-way for this driveway from Arizona State Land Department. 
The permanent Project footprint will be approximately 0.08 acres, which will be finished with aggregate stone 
at the completion of construction. Additionally, a temporary laydown area comprising 0.34 acres will be

DCR Transmission L.L.C.  
Delaney Communication Tower 
A13498.001 
Rev1 
August 22, 2023 
 
 
Maricopa County Special Use Permit  
Pre-Application Package 
 
P. 7 
 
required during construction. Access to the Project will be via the existing access road to Delaney Substation 
and a proposed shared access road along the southern edge of the substation parcel.  
The project would be operational 24/7. The facility will not be manned; however, maintenance and 
inspections of the proposed Project would be performed on a routine basis in accordance with industry 
standards and manufacturer guidelines.  
Relationship to Surrounding Properties 
Existing on-site and surrounding zoning and land use is as follows (Maricopa County Planning and 
Development Department, 2023; Maricopa Association of Governments, 2023): 
 
On-site: 
Rural-43/Vacant, APS Substation 
 
North:   
IND-2/Vacant  
 
South:  
Rural-43/Vacant 
 
East:   
Rural-43/Vacant  
 
West: 
IND-2/Vacant  
There are no wireless communication facilities within a 1,000-foot radius of the site. The proposed Project is 
consistent with the current land use at the property, which is an existing electrical substation. Access along 
the Delaney Substation driveway and the Maricopa County 40’ ROW reservation will be maintained.  
There are no residential uses within a mile of the proposed tower location. Based on the Maricopa County 
Planning and Development PlanNet website, the nearest residences are located on land that is zoned Rural-
43 and are 1.7 miles to the northeast. The nearest residential-zoned parcels are over 3 miles to the west-
south-west. Therefore, there are no compatibility issues with setbacks from current residential uses 
(Maricopa County Planning and Development Department, 2023). 
In recent years, the parcels located north, west, and south of the Project have applied for amendments and 
rezonings in order to allow for solar development: 
• 
The property to the south of the site received a Comprehensive Plan Amendment in 2011 
(CPA2011012) for a solar generating facility, with a land use change from Rural Development Area 
to Industrial (Figure 2)(Maricopa County Planning and Development Department, 2023).  
• 
The property to the north and west of the site obtained a Comprehensive Plan Amendment 
(CPA2019012) in 2021 changing the land use designation in the Tonopah/Arlington Area Plan from 
Rural to Utilities (Figure 2). The same property to the north and west requested, and received, a 
rezoning in 2019. The zoning was changed from Rural-43 to IND-2 IUPD in order to develop a 
utility-scale solar facility (rezoning case Z2019121) (Figure 3) (Maricopa County Planning and 
Development Department, 2023). 
The proposed Project consists of required communications infrastructure to support the interconnection of 
the Atlas Solar Project and other planned renewable energy to the bulk transmission grid via the Cielo Azul 
Switchyard and Ten West Link.  
Taken together, the Project and Ten West Link will improve transmission system efficiency and reliability

DCR Transmission L.L.C.  
Delaney Communication Tower 
A13498.001 
Rev1 
August 22, 2023 
 
 
Maricopa County Special Use Permit  
Pre-Application Package 
 
P. 8 
 
within the fast-growing region. Additionally, they will facilitate development of new renewable energy and 
energy storage resources in Arizona and California, thereby helping both states achieve their renewable 
energy standards and carbon reduction goals. 
 
 
 
Figure 2 – Comprehensive Plan Amendments in the Vicinity of the Project  
 
Note: Areas in purple have received a comprehensive plan amendment, as described in the “Relationship to Surrounding Properties” 
section.

DCR Transmission L.L.C.  
Delaney Communication Tower 
A13498.001 
Rev1 
August 22, 2023 
 
 
Maricopa County Special Use Permit  
Pre-Application Package 
 
P. 9 
 
 
Figure 3 – Re-Zoning in the Vicinity of the Project 
 
Note: Areas in yellow have been re-zoned, as described in the “Relationship to Surrounding Properties” section. 
 
