November 1, 2023
Z2023088
Page 1 of 2
Report to the Board of Supervisors
Prepared by the Maricopa County Planning and Development Department
Board Hearing Date:
November 1, 2023
Case #/Title:
Z2023088 - Delaney Substation Communication Tower
Supervisor District:
4
Applicant/Owner:
Jason Crew, DCR Transmission LLC / Arizona Public Service
Company
Request:
Special Use Permit to allow a 260’ microwave communications
tower
Site Location:
Generally located NW of Salome Hwy & Courthouse Road
Site Size:
Approximately 3,780 sq. ft.
County Island Status:
N/A
Additional
Comments:
The applicant is requesting a 50-year timeframe for the Special Use
Permit to expire in 2073 as that date corresponds to APS’s right of
way lease length for the corresponding transmission infrastructure.
Commission
Recommendation:
On 10/5/23, the Commission voted 5-0 to adopt a motion
recommending the Board of Supervisors approve Z2023088
subject to conditions ‘a’ – ‘g’:
a.
Development of the site shall be in substantial conformance with the Site Plan entitled
“Delaney Substation DCRT MW Tower“, consisting of 8 full-size sheets, dated August 21,
2023, except as modified by the following conditions. Staff may determine slight
refinements to remain in substantial conformance with the approved site plan.
b.
Development of the site shall be in substantial conformance with the Narrative Report
entitled “Delaney Substation Communication Tower”, consisting of 12 pages, dated
August 22, 2023, except as modified by the following conditions.
c.
The following engineering conditions:
1.
A section line , Thomas Road, coincides with the south boundary of the parcel.
Per an approval of reduction, a 40-foot reservation will be required for Thomas
Road.
2.
A mid-section alignment is located on the eastern perimeter of the proposed
November 1, 2023
Z2023088
Page 2 of 2
development requiring building setbacks to start from a future half street of 40-
feet per the Maricopa County Zoning and Ordinance Section 11105.
3.
All development and engineering design shall be in conformance with Section
1205 of the Maricopa County Zoning Ordinance; Drainage Policies and Standards;
Floodplain Regulations for Maricopa County; MCDOT Roadway Design Manual;
and current engineering policies, standards and best practices at the time of
application for construction.
4.
Engineering review of planning and/or zoning cases is for conceptual design only
and does not represent final design approval nor shall it entitle applicants to
future designs that are not in conformance with Section 1205 of the Maricopa
County Zoning Ordinance and Drainage Policies and Standards; Floodplain
Regulations for Maricopa County; and the MCDOT Roadway Design Manual.
5.
Detailed Grading and Drainage Plans showing the new site improvements must
be submitted for the acquisition of building permits.
d.
Tower lighting and marking must meet all FAA regulations.
e.
This special use permit is valid for a period of 25 years and shall expire on October 18,
2048, or upon termination of the use for a period of 90 or more days, whichever occurs
first. All site improvements associated with the special use permit shall be removed within
90 days of such expiration or termination of use.
f.
The granting of this change in use of the property has been at the request of the applicant,
with the consent of the landowner. The granting of this approval allows the property to
enjoy uses in excess of those permitted by the zoning existing on the date of application,
subject to conditions. In the event of the failure to comply with any condition, and at the
time of expiration of the Special Use Permit, the property shall revert to the zoning that
existed on the date of application. It is, therefore, stipulated and agreed that either
revocation due to the failure to comply with any conditions, or the expiration of the Special
Use Permit, does not reduce any rights that existed on the date of application to use,
divide, sell or possess the property and that there would be no diminution in value of the
property from the value it held on the date of application due to such revocation or
expiration of the Special Use Permit. The Special Use Permit enhances the value of the
property above its value as of the date the Special Use Permit is granted and reverting to
the prior zoning results in the same value of the property as if the Special Use Permit had
never been granted.
g.
Noncompliance with any Maricopa County Regulation shall be grounds for initiating a
revocation of this Special Use Permit as set forth in the Maricopa County Zoning
Ordinance.
Presented by:
Andrew Lorentzen, Planner
Reviewed by:
Darren Gérard, AICP, Planning Manager
Attachment:
10/5/23 P&Z Packet (29 pages)
Note:
10/05/23 Draft P&Z Minutes are not available as of the writing of this report, but can be
provided upon request later when available.
Z2023088
Page 1 of 5
Report to the Planning and Zoning Commission
Prepared by the Maricopa County Planning and Development Department
Case:
Z2023088 - Delaney Substation Communication Tower
Hearing Date:
October 5, 2023
Supervisor District:
4
Applicant:
DCR Transmission LLC
Owner:
Arizona Public Service Company (APS)
Request:
Special Use Permit to allow a 260’ microwave communications tower
Site Location:
Generally located NW of Salome Hwy & Courthouse Road
Site Size:
Approximately 3,780 sq. ft.
Density:
N/A
County Island:
No
County Plan:
Tonopah / Arlington Area Plan
Rural Densities (0-1)
Municipal Plan:
N/A
Municipal Comments:
None received to date
Support/Opposition:
None known
Recommendation:
Approve with conditions
Z2023088
Page 2 of 5
Project Summary:
1.
