Minutes of the August 15, 2024 Regular Meeting
Extracted text (via pymupdf)
20538 characters
MINUTES OF THE BOARD OF APPEALS OF THE CITY OF CHANDLER, ARIZONA, held on
Thursday, August 15, 2024, at 7:00 a.m., in the Development Services Building – South
Atrium Conference Room, 215 E. Buffalo Street, Chandler, Arizona.
Members Present
Jeff Cullumber, Chair
David Love Vice Chair
Heather Mattisson, Board Member
Michael Quinn, Board Member
Michael McElhany, Board Member
Guest(s)
Chandni Bhakta, Arizona Multi-housing
Association
Staff Absent
Shicheng Tao, Building Official
Staff Present
Kevin Snyder, Development Services
Director
LeeRay Hanly, Building Plan Review
Administrator
Bob Graffius, Building Inspection
Administrator
Corey Bush, Senior Building Plans
Examiner
Wayne McMinn, Senior Building Plans
Examiner
Catherine Flores, Senior Management
Analyst
Aaron Huckstep, Fire Marshal
1. CALL TO ORDER / ROLL CALL Quorum was established and the meeting was called to
order at 7:02 a.m.
2. UNSCHEDULED PUBLIC APPEARANCES - None
(Members of the audience may address any item not on the agenda. State Statute
prohibits the Board of Appeals from discussing an item not on the agenda, but the
Board of Appeals does listen to your concerns and has staff to follow up on any
questions you raise.)
CONSENT AGENDA
3. APPROVAL OF MINUTES
a. Minutes of August 1, 2024
Motion made by Board Member Michael Quinn to approve the Board of Appeals
Meeting Minutes for August 1, 2024, Motion seconded by Board Member Michael
McElhany. Approved (5-0)
4. BOARD OF APPEALS BUSINESS MEETING
Wayne McMinn, Senior Building Plans Examiner and Aaron Huckstep, Fire Marshal
presented the Proposed Amendments and Significant Changes to the Board of Appeals.
•
Significant Changes to the 2024 IBC
o Proposed Adoption Dates 07/01/2025
o City Council Hearing Dates, 11/04/2024, 11/07/24 & 12/12/2024
o Board of Appeals Review 09/12/24.
Board of Appeals
August 1, 2024
Page 2
•
Proposed Amendments to the 2024 International Building Code
•
Subsection 101.1 Title. These regulations shall be known as the Building Code
of the City of Chandler, Arizona hereinafter referred to as “this code”.
•
Subsection 102.2 Other laws. The provisions of this code shall not be deemed
to nullify any provisions of local, state, or federal law.
o The following provisions are added to the end thereof:
o Additionally, the building official will enforce the provisions of such
other laws when mandated by state or federal law.
•
(NEW) Subsection 104.2.3 Alternative materials, design and methods of
construction and equipment.
o The proposed amendment is to delete the entire exception to this
subsection.
o Exception: Performance based alternative materials, design and
methods of construction and equipment complying with the
international Code Council Performance Code:
•
Subsection 105.3.1 Action on application. The following provisions are added
to the end of the paragraph.
o The building official shall examine or cause to be examined applications
for permits and amendments thereto within a reasonable time after
filing. If the application or the construction documents do not conform
to the requirements of pertinent laws, the building official shall reject
such application in writing stating the reasons, therefore. If the building
official is satisfied that the proposed work conforms to the
requirements of this code and laws and ordinances applicable thereto,
the building official shall issue a permit therefore as soon as practicable.
A permit may be issued solely after the applicant has satisfied all
applicable City of Chandler ordinance and requirements.
•
Subsection 105.5 Expiration.
o Every permit issued shall become invalid unless the work authorized by
such permit commences within 180 days after its issuance or after
commencement of work if more than 180 days pass between
inspections. The building official is authorized to grant, in writing, one
or more extensions of time, for periods not more than 180 days each.
The extension shall be requested in writing and justifiable cause
demonstrated.
•
A new subsection 105.5.1 is added to read as follows:
o 105.5.1 Reinstatement. The Building Official is authorized to reinstate a
permit that has expired upon payment of a reinstatement fee
provided:
1. The permit has not been expired for more than one year and,
2. Code requirements that would affect the project have not
changed.
Board of Appeals
August 1, 2024
Page 3
•
Subsection 109.2 Schedule of permit fees. Delete in its entirety and replace
with a new subsection 109.2 as follows:
o 109.2 Schedule of permit fees. Permit fees, if any, shall be adopted by
the City by resolution.
•
(NEW) Subsection 111.1 Change of occupancy, Subsection 111.2 Certificate
Issued and Subsection 111.3 Temporary occupancy.