Location and Accessibility 
An existing APS access road that runs along the southern portion of the Delaney substation property will be 
used to access the site during construction, and to access the site during operation of the facility. Access to 
existing APS access roads will be via W Salome Highway, approximately 0.4 miles south-southeast of the 
site. Access along these shared access roads will be preserved throughout construction and operations. 
The area around the proposed communication tower will be fenced to prevent public or wildlife access. A 
fence is preferred by the proponent instead of a security wall. 
Circulation System 
Not applicable.  
Development Schedule

DCR Transmission L.L.C.  
Delaney Communication Tower 
A13498.001 
Rev1 
August 22, 2023 
 
 
Maricopa County Special Use Permit  
Pre-Application Package 
 
P. 10 
 
Construction of the tower is scheduled to commence in late 2023 and would last from one to three months. 
Community Facilities and Services 
Elementary School District:  District 47 – Arlington Elementary School District 
High School District:  District 1 – Buckeye Union High School District 
Public Utilities and Services 
DCRT will enter into an agreement with APS to receive electrical service. Additionally, a fiber connection will 
be established between the Project microwave shelter and Delaney substation. No water or sewer 
connections would be built, and no garbage disposal services would be necessary. The Project is located 
outside of any fire district. The Project is within District 2 of the Maricopa County Sherriff’s office.     
Other Information 
The facility would not serve in-person customers. There would be no food service for the proposed use. 
There would be no new parking built for the project. The project is not located within any flood zones, 
washes, or canals, and is on a relatively flat parcel.  
 
A stealth design is not being considered, as it is not feasible for such a large lattice structure. There are no 
trees/windmills in the vicinity for the tower to blend in with a stealth design. The tower will be consistent with 
existing structures at and around the Delaney yard.  
 
Contact Information 
To discuss this application, please contact the below representatives: 
 
 
DCRT Contact 
 
Name:   Randy Schulze 
 
Email:   rschulze@cbxinternational.net 
 
Phone:  303-674-0551 
 
 
APS Contact 
 
Name:   Paul Baumgardt 
         
Email:   paul.baumgardt@aps.com 
         
Phone:  602-371-7849 
 
 
Sargent & Lundy Contact 
 
Name:   Julianna Crumlish 
 
Email:    julianna.r.crumlish@sargentlundy.com 
 
Phone:  312-269-2144

DCR Transmission L.L.C.  
Delaney Communication Tower 
A13498.001 
Rev1 
August 22, 2023 
 
 
Maricopa County Special Use Permit  
Pre-Application Package 
 
P. 11 
 
R E F E R E N C E S 
Maricopa Association of Governments, 2023. “Land Use Explorer.” Web Mapping Application, 
https://geo.azmag.gov/maps/landuse/. Accessed 5 May 2023.  
 
Maricopa County Planning and Development Department, 2019. “Report to the Planning and Zoning Commission, Case: 
CPA2019012 – Papago Solar.” Hearing Date: December 12, 2019. 
 
Maricopa County Planning and Development Department, 2022. “Zoning Ordinance (P-18)”, Ordinances, Regulations 
and Codes. https://www.maricopa.gov/2271/Ordinances-Regulations-and-Codes. Dated March 11, 2022.  
 
Maricopa County Planning and Development Department, 2023. “PlanNet.” ArcGIS Web Application, 
https://maricopa.maps.arcgis.com/apps/webappviewer/index.html?id=3fd3476aa2394fdabc510bee4bcf5c71. Accessed 
30 May 2023.

Krystina Aragon, PE 
Planning & Development 
301 W. Jefferson St., Suite 170 
Phoenix, Arizona 85003 
Phone: (602) 506-8790 
www.maricopa.gov/planning 
Email address: 
krystina.aragon@maricopa.gov 
Planning & Development 
 
Engineering Plan Review 
 Date:    
September 5, 2023 
 
Memo To: 
Darren Gerard, Planning Manager, Planning & Development 
 
Attn: 
Andrew Lorentzen, Planner, Planning and Development 
 
 
 
From: 
Krystina Aragon, PE, Plans Examiner Engineer, Planning and Development 
 
cc: 
Michael Norris, P.E., Engineering Manager, Planning and Development 
 
Subject:   
Z2023088 – SUP for Delaney Substation Communication Tower 
 
 (E1 Memo) 
 
Job Site Address: 
45550 W Salome Hwy, Tonopah 
APN(s): 
506-31-006D 
 
PND engineering plan review (DPR, FCD and PND Transportation) has reviewed the 2nd  
submittal of the SUP application routed for review on August 25, 2023. PND Engineering has 
no comments or objections subject to the following conditions: 
 
1. A section line , Thomas Road, coincides with the south boundary of the parcel. Per an 
approval of reduction, a 40-foot reservation will be required for Thomas Road.  
 
2. A mid-section alignment is located on the eastern perimeter of the proposed 
development requiring building setbacks to start from a future half street of 40-feet per 
the Maricopa County Zoning and Ordinance Section 11105. 
 