The applicant, DCR Transmission LLC, is requesting a special use permit (SUP) on a Rural-43
zoned parcel for the use of a microwave communications tower. The subject parcel 506-31-006D
is an operating electrical power substation (known as the Delaney Substation) owned by Arizona
Public Service Company otherwise known as APS. APS created the Delaney Substation in
approximately 2010 to prepare for utility solar power generation facilities that are planned in the
immediate area. The proposed 260’ microwave communications tower will allow
communications between Delaney and other electrical substations to allow APS to better
understand the power needs and shortcomings within its electrical grid network.
2.
The proposed microwave communications tower will be comprised of 2 microwave
communications antennae. The tower is a triangular structure extending to 250’ with a 10’
lightning rod placed at the top.
Existing On-Site and Adjacent Zoning / Land Use:
3.
On-site:
Rural-43 / Electrical substation
North:
IND-1 / Vacant
South:
Rural-43 / Vacant (AZ State Land)
East:
Rural-43 / Vacant (AZ State Land)
West:
IND-1 / Vacant
Z2023088
Page 3 of 5
Utilities and Services:
4.
Water:
N/A
Wastewater:
N/A
Fire:
Tonopah Valley Fire District
Police:
Maricopa County Sherriff
Right-of-Way:
5.
The following table includes existing and proposed half-width right-of-way and the future
classification based upon the Maricopa County Department of Transportation (MCDOT) Major
Streets and Routes Plan.
Street Name
Half-width Existing R/W
Half-width Proposed R/W
Future Classification
Thomas Rd.
40’
40’
Minor Arterial
Adopted Plan:
6.
Tonopah / Arlington Area Plan (adopted September 6, 2000): The area is established as Rural
Density Development Area (0-1). Utility infrastructure and substations are acceptable uses with
the rural density comprehensive plan land element.
Public Participation Summary:
7.
The applicant notified the surrounding parcel owners of the proposal within 300’. The site has
also been posted pursuant to Maricopa County requirements. The applicant met all public
participation requirements. There has been no public comments received.
Outstanding Concerns from Reviewing Agencies:
8.
Luke Air Force Base has reviewed the proposal noting that the tower is in the general area that it
conducts
its
training
exercises.
The
agency
reviewing
stated
the
tower
will
“not negatively impact the flying and base operations at Luke AFB”. The agency did request
additional “Aviation Obstruction Light (AOL) or Aircraft Warning Light (ACWL)” to be installed due
to height and location of the tower. The applicant has complied with the request adding an
additional light to the tower per the request.
Staff Analysis:
9.
The immediate areas to the west and north of the subject parcel have been both rezoned and
comprehensively planned for utility scale solar generation facilities. The request for the
microwave communications facility will allow the owner, APS, to better manage its electrical
loads on transmission lines which will benefit all anyone with access to the power grid. The tower
height is requested specifically due to the technical aspects of microwave communications
needing line of sight for transmission purposes. The vast distances between the utility
substations justify the height proposed.
Z2023088
Page 4 of 5
Recommendation:
10.
Staff recommends the Commission adopt a motion recommending that the Board of Supervisors
approve Z2023088 subject to the following conditions ‘a’ – ‘g’.
a.
Development of the site shall be in substantial conformance with the Site Plan entitled
“Delaney Substation DCRT MW Tower“, consisting of 8 full-size sheets, dated August 21,
2023, except as modified by the following conditions. Staff may determine slight
refinements to remain in substantial conformance with the approved site plan.
b.
Development of the site shall be in substantial conformance with the Narrative Report
entitled “Delaney Substation Communication Tower”, consisting of 12 pages, dated
August 22, 2023, except as modified by the following conditions.
c.
The following engineering conditions:
1. A section line , Thomas Road, coincides with the south boundary of the parcel.
Per an approval of reduction, a 40-foot reservation will be required for Thomas
Road.
2. A mid-section alignment is located on the eastern perimeter of the proposed
development requiring building setbacks to start from a future half street of 40-
feet per the Maricopa County Zoning and Ordinance Section 11105.
3. All development and engineering design shall be in conformance with Section
1205 of the Maricopa County Zoning Ordinance; Drainage Policies and Standards;
Floodplain Regulations for Maricopa County; MCDOT Roadway Design Manual;
and current engineering policies, standards and best practices at the time of
application for construction.
4. Engineering review of planning and/or zoning cases is for conceptual design
only and does not represent final design approval nor shall it entitle applicants to
future designs that are not in conformance with Section 1205 of the Maricopa
County Zoning Ordinance and Drainage Policies and Standards; Floodplain
Regulations for Maricopa County; and the MCDOT Roadway Design Manual.
5. Detailed Grading and Drainage Plans showing the new site improvements must
be submitted for the acquisition of building permits
d.
Tower lighting and marking must meet all FAA regulations.
e.
This special use permit is valid for a period of 50 years and shall expire on October 18,
2073, or upon termination of the use for a period of 90 or more days, whichever occurs
first. All site improvements associated with the special use permit shall be removed within
90 days of such expiration or termination of use.
f.