•
The City has no proposed amendment to these subsections. When the new
code is adopted then it will go into the City Code as written.
•
Subsection 111 Certificate of Occupancy.
•
Add a new subsection 111.5 to read as follows:
o 111.5 Certificate of Completion. A Certificate of Completion may be
issued at completion of permitted work when:
a. The work authorized does not change the scope of an
existing certificate of occupancy or:
b. The work authorized does not result in a building ready for
occupancy.
o A Certificate of Completion alone shall not authorize occupancy of a
building.
•
Subsection 308.2 Institutional Group I-1 and Subsection208.2.3 Six to 16
persons receiving custodial care. Replace 16 persons with 10 persons.
•
308.2 Institutional Group I-1. Institutional group I-1 occupancy shall include
buildings, structures, or portions thereof for more than 10 persons, excluding
staff, who reside on a 24-hour basis in a supervised environment and receive
custodial care.
•
308.2.3 Six to 10 persons receiving custodial care. A facility housing not fewer
than six and not more than 10 persons receiving custodial care shall be
classified as Group R-4.
•
Subsection 310.5 Residential Group R-4. Residential Group R-4 occupancy
shall include buildings, structures, or portions thereof for more than five but
not more than 16 persons, excluding staff, who reside on a 24-hour basis in a
supervised residential environment and receive custodial care.
o Replace 16 person with 10 persons in the first sentence.
o Residential Group R-4 occupancy shall include buildings, structures, or
portions thereof for more than five but not more than 10 persons,
excluding staff, who reside on a 24-hour basis in a supervised residential
environment and receive custodial care.
•
(NEW) Subsection 412.4.5 Height and area limits. Residential aircraft hangars
shall be not greater than 2,000 square feet (186 m2) in area and 20 feet (6096
mm) in building height.
o Proposed amendment is to delete the entire paragraph and replace it
with the following along with an additional note “d” to TABLE 412.3.6:
o 412.4.5 Height and area limits. Residential aircraft hangars (those private
hangars associated and attached to single family residential dwelling
units) shall meet the City of Chandler fire suppression requirements as
Board of Appeals
August 1, 2024
Page 4
amended in TABLE 412.3.6 “HANGAR FIRE SUPPRESSION
REQUIREMENTS”.
o A note ‘d’ has been added to the TABLE 412.3.6 as follows:
Residential aircraft hangars shall be provided with a group 13R fire
suppression system OR the hangar and dwelling may be provided with a
group 13D fire suppression system.
•
(NEW) Subsection 1612.3 Establishment of flood hazard areas.
o Proposed amendment is to insert The City of Chandler, Arizona as Name
of Jurisdiction and the latest effective date as Date of Issuance as
follows:
o 1612.3 Establishment of flood hazard areas. To establish flood hazard
areas, the applicable governing authority shall adopt a flood hazard map
and supporting data. The flood hazard map shall include, at a minimum,
areas of special flood hazard as identified by the Federal Emergency
Management Agency in an engineering report entitled “The Flood
Insurance Study for The City of Chandler, Arizona,” dated the latest
effective date, as amended, or revised with the accompanying Flood
Insurance Rate Map (FIRM) and Flood Boundary and Floodway Map
(FBFM) and related supporting data along with any revisions thereto. The
adopted flood hazard map and supporting data are hereby adopted by
reference and declared to be part of this section.
•
Preface – Replacement of Margins with QR Codes
o Solid vertical lines for new text, arrows for deletions and asterisks for
relocations have been removed and replaced with a QR code.
o A QR code is placed at the beginning of any section that has undergone a
technical revision. (No QR code means there were no changes).
o To see the changes, scan the QR code with a smart device or enter the 7-
digit code beneath the QR code @ wr.iccsafe.org.
•
Chapter 9 – Fire Protection and Life Safety Systems
o There are numerous additions through the 2024 IBC and IFC to address
the ever-growing lithium-ion battery applications.
o Chapter 9 has added many sections for fire protection requirements
associated with lithium-ion batter manufacturing, storage, use, repair,
charging and research.
•
Section 907.10.1 – Smoke Alarm Replacement
o A new section was added requiring the replacement of smoke detectors
when:
o It does not work.
o The detector is 10 years past the manufactured date.
o The end-of-life signal is sounded.
o The date of manufacture cannot be determined.
o This requirement is already enforced by Fire.
o Significance – Will not affect Building Inspections and is not enforceable
in residential homes.