3. All development and engineering design shall be in conformance with Section 1205 of the 
Maricopa County Zoning Ordinance; Drainage Policies and Standards; Floodplain 
Regulations for Maricopa County; MCDOT Roadway Design Manual; and current 
engineering policies, standards and best practices at the time of application for 
construction. 
 
4. Engineering review of planning and/or zoning cases is for conceptual design only and 
does not represent final design approval nor shall it entitle applicants to future designs 
that are not in conformance with Section 1205 of the Maricopa County Zoning Ordinance 
and Drainage Policies and Standards; Floodplain Regulations for Maricopa County; and 
the MCDOT Roadway Design Manual. 
 
5. Detailed Grading and Drainage Plans showing the new site improvements must be 
submitted for the acquisition of building permits.  
Please contact me if you have any questions or require any additional information.

1
Andrew Lorentzen (PND)
From:
RAHN, JENNIFER L CIV USAF AETC 56 FW/CVE <jennifer.rahn@us.af.mil>
Sent:
Monday, August 7, 2023 3:00 PM
To:
Andrew Lorentzen (PND)
Cc:
56 FW/CIT Community Initiative
Subject:
RE: Z2023088 - Delaney Substation Communication Tower Special Use Permit Application
Good afternoon Mr. Lorentzen, 
 
Thank you for the opportunity to provide comments on the Special Use Permit for the proposed Delaney Substation 
Communication Tower.  The site is approximately 0.7 acres and is located at 45550 W. Salome Highway in 
unincorporated Maricopa County, AZ.  The developer is proposing a 250ft microwave tower with additional 10ft 
lightening rod at the SW corner of the property boundary (APN: 506‐31‐006D).  The parcel in the application is located 
outside of the Luke AFB 1988 JLUS 65 Ldn “high noise or accident potential zone” as identified by A.R.S. § 28‐8461 and is 
within the “territory in the vicinity of a military airport” defined by A.R.S. § 28‐8461.    
 
Subject to the results of an FAA Obstruction Evaluation/Airport Airspace and Spectrum Analysis (OE/AAA), this request, 
as described in the narrative, will not negatively impact the flying and base operations at Luke AFB.  We do however 
request the installation of an Aviation Obstruction Light (AOL) or Aircraft Warning Light (ACWL) due to its height and 
location.  Approved lighting includes L‐810 red lighting in accordance with AC 70/7460‐1M. Lighting will increase 
operational awareness of the tower location. The night vision goggle (NVG) compliant L‐810 red light is comprised of 
visible red emitters and infrared (IR) emitters for pilot safety. 
 
Since the site will be located within the “territory in the vicinity of a military airport,” it will be subjected to 
approximately 170 over flights per day.  We recommend a strong notification program on part of the County to inform 
the applicant about Luke AFB operations.    
 
V/r, 
 
Jenn Rahn 
Senior Planner, Community Initiatives Team 
56th Fighter Wing 
Luke AFB AZ 85309 
Office:  623‐856‐9981 
DSN:  896‐9981 
 
 
 
 
From: Andrew Lorentzen (PND) <Andrew.Lorentzen@maricopa.gov>  
Sent: Thursday, July 27, 2023 2:31 PM 
To: tvcc.events@gmail.com; dmheisler1@aol.com; ronsatt@ev1.net; proetto1950@gmail.com; twilliford@azgfd.gov; 
tstruck@azgfd.gov; tsprague@azgfd.gov; pep@azfgd.gov; 56 FW/CIT Community Initiative 
<56FW.CIT.CommunityInitiative@us.af.mil>; swilken@azmag.gov; kcotner@azmag.gov; agarza@azmag.gov; 
pe@azland.gov; bfenske@azdot.gov; jgarcia@azdot.gov; redletter@azdot.gov; gramirez@azdot.gov; 
Dkrantz@citytocitycre.com; jcrew@lotuspartners.com 
Subject: [URL Verdict: Neutral][Non‐DoD Source] Z2023088 ‐ Delaney Substation Communication Tower Special Use 
Permit Application

2
Hello Registered Area of Interest Member,  
Please find attached a planning & development application routing for Z2023088 - Delaney Substation 
Communication Tower Special Use Permit. 
See attached document for instructions to download application materials.  
Thank you,  
 
 
Andrew Lorentzen 
Planner 
PLANNING & DEVELOPMENT 
301 W. Jefferson St. Suite 170  
Phoenix, AZ 85003 
O:   602-506-2364     
MARICOPA.GOV 
Andrew.lorentzen@maricopa.gov 
Facebook | Instagram | Twitter | YouTube | LinkedIn