The granting of this change in use of the property has been at the request of the applicant,
with the consent of the landowner. The granting of this approval allows the property to
enjoy uses in excess of those permitted by the zoning existing on the date of application,
subject to conditions. In the event of the failure to comply with any condition, and at the
time of expiration of the Special Use Permit, the property shall revert to the zoning that
Z2023088
Page 5 of 5
existed on the date of application. It is, therefore, stipulated and agreed that either
revocation due to the failure to comply with any conditions, or the expiration of the Special
Use Permit, does not reduce any rights that existed on the date of application to use,
divide, sell or possess the property and that there would be no diminution in value of the
property from the value it held on the date of application due to such revocation or
expiration of the Special Use Permit. The Special Use Permit enhances the value of the
property above its value as of the date the Special Use Permit is granted and reverting to
the prior zoning results in the same value of the property as if the Special Use Permit had
never been granted.
g.
Noncompliance with any Maricopa County Regulation shall be grounds for initiating a
revocation of this Special Use Permit as set forth in the Maricopa County Zoning
Ordinance.
Presented by:
Andrew Lorentzen, Planner
Reviewed by:
Matthew Holm, AICP, Planning Supervisor
Attachments:
Case Map (1 page)
Site Plan (8 pages)
Narrative Report (12 pages)
MCDOT comments (1 page)
Luke AFB Comments (2 pages)
/
Maricopa County Planning & Development - Phoenix, AZ
4
Gross Acres: 1 approx.
Generated September 21, 2023 2:22 PM
Z2023088
Application Name:
Legal Description
Delaney Substation Communication Tower EDR
Applicant
Case Address
T02N R08W 025,
Jason Crew for DCR Transmission, L.L.C.
45550 W SALOME Hwy
Applicant Phone/Email
Parcel Primary:506-31-006D
713.569.8995
jcrew@lotuspartners.com
TONOPAH AZ 85354
Map scale 1:3,268
Supervisor District No.
DCR TRANSMISSION, L.L.C. (“DCRT”), AN AFFILIATE OF LOTUS INFRASTRUCTURE PARTNERS, SEEKS
A SPECIAL USE PERMIT FOR THE INSTALLATION OF A NEW 250-FOOT MICROWAVE COMMUNICATION
REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY
OF ALL PEOPLE LOCATED ON THE WORK SITE,
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL
(OR THAT OF ITS SUB-CONTRACTOR(S))
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS
DRAWING BY AN ORGANIZATION OTHER THAN
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY
OF SARGENT & LUNDY.
1
A
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING
DOCUMENT WAS PREPARED BY ME OR UNDER MY
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ENTER NAME.
ENTER NAME
ENTER DATE
IS: ENTER DATE
B
SARGENT & LUNDY
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-1501
0C
0A
03/31/23
D-E-1501.DWG
1"=100'-0"
MICROWAVE YARD LAYOUT
FOR APS REVIEW
DELANEY SUBSTATION
DCR TRANSMISSION
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPB/XXX
FOR PERMIT APPLICATION
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY
OF ALL PEOPLE LOCATED ON THE WORK SITE,
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL
(OR THAT OF ITS SUB-CONTRACTOR(S))
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS
DRAWING BY AN ORGANIZATION OTHER THAN
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY
OF SARGENT & LUNDY.
1
A
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING
DOCUMENT WAS PREPARED BY ME OR UNDER MY
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ENTER NAME.
ENTER NAME
ENTER DATE
IS: ENTER DATE
B
SARGENT & LUNDY
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-2550
0C
0A
03/31/23
D-E-2550.DWG
1"=10'-0"
LATTICE TOWER
FOR APS REVIEW
PLAN VIEW & SECTIONS
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPB/XXX
FOR PERMIT APPLICATION
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)
45°
45°
45°
8'-6"
19'-0"
LEGEND:
NOTES:
CONSTRUCTION NOTES:
SCALE
1.
ONLY ONE (1) MAIN GROUND BAR (MGB) TO BE INSTALLED IN ORDER TO ENSURE
SINGLE-POINT GROUNDING. LOCATE MGB AT POINT OF FEEDLINE ENTRY THAT IS
MOST PRACTICAL BASED ON SITE LAYOUT. SEPARATION IN INTERIOR PERIMETER
GROUND BUS (IPGB) TO BE LOCATED ON OPPOSITE WALL OF MGB.
2.
MAIN GROUND GRID TO BE BURIED 30" BELOW FINISHED GRADE.
3.
RACK #1 IS 23" WIDTH, RACKS #2-5 ARE 19" WIDTH
COMPRESSION CONNECTION
5/8" x 20'-0" DIA. COPPERWELD GROUND ROD
300 KCM BARE COPPER, STRANDED, HARD DRAWN
GROUNDING CABLE
REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY
OF ALL PEOPLE LOCATED ON THE WORK SITE,
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL
(OR THAT OF ITS SUB-CONTRACTOR(S))
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS
DRAWING BY AN ORGANIZATION OTHER THAN
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY
OF SARGENT & LUNDY.
1
A
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING
DOCUMENT WAS PREPARED BY ME OR UNDER MY
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ENTER NAME.