Board of Appeals
August 1, 2024
Page 5
•
Sections 912.5.1 & 912.5.4 – Signs
o These sections were added dictating signage for sprinkler system fire
department connections on multiple buildings or with combined
systems.
o Dictates the lettering be not less than 1” in height.
o Adds the requirement to provide a sign at the FDC stating the required
pressure needed unless the required pressure is 150 pounds per square
inch or less.
o Significance – FDC signage is Chandler is dictated by Fire Department
detail FD104 and requires 2” letters.
•
Section 915 – Carbon Monoxide Detection
o Several changes in section 915 for carbon monoxide (CO) detection and
alarm.
o Previously CO detection limited dwellings, sleeping quarters, enclosed
parking, and educational occupancies.
o Now any occupancy with a CO source requires detection and/or alarm.
o CO detectors are required to be tied into the fire alarm and activate
notification alarm.
o CO alarm requirements are retroactive per IFC 1103.9.
•
Section 917.2 – Mass Notification
o This section was added including all Group E occupancies in addition to
college and university, campuses that were previously in this section.
o Prior to construction of a Group E occupancy that requires a fire alarm
or has an occupant load over 500, a mass notification risk analysis must
be conducted in accordance with NFPA72.
o Significance – If the risk analysis determines the need for mass
notification, an approved mass notification system would be required to
be installed.
•
Significant Changes to the 2024 IFC
o Proposed Adoption Date 07/1/2025
o City Council Hearing Dates 11/04/2024, 11/07/2024, & 12/12/2024
o Board of Appeals Review 09/12/2024.
•
Chapter 28 – 2024 City Amendments
•
28-21 Construction Requirements for Existing Buildings
•
Section 1103.8 of the code is hereby amended by adding a new Section
1103.8.2.1 entitled “Interconnection for R-3 Group Homes” to be read as
follows:
o 1103.8.2.1 Interconnection for R-3 Group Homes. All smoke detectors
located in R-3 group occupancy types shall be interconnected in such a
manner that the activations of one alarm will activate all the alarms in
the individual unit. Physical interconnection of smoke alarms shall not
be required where listed wireless alarms are installed and all alarms
sound upon activation of one alarm. The alarm shall be clearly audible
Board of Appeals
August 1, 2024
Page 6
in all bedrooms over background noise levels with all intervening
doors closed.
•
28-25 – Appendices
•
Firefighter Air Replenishment System (FARS)
o L101.11. Air monitoring system. An approved air monitoring system
shall be provided. The system shall automatically monitor air quality,
moisture, and pressure on a continual basis. The air monitoring system
shall be equipped with not less than two content analyzers capable of
detecting carbon monoxide, carbon dioxide, nitrogen, oxygen,
moisture, and hydrocarbons.
o L101.11.1 The air monitoring system shall be tied into the FACP and
transmit a supervisory signal when any of the following levels are
detected:
1. Carbon monoxide exceeds 5 ppm.
2. Carbon dioxide exceeds 1,000 ppm.
3. An oxygen level below 19.5 percent or above 23.5 percent.
4. A nitrogen level below 75 percent or above 81 percent.
5. Hydrocarbon (condensed) content exceeds 5 milligrams per cu
cubic meter of air.
6. The moisture concentration exceeds 24 ppm by volume.
7. The pressure falls below 90 percent of the maintenance pressure
of (4,500) psi.
•
28-25 – Appendices
•
Firefighter Air Replenishment Systems (FARS)
o Delete Section 2 and first sentence of 3.
•
Preface – Replacement of Margins with QR Codes
o Solid vertical lines for new text, arrows for deletions and asterisks for
relocations have been removed and replaced with a QR code.
o A QR code is placed at the beginning of any section that has undergone
a technical revision. (No QR code means there were no changes).
o To see the changes, scan the QR code with a smart device or enter the
7-digit code beneath the QR code @ qr.iccsafe.org.
•
Section 107 – Temporary Structures
o A new section was added addressing temporary structures, uses,
equipment and systems.
o Fire Code Official is authorized to issue a permit for temporary
structures, uses, equipment or systems for a period not exceeding 180
days. The Fire Code Official can also discontinue this permit.
o The Fire Code Official is authorized to give permission to temporarily
supply utilities.
•
Chapter 2 – Definitions
o Just like every other code cycle, there were many additions, deletions,
relocations, and changes to this section.
•
Section 203 - Occupancy Classification and Use
Board of Appeals
August 1, 2024
Page 7
o Entire section from 203.1 – 203.11.3 was added.
o Most of, but not all, of the occupancy classification code sections were
taken from the International Building Code and are now also a part of
the International Fire Code.
•
Section 320 – Lithium–Ion and Lithium Metal Battery Storage
o An entire new section was added addressing lithium battery storage.
(320.1 through 320.4.3.3.).
o These new sections provide code requirements ranging from
permitting, indoor storage, outdoor storage, fire protection, occupancy
separation, construction, explosion control and fire alarms.
o Significance – We are seeing this more and more and the Fire
department is responding to more battery fires.