ENTER NAME
ENTER DATE
IS: ENTER DATE
B
SARGENT & LUNDY
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-2551
0C
0A
03/31/23
D-E-2551.dwg
1/2"=1'-0"
COMMUNICATION SHELTER
FOR APS REVIEW
PLAN & ELEVATION VIEWS
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPB/XXX
FOR PERMIT APPLICATION
C5551
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)
REFERENCE DRAWINGS:
LATTICE TOWER PLAN & SECTIONS
D-E-2550
WAVE GUIDE BRIDGE PLAN & SECTIONS
D-E-2552
EXTERNAL GROUNDING
D-E-3501
INTERNAL GROUNDING
D-E-3502
HANDHOLE DETAIL
D-E-4501
GENSET DETAIL
D-E-4502
CONDUIT LAYOUT
D-E-2501
FOUNDATION LAYOUT
D-E-2502
GROUNDING LAYOUT
D-E-2503
MICROWAVE YARD LAYOUT
D-E-1501
CABLE TRAY
1.
CONTRACTOR/INSTALLER SHALL TAKE ALL APPROPRIATE PRECAUTIONS WITHIN OR
ADJACENT TO THE AREA IN WHICH EXCAVATION, DEMOLITION, FOUNDATION OR
MODIFICATION WORK IS TO BE PERFORMED.
2.
THE CONTRACTOR/INSTALLER SHALL EXERCISE DUE CAUTION DURING ALL
EXCAVATION/FOUNDATION/DEMOLITION WORK.
3.
CONTRACTOR/INSTALLER SHALL TAKE ALL APPROPRIATE PRECAUTIONS TO ENSURE
THE SAFETY OF ALL PEOPLE LOCATED ON THE WORK SITE, INCLUDING
CONTRACTOR'S/INSTALLER'S PERSONNEL (OR THAT OF ITS SUBCONTRACTOR(S))
PERFORMING THE WORK.
4.
FOR GENERAL NOTES SEE DWG. D-E-1501.
·
·
·
·
·
REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY
OF ALL PEOPLE LOCATED ON THE WORK SITE,
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL
(OR THAT OF ITS SUB-CONTRACTOR(S))
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS
DRAWING BY AN ORGANIZATION OTHER THAN
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY
OF SARGENT & LUNDY.
1
$DATE$
$FILEABBREV$
A
B
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING
DOCUMENT WAS PREPARED BY ME OR UNDER MY
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ARIZONA.
ENTER NAME
ENTER DATE
IS: ENTER DATE
$TIME$
$PINFO1$
Form GDG-0401-01-08, ANSI (Imperial) MicroStation Border - Size E - 34 x 44
Revision 11A, Revision Date: 04-30-2010
SARGENT & LUNDY
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-2552
0C
0A
1
1
03/31/23
D-E-2552.dwg
NTS
WAVEGUIDE BRIDGE
FOR APS REVIEW
PLAN VIEW & ELEVATION VIEW
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPBXXX
FOR PERMIT APPLICATION
C5551
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)
REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY
OF ALL PEOPLE LOCATED ON THE WORK SITE,
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL
(OR THAT OF ITS SUB-CONTRACTOR(S))
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS
DRAWING BY AN ORGANIZATION OTHER THAN
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY
OF SARGENT & LUNDY.
1
$DATE$
$FILEABBREV$
A
B
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING
DOCUMENT WAS PREPARED BY ME OR UNDER MY
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ARIZONA.
ENTER NAME
ENTER DATE
IS: ENTER DATE
$TIME$
$PINFO1$
Form GDG-0401-01-08, ANSI (Imperial) MicroStation Border - Size E - 34 x 44
Revision 11A, Revision Date: 04-30-2010
SARGENT & LUNDY
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-4503
0C
0A
03/31/23
D-E-4503.dwg
1"=1'-0"
RF SAFETY EXPOSURE
FOR APS REVIEW
WARNING SIGNS, LABELS PLACARDS
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPB/XXX
FOR PERMIT APPLICATION
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)
REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY
OF ALL PEOPLE LOCATED ON THE WORK SITE,
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL
(OR THAT OF ITS SUB-CONTRACTOR(S))
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS
DRAWING BY AN ORGANIZATION OTHER THAN
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY
OF SARGENT & LUNDY.
1
$DATE$
$FILEABBREV$
A
B
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING
DOCUMENT WAS PREPARED BY ME OR UNDER MY
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ARIZONA.
ENTER NAME
ENTER DATE
IS: ENTER DATE
$TIME$
$PINFO1$
Form GDG-0401-01-08, ANSI (Imperial) MicroStation Border - Size E - 34 x 44
Revision 11A, Revision Date: 04-30-2010
SARGENT & LUNDY
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-4504
0C
0A
05/11/23
D-E-4504.dwg
NTS
LATTICE TOWER
FOR APS REVIEW
OBSTRUCTION LIGHTING DETAILS
A13498.001
0B
06/08/23
FOR PERMIT APPLICATION
DELANEY SUBSTATION
0C
08/21/23
DCRT MW TOWER
MDL/XXX
FOR PERMIT APPLICATION
MPB/XXX
FOR PERMIT APPLICATION
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)
REVISION
DRAWING NUMBER
DRAWING TITLE
CAD FILE NAME:
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DATE
DESCRIPTION
RELEASE INFORMATION
DESCRIPTION
HOLD INFORMATION
CONTRACTOR/INSTALLER SHALL TAKE ALL
APPROPRIATE PRECAUTIONS TO ENSURE THE SAFETY
OF ALL PEOPLE LOCATED ON THE WORK SITE,
INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL
(OR THAT OF ITS SUB-CONTRACTOR(S))
PERFORMING THE WORK.
SHEET
OF
REV.
NO.
CIELO AZUL
SPECIFICATION:
ISSUE PURPOSE:
PROJECT NO.:
1
ANY MODIFICATION OR ADDITION TO THIS
DRAWING BY AN ORGANIZATION OTHER THAN
SARGENT & LUNDY, IS NOT THE RESPONSIBILITY
OF SARGENT & LUNDY.
1
A
C
D
E
I HEREBY CERTIFY THAT THIS ENGINEERING
DOCUMENT WAS PREPARED BY ME OR UNDER MY
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS
MY LICENSE RENEWAL DATE
THIS DOCUMENT ONLY.
PAGES OR SHEETS COVERED BY
THIS SEAL:
3
4
5
6
7
2
1
7
6
5
4
3
2
E
D
C
B
A
OF THE STATE OF ENTER NAME.
ENTER NAME
ENTER DATE
IS: ENTER DATE
B
SARGENT & LUNDY
55 EAST MONROE STREET
CHICAGO, ILLINOIS 60603-5780
DCR TRANSMISSION
DCR Transmission, L.L.C.
D-E-1502
0A
0A
08/21/23
D-E-1501.DWG
1"=10'-0"
MICROWAVE YARD LAYOUT
FOR PERMIT APPLICATION
DELANEY SUBSTATION
DCR TRANSMISSION
A13498.001
DELANEY SUBSTATION
DCRT MW TOWER
MDL/XXX
MPB/XXX
FOR PERMIT APPLICATION
CERTIFICATE OF AUTHORIZATION (WHEN REQ'D)
Delaney Colorado River Transmission, L.L.C.
Rev1
August 22, 2023
Project No.: 13498.001
55 East Monroe Street
Chicago, IL 60603-5780 USA
312-269-2000
www.sargentlundy.com
Maricopa County Special Use Permit
Project Narrative
Delaney Substation Communication Tower
45550 W Salome Hwy
Tonopah, AZ 85354
Tracking # PA2023070
DCR Transmission L.L.C.
Delaney Communication Tower
A13498.001
Rev1
August 22, 2023
Maricopa County Special Use Permit
Pre-Application Package
P. 1
L E G A L N O T I C E
This deliverable was prepared by Sargent & Lundy, L.L.C. (“S&L”) expressly for the sole use of DCR
Transmission, L.L.C. (“Client”) in accordance with the contract agreement between S&L and Client. This
deliverable was prepared using the degree of skill and care ordinarily exercised by engineers practicing
under similar circumstances. Client acknowledges: (1) S&L prepared this deliverable subject to the particular
scope limitations, budgetary and time constraints, and business objectives of Client; (2) information and data
provided by others, including Client, may not have been independently verified by S&L; and (3) the
information and data contained in this deliverable are time-sensitive and changes in the data, applicable
codes, standards, and acceptable engineering practices may invalidate the findings of this deliverable. Any
use or reliance upon this deliverable by third parties shall be at their sole risk.
DCR Transmission L.L.C.
Delaney Communication Tower
A13498.001
Rev1
August 22, 2023
Maricopa County Special Use Permit
Pre-Application Package
P. 2
V I C I N I T Y M A P
DCR Transmission L.L.C.
Delaney Communication Tower
A13498.001
Rev1
August 22, 2023
Maricopa County Special Use Permit
Pre-Application Package
P. 3
DCR Transmission L.L.C.
Delaney Communication Tower
A13498.001
Rev1
August 22, 2023
Maricopa County Special Use Permit
Pre-Application Package
P. 4
P R O J E C T N A R R A T I V E
DCR Transmission L.L.C.
Delaney Communication Tower
A13498.001
Rev1
August 22, 2023
Maricopa County Special Use Permit
Pre-Application Package
P. 5
Introduction
DCR Transmission, L.L.C. (“DCRT”), an affiliate of Lotus Infrastructure Partners, is a transmission utility in
the state of California and will be a Participating Transmission Owner under the jurisdiction of the Federal
Energy Regulatory Commission.
DCRT seeks a Special Use Permit (“SUP”) from Maricopa County for the installation of a new microwave
communication tower and associated infrastructure (“Project”) in Maricopa County, Arizona, on land leased
from Arizona Public Service Company (“APS”). This project narrative was prepared by Sargent and Lundy to
support DCRT’s SUP Application.
The tower would be built immediately adjacent to APS’s existing Delaney Substation, which is located at
45550 W Salome Highway, Tonopah, AZ, 85354. Lease negotiations are currently underway with APS, who
is aware of and supportive of DCRT’s Special Use Permit application.