•
Section 322 – Powered Micro Mobility Devices
o What is a powered micro mobility device? Electric micro mobility
includes any small, low speed, electric powered transportation device,
including electric assist bicycles (e-bikes), electric scooters (e-scooters),
and other small lightweight, wheeled electric powered conveyances.
o Another new section was added addressing storage and charging.
o Significance – These often contain lithium-ion or lithium metal
batteries.
•
Section 401.10.6 & 403.10.6.1 – Lithium-Ion Batteries
o Another two new sections addressing lithium-ion batteries.
o Additional include providing a fire safety and evacuation plan as well as
providing mitigation planning for occupancies involved in the research,
development, testing, manufacturing, handling, or storing of these
batteries.
o Significance – There is a “theme” forming with this years Fire Code
changes.
•
Section 510 - Emergency Responder Communications Enhancement Systems
o The title of this section changes from Emergency Responder
Communication Coverage to Emergency Responder Communications
Enhancement Systems.
o Significance – No change to inspection protocol.
•
Section – Lithium-Ion Batteries
o Another new section was added regarding lithium-ion and lithium
metal batteries.
o The new section requires that fire sprinkler systems for areas
containing these batteries be designed based on laboratory test(s) and
scenarios.
•
Section 9904.14.1 – Manual System Operation
o Exception #2 was added to this section.
o This exception allows the Fire code official to accept an approved
alternate location when the “no less than 10 feet, no more than 20 feet
from the cooking area” requirement is not feasible.
Board of Appeals
August 1, 2024
Page 8
•
Section 9907.2.2.2 / 907.2.4.1 – Lithium-Ion
o Another two sections were added regarding lithium-ion and lithium
metal batteries.
o Air-sampling smoke detection or radiant-energy sensing detection
systems need to be installed in areas involving research and
development of these batteries.
o Air-sampling smoke detection or radiant-energy sensing detection
systems need to be installed in areas involving manufacturing, vehicle
manufacturing or other equipment where these type batteries are
installed during manufacturing.
•
Section 907.2.11.3 – Installation near cooking appliances
o This section was re-written and changed.
o Smoke alarms in R-2, R-3, R-4, and I-1 occupancies shall be installed not
less than 10 feet horizontally from a permanently installed cooking
appliance.
Regarding of type of smoke alarm
o Exception allows smoke alarm to be installed not less than 6 feet from
the appliance where necessary to comply with section 9097.2.11.1 or
907.2.11.2.
o Significance – Previously this section addressed the different types of
smoke detectors and distance requirements.
•
Section 907.10.1 – Smoke Alarm Replacement
o A new section was added requiring the replacement of smoke
detectors when:
It does not work.
The detector is 10 years past the manufactured date.
The end-of-life signal is sounded.
The date of manufacture cannot be determined.
o This requirement is already enforced by Fire Inspectors.
•
Section 912.5.1. – 912.5.4 Signs
o These sections were added dictating signage for sprinkler systems fire
department connections on multiple buildings or with combined
systems.
o Dictates the lettering be not less than 1” in height.
o Adds the requirement to provide a sign at the FDC stating the required
pressure needed unless the required pressure is 150 pounds per
square inch or less.
o Significance – FDC signage in Chandler is dictated by Fire department
detail FD104 and requires 2” letters.
•
Section 917.2 – Mass Notification
o This section was added including all Group E occupancies in addition to
college and university campuses that were previously in this section.
Board of Appeals
August 1, 2024
Page 9
o Prior to construction of a Group E occupancy that requires a fire alarm
or has an occupant load over 500, a mass notification risk analysis
must be conducted in accordance with NFPA72.
o Significance – If the risk analysis determines the need for mass
notification, an approved mass notification shall be provided in
accordance with the findings.
ACTION AGENDA
a. None
5. BRIEFING ITEMS
Wayne McMinn, Senior Building Plans Examiner and Aaron Huckstep, Fire Marshal
spoke on the Code Amendment and Significant Changes Presentation. It was discussed
that the board members will be briefed by staff pertaining to the building code editions
in the upcoming meetings.
6. MEMBER COMMENTS/ANNOUNCEMENTS
7. CALENDAR
a. Next meeting is scheduled Thursday, August 29, 2024, @ 7:00 a.m.
8. ADJOURN
Board Member Michael Quinn motioned for the meeting to adjourn. Motion seconded
by Vice Chair David Love.
The meeting was adjourned at 8:15 a.m.
______________________________
_______________________________
Jeff Cullumber, Chairman
Shicheng Tao, Secretary