Purpose of Request
The purpose of the Project is to establish the required communication between the existing Southern
California Edison (“SCE”) Colorado River Substation (“CRS”), the series compensation station (“SCS”)
associated with Ten West Link 500 kV transmission line (“Ten West Link”), the new 500 kV Cielo Azul
switchyard (“Cielo Azul” or “Switchyard”) located in La Paz County, Arizona, the Atlas Solar Project (a
renewable energy project proposing to connect to Cielo Azul) and Delaney Substation (Figure 1).
Establishing this telecommunications system will assist in satisfying the communication requirements
associated with the interconnection of the Atlas Solar Project and the new renewable energy facilities
proposing to connect to the Switchyard to the bulk transmission grid via Ten West Link. This new
communication path is required to support the System Protection and is an essential element to maintain the
reliability of the bulk transmission network serving California and Arizona.
Figure 1. Microwave Communication Path
DCR Transmission L.L.C.
Delaney Communication Tower
A13498.001
Rev1
August 22, 2023
Maricopa County Special Use Permit
Pre-Application Package
P. 6
Description of Proposal
The proposed Project would be located on the southwest corner of Delaney Substation, outside of the
existing substation fence line, as shown on the preliminary Site Plan included in this package. The parcel is
zoned Rural-43 with a land use of “Other Employment”( Maricopa County Planning and Development
Department, 2023; Maricopa Association of Governments, 2023). On Maricopa County planning documents,
the land use is listed as “Vacant/APS Substation” (Maricopa County Planning and Development Department,
2019). The proposed Project footprint has previously been disturbed and is covered with aggregate stone.
The proposed Project consists of the following:
•
A single 250-foot self-support microwave communication tower with a 10-foot lightning rod (total
height 260 feet above ground level (“agl”)).
o
The proposed microwave communication tower will have two antennas: one located at 245
feet agl and one located at 215 feet agl. Additional antennas may be added to the tower in
the future.
o
The tower will be constructed of galvanized steel, which will be grey in color and will
naturally dull over the course of a year or less as the galvanizing is exposed to natural
weathering conditions.
o
The tower will be marked/lighted in accordance with FAA Advisory circular 70/7460-1 M,
Obstruction Marking and Lighting, a med-dual system-Chapters 4, 8 (M-Dual), & 15. This
will include infrared as well as signal lighting.
•
9-foot by 19-foot communication enclosure. Shelter height will be approximately 14 feet agl. The
below details are from the Communication Shelter Specification for the Project:
o
The equipment supplied shall be of metal construction and shall be self-supporting and free
standing. All metal work shall be free from burrs and sharp edges. Elements may be
connected by bolts, thread forming screws, or welds.
o
The Communication Shelter shall be fabricated as heavy duty, fire resistant and non-
combustible construction. The shelter walls shall provide a two-hour fire rating.
•
An approximately 30 kW diesel-powered emergency generator set.
•
APS will provide station power.
•
Sign and fence details are included in the Site Plan and design drawings included in this
application.
•
There will be no landscaping – disturbed areas will be restored to be consistent with the current
land cover (gravel).
•
Access to the SUP area will be via the existing Delaney Substation driveway. APS holds an existing
right-of-way for this driveway from Arizona State Land Department.
The permanent Project footprint will be approximately 0.08 acres, which will be finished with aggregate stone
at the completion of construction. Additionally, a temporary laydown area comprising 0.34 acres will be
DCR Transmission L.L.C.
Delaney Communication Tower
A13498.001
Rev1
August 22, 2023
Maricopa County Special Use Permit
Pre-Application Package
P. 7
required during construction. Access to the Project will be via the existing access road to Delaney Substation
and a proposed shared access road along the southern edge of the substation parcel.
The project would be operational 24/7. The facility will not be manned; however, maintenance and
inspections of the proposed Project would be performed on a routine basis in accordance with industry
standards and manufacturer guidelines.
Relationship to Surrounding Properties
Existing on-site and surrounding zoning and land use is as follows (Maricopa County Planning and
Development Department, 2023; Maricopa Association of Governments, 2023):
On-site:
Rural-43/Vacant, APS Substation
North:
IND-2/Vacant
South:
Rural-43/Vacant
East:
Rural-43/Vacant
West:
IND-2/Vacant
There are no wireless communication facilities within a 1,000-foot radius of the site. The proposed Project is
consistent with the current land use at the property, which is an existing electrical substation. Access along
the Delaney Substation driveway and the Maricopa County 40’ ROW reservation will be maintained.
There are no residential uses within a mile of the proposed tower location. Based on the Maricopa County
Planning and Development PlanNet website, the nearest residences are located on land that is zoned Rural-
43 and are 1.7 miles to the northeast. The nearest residential-zoned parcels are over 3 miles to the west-
south-west. Therefore, there are no compatibility issues with setbacks from current residential uses
(Maricopa County Planning and Development Department, 2023).
In recent years, the parcels located north, west, and south of the Project have applied for amendments and
rezonings in order to allow for solar development:
•
The property to the south of the site received a Comprehensive Plan Amendment in 2011
(CPA2011012) for a solar generating facility, with a land use change from Rural Development Area
to Industrial (Figure 2)(Maricopa County Planning and Development Department, 2023).
•
The property to the north and west of the site obtained a Comprehensive Plan Amendment
(CPA2019012) in 2021 changing the land use designation in the Tonopah/Arlington Area Plan from
Rural to Utilities (Figure 2). The same property to the north and west requested, and received, a
rezoning in 2019. The zoning was changed from Rural-43 to IND-2 IUPD in order to develop a
utility-scale solar facility (rezoning case Z2019121) (Figure 3) (Maricopa County Planning and
Development Department, 2023).
The proposed Project consists of required communications infrastructure to support the interconnection of
the Atlas Solar Project and other planned renewable energy to the bulk transmission grid via the Cielo Azul
Switchyard and Ten West Link.
Taken together, the Project and Ten West Link will improve transmission system efficiency and reliability
DCR Transmission L.L.C.
Delaney Communication Tower
A13498.001
Rev1
August 22, 2023
Maricopa County Special Use Permit
Pre-Application Package
P. 8
within the fast-growing region. Additionally, they will facilitate development of new renewable energy and
energy storage resources in Arizona and California, thereby helping both states achieve their renewable
energy standards and carbon reduction goals.
Figure 2 – Comprehensive Plan Amendments in the Vicinity of the Project
Note: Areas in purple have received a comprehensive plan amendment, as described in the “Relationship to Surrounding Properties”
section.
DCR Transmission L.L.C.
Delaney Communication Tower
A13498.001
Rev1
August 22, 2023
Maricopa County Special Use Permit
Pre-Application Package
P. 9
Figure 3 – Re-Zoning in the Vicinity of the Project
Note: Areas in yellow have been re-zoned, as described in the “Relationship to Surrounding Properties” section.
Location and Accessibility
An existing APS access road that runs along the southern portion of the Delaney substation property will be
used to access the site during construction, and to access the site during operation of the facility. Access to
existing APS access roads will be via W Salome Highway, approximately 0.4 miles south-southeast of the
site. Access along these shared access roads will be preserved throughout construction and operations.
The area around the proposed communication tower will be fenced to prevent public or wildlife access. A
fence is preferred by the proponent instead of a security wall.
Circulation System
Not applicable.
Development Schedule
DCR Transmission L.L.C.
Delaney Communication Tower
A13498.001
Rev1
August 22, 2023
Maricopa County Special Use Permit
Pre-Application Package
P. 10
Construction of the tower is scheduled to commence in late 2023 and would last from one to three months.
Community Facilities and Services
Elementary School District: District 47 – Arlington Elementary School District
High School District: District 1 – Buckeye Union High School District
Public Utilities and Services
DCRT will enter into an agreement with APS to receive electrical service. Additionally, a fiber connection will
be established between the Project microwave shelter and Delaney substation. No water or sewer
connections would be built, and no garbage disposal services would be necessary. The Project is located
outside of any fire district. The Project is within District 2 of the Maricopa County Sherriff’s office.
Other Information
The facility would not serve in-person customers. There would be no food service for the proposed use.
There would be no new parking built for the project. The project is not located within any flood zones,
washes, or canals, and is on a relatively flat parcel.
A stealth design is not being considered, as it is not feasible for such a large lattice structure. There are no
trees/windmills in the vicinity for the tower to blend in with a stealth design. The tower will be consistent with
existing structures at and around the Delaney yard.
Contact Information
To discuss this application, please contact the below representatives:
DCRT Contact
Name: Randy Schulze
Email: rschulze@cbxinternational.net
Phone: 303-674-0551
APS Contact
Name: Paul Baumgardt
Email: paul.baumgardt@aps.com
Phone: 602-371-7849
Sargent & Lundy Contact
Name: Julianna Crumlish
Email: julianna.r.crumlish@sargentlundy.com
Phone: 312-269-2144
DCR Transmission L.L.C.
Delaney Communication Tower
A13498.001
Rev1
August 22, 2023
Maricopa County Special Use Permit
Pre-Application Package
P. 11
R E F E R E N C E S
Maricopa Association of Governments, 2023. “Land Use Explorer.” Web Mapping Application,
https://geo.azmag.gov/maps/landuse/. Accessed 5 May 2023.
Maricopa County Planning and Development Department, 2019. “Report to the Planning and Zoning Commission, Case:
CPA2019012 – Papago Solar.” Hearing Date: December 12, 2019.
Maricopa County Planning and Development Department, 2022. “Zoning Ordinance (P-18)”, Ordinances, Regulations
and Codes. https://www.maricopa.gov/2271/Ordinances-Regulations-and-Codes. Dated March 11, 2022.
Maricopa County Planning and Development Department, 2023. “PlanNet.” ArcGIS Web Application,
https://maricopa.maps.arcgis.com/apps/webappviewer/index.html?id=3fd3476aa2394fdabc510bee4bcf5c71. Accessed
30 May 2023.
Krystina Aragon, PE
Planning & Development
301 W. Jefferson St., Suite 170
Phoenix, Arizona 85003
Phone: (602) 506-8790
www.maricopa.gov/planning
Email address:
krystina.aragon@maricopa.gov
Planning & Development
Engineering Plan Review
Date:
September 5, 2023
Memo To:
Darren Gerard, Planning Manager, Planning & Development
Attn:
Andrew Lorentzen, Planner, Planning and Development
From:
Krystina Aragon, PE, Plans Examiner Engineer, Planning and Development
cc:
Michael Norris, P.E., Engineering Manager, Planning and Development
Subject:
Z2023088 – SUP for Delaney Substation Communication Tower
(E1 Memo)
Job Site Address:
45550 W Salome Hwy, Tonopah
APN(s):
506-31-006D
PND engineering plan review (DPR, FCD and PND Transportation) has reviewed the 2nd
submittal of the SUP application routed for review on August 25, 2023. PND Engineering has
no comments or objections subject to the following conditions:
1. A section line , Thomas Road, coincides with the south boundary of the parcel. Per an
approval of reduction, a 40-foot reservation will be required for Thomas Road.
2. A mid-section alignment is located on the eastern perimeter of the proposed
development requiring building setbacks to start from a future half street of 40-feet per
the Maricopa County Zoning and Ordinance Section 11105.
3. All development and engineering design shall be in conformance with Section 1205 of the
Maricopa County Zoning Ordinance; Drainage Policies and Standards; Floodplain
Regulations for Maricopa County; MCDOT Roadway Design Manual; and current
engineering policies, standards and best practices at the time of application for
construction.
4. Engineering review of planning and/or zoning cases is for conceptual design only and
does not represent final design approval nor shall it entitle applicants to future designs
that are not in conformance with Section 1205 of the Maricopa County Zoning Ordinance
and Drainage Policies and Standards; Floodplain Regulations for Maricopa County; and
the MCDOT Roadway Design Manual.
5. Detailed Grading and Drainage Plans showing the new site improvements must be
submitted for the acquisition of building permits.
Please contact me if you have any questions or require any additional information.
1
Andrew Lorentzen (PND)
From:
RAHN, JENNIFER L CIV USAF AETC 56 FW/CVE <jennifer.rahn@us.af.mil>
Sent:
Monday, August 7, 2023 3:00 PM
To:
Andrew Lorentzen (PND)
Cc:
56 FW/CIT Community Initiative
Subject:
RE: Z2023088 - Delaney Substation Communication Tower Special Use Permit Application
Good afternoon Mr. Lorentzen,
Thank you for the opportunity to provide comments on the Special Use Permit for the proposed Delaney Substation
Communication Tower. The site is approximately 0.7 acres and is located at 45550 W. Salome Highway in
unincorporated Maricopa County, AZ. The developer is proposing a 250ft microwave tower with additional 10ft
lightening rod at the SW corner of the property boundary (APN: 506‐31‐006D). The parcel in the application is located
outside of the Luke AFB 1988 JLUS 65 Ldn “high noise or accident potential zone” as identified by A.R.S. § 28‐8461 and is
within the “territory in the vicinity of a military airport” defined by A.R.S. § 28‐8461.
Subject to the results of an FAA Obstruction Evaluation/Airport Airspace and Spectrum Analysis (OE/AAA), this request,
as described in the narrative, will not negatively impact the flying and base operations at Luke AFB. We do however
request the installation of an Aviation Obstruction Light (AOL) or Aircraft Warning Light (ACWL) due to its height and
location. Approved lighting includes L‐810 red lighting in accordance with AC 70/7460‐1M. Lighting will increase
operational awareness of the tower location. The night vision goggle (NVG) compliant L‐810 red light is comprised of
visible red emitters and infrared (IR) emitters for pilot safety.
Since the site will be located within the “territory in the vicinity of a military airport,” it will be subjected to
approximately 170 over flights per day. We recommend a strong notification program on part of the County to inform
the applicant about Luke AFB operations.
V/r,
Jenn Rahn
Senior Planner, Community Initiatives Team
56th Fighter Wing
Luke AFB AZ 85309
Office: 623‐856‐9981
DSN: 896‐9981
From: Andrew Lorentzen (PND) <Andrew.Lorentzen@maricopa.gov>
Sent: Thursday, July 27, 2023 2:31 PM
To: tvcc.events@gmail.com; dmheisler1@aol.com; ronsatt@ev1.net; proetto1950@gmail.com; twilliford@azgfd.gov;
tstruck@azgfd.gov; tsprague@azgfd.gov; pep@azfgd.gov; 56 FW/CIT Community Initiative
<56FW.CIT.CommunityInitiative@us.af.mil>; swilken@azmag.gov; kcotner@azmag.gov; agarza@azmag.gov;
pe@azland.gov; bfenske@azdot.gov; jgarcia@azdot.gov; redletter@azdot.gov; gramirez@azdot.gov;
Dkrantz@citytocitycre.com; jcrew@lotuspartners.com
Subject: [URL Verdict: Neutral][Non‐DoD Source] Z2023088 ‐ Delaney Substation Communication Tower Special Use
Permit Application
2
Hello Registered Area of Interest Member,
Please find attached a planning & development application routing for Z2023088 - Delaney Substation
Communication Tower Special Use Permit.